Plan Review Notes
Plan Review Notes For Permit 05070691
Permit Number 05070691
Review Stop B
Sequence Number 3
Notes
Date Text
2005-12-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 COMMENTS FROM PREVIOUS REVIEWS,
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.MISSING NUMBERS INDICATE
 COMMENTS WHICH WERE ADDRESSED CORRECTLY.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025 FOR MORE
 INFORMATION.
  
 9.)(SECOND REVIEW) . . . THE CALCS
 REFER TO THE 2003 FBC, GOVERNING CODE IS
 FBC2001.
  
 (THIRD REVIEW)GOVERNING CODE STILL
 STATES 2003 FBC.PLEASE REVISE.
  
 11.)HURRICANE SHUTTER STORAGE IS SHOWN
 ON THE PLAN (TIRE STORAGE AREA).SEE
 ATTACHED IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13.SUBMIT A PLAN FOR
 INSTALLATION FOR REVIEW.
  
 (SECOND REVIEW) NOT ADDRESSED.USE OF
 REMOVABLE SHUTTERS AND THE INSTALLATION
 PLAN IS TO BE APPROVED BY THE BUILDING
 OFFICIAL.
  
 (THIRD REVIEW) RESPONSE LETTER PROVIDED
 SOME INFORMATION IN REGARDS TO SHUTTER
 INSTALLATION.THIS IS NOT AN
 INSTALLATION PLAN.PLEASE PROVIDE A
 PLAN AS REQUESTED WITH ALL NECESSARY
 INFORMATION TO SHOW COMPLIANCE WITH THE
 POLICY AND SUBMIT.THIS PLAN WILL BE
 REVIEWED FOR COMPLETENESS PRIOR TO
 SUBMITTAL TO THE BUILDING OFFICIAL, WHO
 WILL MAKE DETERMINATION AS TO WHETHER OR
 NOT APPROVAL IS GRANTED.THE PLAN IS TO
 BE APPROVED PRIOR TO PERMIT ISSUANCE OR
 THE PLAN IS TO BE REVISED FOR IMPACT
 GLASS.
  
 12.)SEE PROCEDURES, ITEM I, ON THE
 ATTACHED STANDARD IN REGARDS TO REQUIRED
 INFORMATION.A FORM IS ATTACHED FOR
 YOUR CONVENIENCE.
  
 (SECOND REVIEW)NOT ADDRESSED.FORM
 WAS RETURNED BLANK.
  
 (THIRD REVIEW)THIS CANNOT BE ISSUED AS
 SUBMITTED UNTIL AN INSTALLATION PLAN HAS
 BEEN APPROVED BY THE BUILDING OFFICIAL.
  
 13.)ONLY ONE ACCESSIBLE EXIT IS SHOWN
 FROM THE SERVICE AREA AND THE TIRE
 STORAGE FBC11-4.11(3), FBC1004.2.2.
  
 (SECOND REVIEW) SAME PLANS PROVIDED.
 NOTE THAT EXIT 2HAS A RAMP, EXITS 3 AND
 4 HAVE STEPS.THE RESPONSE LETTER
 STATES THAT DOORS 107 AND 108 ARE
 ACCESSIBLE EGRESS DOORS. DOOR 107 IS AN
 INTERIOR DOOR, IS NOT AN EXIT.DOOR 108
 HAS A STEP DOWN, NOT AN ACCESSIBLE EXIT.
  
 (THIRD REVIEW)THE RESPONSE LETTER
 STATES THAT DOORS 101, 107 AND 110 ARE
 ACCESSIBLE EXITS.PLEASE NOTE THE
 FOLLOWING:
  
 DOOR 107 IS NOT AN EXIT, IT IS AN
 INTERIOR DOOR LEADING TO THE WORK AREA.
 SEE FBC CHAPTER 2, DEFINITIONS.
  
 DOORS 107 AND 110 ARE 40 FEET APART.
 THEY DO NOT COMPLY WITH FBC1004.1.4, THE
 REQUIREMENT TO BE REMOTELY LOCATED.
  
 **NOTE - PER ARCHITECT, THE SECOND
 ACCESSIBLE EXIT IS TO BE DOOR 108, WHICH
 WILL BE REVISED TO ELIMINATE THE DOOR
 LANDING.**PLEASE NOTE THAT THE CIVILS
 WILL BE REQUIRED TO BE UPDATED AS WELL
 TO BE CONSISTENT WITH THE
 ARCHITECTURALS.
  
 14.)PROVIDE A DETAIL FOR THE SALES
 COUNTER, FBC11-7.2.
  
 THE RESPONSE LETTER INDICATES THAT SHOP
 DRAWINGS WILL BE SUBMITTED.THE PERMIT
 WILL BE ISSUED WITH THIS AS A PROVISO.
  
 16.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FAC9B72 IN ADDITION
 TO EVALUATION OR TEST REPORT.SUBMIT
 FOR THE FOLLOWING:
  
 ROOF, FLAT - OK
 ROOF, TILE - OK
 EIFS SYSTEM -
 OVERHEAD DOOR - DOES NOT MEET DP
 METAL DOORS - DOES NOT MEET DP
 STOREFRONT - CANNOT BE APPROVED UNTIL
 AFTER BUILDING OFFICIAL APPROVES USE OF
 REMOVABLE SHUTTERS AND ENGINEER
 SPECIFIES DP.INDICATE DP LIMITATION OF
 YOUR APPLICATION ON SHEETS 4 AND 5 OF
 THE NOA.
  
