| 2005-07-27 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- STORM SHUTTERS: A) PROVIDE KEY PLAN |
| | AND COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. |
| | B) CIRCLE ON SHUTTER DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS, TYPE OF ANCHOR AND |
| | SPACING TO BE USED ACCORDING TO THE |
| | DESIGN PRESSURES, THE EDGE DISTANCE, |
| | PANEL SPAN, CONNECTION TYPE AND |
| | STRUCTURE TO BE ATTACHED TO (MASONRY OR |
| | CONCRETE). |
| | C) PROVIDE 2 COPIES OF PRODUCT APPROVAL |
| | AND INFORMATION REQUESTED ABOVE. |
| | |
| | 2- ENGINEER TO PROVIDE CALCULATIONS TO |
| | DETERMINE TYPE, SIZE AND THICKNESS OF |
| | GLASS TO RESIST THE CALCULATED DESIGN |
| | PRESSURES. CALCULATIONS SHALL BE BASED |
| | ON ASTM E 1300 1994 EDITION AS REQUIRED |
| | BY CHAPTER 35 FBC 2001 AND SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | *NOTE: INFORMATION WRITTEN ON PRODUCT |
| | APPROVAL PAGE 5 OF 8 TO BE ON ENGINEER |
| | OF RECORD DRAWINGS, NOT IN THE PRODUCT |
| | APPROVAL. SIZE OF WINDOW DOESN'T MATCH |
| | PLANS AND NEED TO USE ASTM E 1300 1994 |
| | EDITION. |
| | |
| | |
| | 3- SPECIFY GLASS SUPPORTS AS REQUIRED BY |
| | SEC. 2406.1 FBC 2001 FOR DEFLECTION |
| | CONSIDERATION. |
| | |
| | 4- SPECIFY STRUCTURAL BUCK DETAILS FOR |
| | WINDOW ATTACHMENT. SEC. 1707.4.4 FBC. |
| | |
| | 5- SIZE OF WINDOW SHOWN ON WALL SECTION |
| | DOESN'T MATCH SIZE SHOWN ON FLOOR PLAN. |
| | ALSO, SIZE SHOWN ON FLOOR PLAN DOESN'T |
| | CORRESPOND TO SIZE SHOWN ON FRONT |
| | ELEVATION. REVISE AS REQUIRED. |
| | |
| | 6- PROVIDE RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |