Plan Review Notes
Plan Review Notes For Permit 05070693
Permit Number 05070693
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-27 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- STORM SHUTTERS: A) PROVIDE KEY PLAN
 AND COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
 B) CIRCLE ON SHUTTER DRAWINGS SPECIFIC
 MOUNTING CONDITIONS, TYPE OF ANCHOR AND
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, THE EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (MASONRY OR
 CONCRETE).
 C) PROVIDE 2 COPIES OF PRODUCT APPROVAL
 AND INFORMATION REQUESTED ABOVE.
  
 2- ENGINEER TO PROVIDE CALCULATIONS TO
 DETERMINE TYPE, SIZE AND THICKNESS OF
 GLASS TO RESIST THE CALCULATED DESIGN
 PRESSURES. CALCULATIONS SHALL BE BASED
 ON ASTM E 1300 1994 EDITION AS REQUIRED
 BY CHAPTER 35 FBC 2001 AND SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 *NOTE: INFORMATION WRITTEN ON PRODUCT
 APPROVAL PAGE 5 OF 8 TO BE ON ENGINEER
 OF RECORD DRAWINGS, NOT IN THE PRODUCT
 APPROVAL. SIZE OF WINDOW DOESN'T MATCH
 PLANS AND NEED TO USE ASTM E 1300 1994
 EDITION.
  
  
 3- SPECIFY GLASS SUPPORTS AS REQUIRED BY
 SEC. 2406.1 FBC 2001 FOR DEFLECTION
 CONSIDERATION.
  
 4- SPECIFY STRUCTURAL BUCK DETAILS FOR
 WINDOW ATTACHMENT. SEC. 1707.4.4 FBC.
  
 5- SIZE OF WINDOW SHOWN ON WALL SECTION
 DOESN'T MATCH SIZE SHOWN ON FLOOR PLAN.
 ALSO, SIZE SHOWN ON FLOOR PLAN DOESN'T
 CORRESPOND TO SIZE SHOWN ON FRONT
 ELEVATION. REVISE AS REQUIRED.
  
 6- PROVIDE RECORDED NOTICE OF
 COMMENCEMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.