 WWW.FLORIDABUILDING.ORG
  
 THE HURRICANE SHUTTER PRODUCT APPROVALS
 SUBMITTED MUST INCLUDE THE SCHEDULE FOR
 INSTALLATION, SEE ITEM 12.
  
 THE INSTALLATION SPECIFIES THE SAME SIZE
 SHUTTER AS THE OPENING SIZE FOR ALL
 OPENINGS, DOES NOT STATE IF THEY ARE TO
 BE INSTALLED VERTICALLY OR HORIZONTALLY.
  
 THE SWINGING DOOR DOES NOT MEET THE DP
 SPECIFIED ON S-0.
  
 (SECOND REVIEW)THE PRODUCT APPROVALS
 FOR THE CLOPAY
 OVERHEAD DOORS HAS A DESIGN PRESSURE
 LIMITATION OF +37/-42.ALSO STATES ON
 THE SPEC SHEET THAT IT IS COMPLIANT FOR
 150MPH EXPOSURE B, YOUR BUILDING HAS
 BEEN DECLARED AS EXPOSURE D.
  
 (THIRD REVIEW)THE NEW PRODUCT APPROVAL
 SUBMITTED HAS A DP LIMITATION OF
 +52/-58, SEE S-0.
  
 19.)PROVIDE DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING, ROOF.
  
 (SECOND REVIEW) THIS BUILDING HAS
 BEEN DECLARED AS
 150MPH EXPOSURE D DESIGN.THE DESIGN
 PRESSURE FOR A FLAT ROOF, ZONE 3, 150,
 EXPOSURE B IS -102.2.SEE FBC TABLE
 1606.2B, FBC1606.2D.THE DESIGN
 PRESSURES YOU HAVE PROVIDED ON S0, 59
 FOR END ZONES FOR OPENINGS, 68 FOR END
 ZONES FOR ROOF, ARE NOT COMPLIANT FOR
 150MPH EXPOSURE D.PLEASE REVISE OR
 CLARIFY AS TO HOW YOU HAVE ARRIVED AT
 THESE DESIGN PRESSURES.
  
 (THIRD REVIEW)IT IS STILL NOT CLEAR AS
 TO HOW YOU HAVE DETERMINED THE ROOF
 CLADDING DESIGN WIND PRESSURES, S0.YOU
 HAVE THIS BROKEN DOWN IN SQUARE FOOT
 AREAS, LEEWARD AND WINDWARD ZONES.I
 BELIEVE THIS MAY APPLY TO THE MWFRS BUT
 NOT TO THE ROOF, SEE FBC TABLE 1606.2B,
 TABLE 1606.2D, FIGURE 1606.2(C).
 REGARDLESS OF HOW YOU DERIVED THE
 NUMBERS ON SHEET S0, 105.2 PSF FOR 10SF
 OF AREA ROOF ZONE 3 IS NON COMPLIANT FOR
 150MPH EXPOSURE D (-102.2*155=158.41).
  
 20.)PROVIDE WIND DESIGN INFORMATION
 FBC1606.1.7.
  
 (SECOND REVIEW) I WAS UNABLE TO LOCATE
 THE INFORMATION.
 SOME OF THE INFORMATION IS ON THE PLAN
 IN VARIOUS PLACES BUT OTHER ITEMS ARE
 MISSING.
  
 (THIRD REVIEW)PLEASE ADD THE
 INFORMATION REQUIRED BY FBC1606.1.7(4).
 REVISE ROOF DESIGN PRESSURES AS NOTED IN
 19 ABOVE.
  
 NEW COMMENTS:
  
 21.)ADDRESSED.
  
 22.)WALL SECTIONS ON A5 SHOW A 21?
 TALL MASONRY WALL WITH NO INTERMEDIATE
 BEAM.3-A5 REFERS TO A BOND BEAM AT
 APPROXIMATELY 13?, AND STATES TO SEE
 STRUCTURALS.I AM UNABLE TO FIND THIS
 INTERMEDIATE BEAM AND IT IS NOT SHOWN
 GRAPHICALLY ON THE ARCHITECTURAL OR
 STRUCTURAL DETAILS.
  
 23.)A TABLE WAS PROVIDED WITH DESIGN
 PRESSURES BASED ON SIZE AND ZONE, S0.
 PROVIDE A SCHEDULE OF OPENINGS
 SPECIFYING DESIGN PRESSURES (OPENING;
 COMPONENT TYPE I.E. ROLLUP DOOR,
 STOREFRONT, ETC.; AND DESIGN PRESSURE
 FOR THAT OPENING).ALSO SPECIFY DP FOR
 EIFS.
  
 (SECOND REVIEW)SEE ATTACHED
 FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED AS REQUIRED
 BY FLORIDA STATE STATUTE IF ITEMS ARE
 NOT CORRECTLY ADDRESSED ON THE NEXT
 REVIEW.
  
 (THIRD REVIEW)A 4X FEE HAS BEEN
 CHARGED AS REQUIRED BY FLORIDA STATUTE.
 NO RESUB FEE WILL BE CHARGED.THE 4X
 FEE IS TO BE PAID PRIOR TO RESUBMITTAL.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved