| 2006-03-24 00:00:00 | ROOF REVIEW |
| | NOA 03-0114.06, SANTAFE TILE CORPORATION |
| | MISSION BARREL ROOFING TILE |
| | |
| | FLAT DECK - FL735, TAMKO MODIFIED, |
| | NOA01-1011.03 |
| | |
| | |
| 2006-03-23 00:00:00 | ****PROVISO ITEMS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | PROVISO ITEMS: |
| | |
| | 1.)REVISE THE LANDSCAPE AND CIVIL |
| | SHEETS TO SHOW THE NEW SIDEWALK AS |
| | REQUESTED.NOTE THAT THE SIDEWALK IS |
| | PLACED WHERE A MAHOGANY TREE IS LOCATED. |
| | |
| | 2.)REVISE THE LIFE SAFETY PLAN TO SHOW |
| | ALL REQUIRED EXIT LIGHTS.THE DISTANCE |
| | BETWEEN THE REMOTELY LOCATED EXITS |
| | SHOULD BE THE TWO ACCESSIBLE EXITS. |
| | |
| | 3.)SUBMIT A LETTER FROM THE ENGINEER |
| | CONFIRMING THAT NONE OF THE OPENINGS ARE |
| | IN ZONE 5. |
| | |
| | 4.)PROVIDE THE CHANGE OF CONTRACTOR |
| | FORM BEFORE FIRST INSPECTION. |
| | |
| | 5.)THE FIRE SPRINKLER CALCS ARE TO BE |
| | EITHER SIGNED AND SEALED EACH SHEET OR |
| | HAVE AN INDEX SHEET.THE INFORMATION |
| | REQUIRED (PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT, PRINTED LICENSE |
| | NUMBER OF THAT INDIVIDUAL, AND CA NUMBER |
| | FOR THE FIRM) IS LACKING.SEE |
| | FAC61G15-23. |
| | |
| | 6.)INDICATE WHICH APPROVED ASSEMBLY |
| | YOU ARE INSTALLING (MODIFIED ROOF). |