2005-10-15 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1) NOTES 3 THRU 5 ON FROM PREVIOUS PLAN
 REVIEW, DATED 08-22-05 NEED TO BE PLACED
 ON THE PLANS, RE SUBMITTED.
 3)SHT A-7 ALL TOILET ROOMS,
 NEW NOTE:
 SEC 310.4 WATER CLOSET COMPARTMENT.
 EXCEPTION: WATER CLOSET COMPARTMENTS.
 SHALL NOT BE REQUIRED IN A SINGLE-
 OCCUPANT TOILET ROOM WITH A LOCKABLE
 DOOR.
 "INCLUDE ALL NOTES ON PLANS"
 4. SHTS P-1 & P-3 THE OIL SEPARATOR
 SHALL BE SIZED BY LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT HER AT (561) 822-2271, FAX (561)
 822-2279, OR E-MAIL [email protected].
 WASTE ORD. #3434.INC WITH PLANS
 5. RPZ BACKFLOW SHALL BE INSTALLED ON
 THE WATER SERVICE AS CLOSE TO THE METER
 AS POSSIBLE. PER UTILITY DEPT.
 6. P-3 INDICATE MATERIAL TYPE FOR
 COMPRESSED AIR SYSTEM PIPING. PVC NOT
 APPROVED FOR COMPRESSED AIR PER MANUF.
 INSTALLATION REQUIREMENTS. TYPICAL AIR
 LINE RISER SHOWS 2" PVC TO LIFT. THIS IS
 NOT APPROVED.
 END OF COMMENTS QUESTIONS 561-805-6692
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  