| 2006-01-31 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A. FROM PREVIOUS REVIEWS: COMMENT |
| | NUMBERS TO REMAIN THE SAME AS PRIOR |
| | REVIEWS. |
| | |
| | 1. SHT A-1 FINISH SCHEDULE SHOWS GYP-BD |
| | PAINTED FOR THE WALLS OF THE TOILET |
| | ROOMS. PLEASE INDICATE HOW THIS WILL |
| | COMPLY WITH THE REQUIREMENT FOR THE |
| | WALLS TO BE NONABSORBENT UP TO 4' IN |
| | PUBLIC TOILET ROOMS. SECTION 1204.2 |
| | FBC-2001 BUILDING. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | 3. SHT A-7 ALL TOILET ROOMS, (INCLUDING |
| | EMPLOYEES), SHALL BE ACCESSIBLE. SHOW |
| | THE FOLLOWING: |
| | FOR LAVS: |
| | C. 11-4.19.2 HEIGHT & CLEARANCES |
| | (CLEARANCES NOT SHOWN) |
| | F. 11-4.19.5 FAUCETS |
| | FOR TOILET ROOMS: |
| | 11-4.22.3 UNOBSTRUCTED TURNING AREA - |
| | FOR EMPLOYEES TOILET ROOM. |
| | 4. SHTS P-1 & P-3 THE OIL SEPARATOR |
| | SHALL BE SIZED BY LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE |
| | CONTACT HER AT (561) 822-2271, FAX (561) |
| | 822-2279, OR E-MAIL [email protected]. |
| | WASTE ORD. #3434. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | 6. P-3 INDICATE MATERIAL TYPE FOR |
| | COMPRESSED AIR SYSTEM PIPING. PVC NOT |
| | APPROVED FOR COMPRESSED AIR PER MANUF. |
| | INSTALLATION REQUIREMENTS. TYPICAL AIR |
| | LINE RISER SHOWS 2" PVC TO LIFT. THIS IS |
| | NOT APPROVED. (NO RESPONSE, NOT |
| | ADDRESSED). SEE DETAIL SHT P-2 |
| | **NOTE FROM SECOND REVIEW** |
| | SECTION 310.4 WATER CLOSET COMPARTMENT. |
| | EXCEPTION: WATER CLOSET COMPARTMENTS |
| | SHALL NOT BE REQUIRED IN A SINGLE - |
| | OCCUPANT TOILET ROOM WITH A LOCKABLE |
| | DOOR. "INCLUDE ALL NOTES ON PLANS". |
| | ****NEW COMMENT**** |
| | 1C. SEE ATTACHED SHEET CONCERNING FS |
| | 533.80(2)(B) AND THE DESIGN |
| | PROFESSIONAL. IF PLANS ARE RESUBMITTED |
| | AND HAVE NOT ADDRESSED THE COMMENTS FROM |
| | PREVIOUS REVIEWS, 4 TIMES THE PLAN |
| | REVIEW FEE WILL BE ATTACHED AND BE |
| | REQUIRED TO BE PAID BY THE DESIGN |
| | PROFESSIONAL. THIS WILL BE IN ADDITION |
| | TO THE 4 TIMES FEE REQUIRED BY THE |
| | BUILDING PLANS EXAMINER. |
| | |
| | |