| Date |
Text |
| 2005-10-15 00:00:00 | PAUL SCHMITZ |
| | FBC2001 FUEL GAS CODEPLAN REVIEW |
| | FBC 2001 PLUMBING CODEPLAN REVIEW |
| | FBC 2001 FL ACESSIBILITY CODE PLAN |
| | REVIEW |
| | DENIED |
| | 1) NOTES 3 THRU 5 ON FROM PREVIOUS PLAN |
| | REVIEW, DATED 08-22-05 NEED TO BE PLACED |
| | ON THE PLANS, RE SUBMITTED. |
| | 3)SHT A-7 ALL TOILET ROOMS, |
| | NEW NOTE: |
| | SEC 310.4 WATER CLOSET COMPARTMENT. |
| | EXCEPTION: WATER CLOSET COMPARTMENTS. |
| | SHALL NOT BE REQUIRED IN A SINGLE- |
| | OCCUPANT TOILET ROOM WITH A LOCKABLE |
| | DOOR. |
| | "INCLUDE ALL NOTES ON PLANS" |
| | 4. SHTS P-1 & P-3 THE OIL SEPARATOR |
| | SHALL BE SIZED BY LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE |
| | CONTACT HER AT (561) 822-2271, FAX (561) |
| | 822-2279, OR E-MAIL [email protected]. |
| | WASTE ORD. #3434.INC WITH PLANS |
| | 5. RPZ BACKFLOW SHALL BE INSTALLED ON |
| | THE WATER SERVICE AS CLOSE TO THE METER |
| | AS POSSIBLE. PER UTILITY DEPT. |
| | 6. P-3 INDICATE MATERIAL TYPE FOR |
| | COMPRESSED AIR SYSTEM PIPING. PVC NOT |
| | APPROVED FOR COMPRESSED AIR PER MANUF. |
| | INSTALLATION REQUIREMENTS. TYPICAL AIR |
| | LINE RISER SHOWS 2" PVC TO LIFT. THIS IS |
| | NOT APPROVED. |
| | END OF COMMENTS QUESTIONS 561-805-6692 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |