Plan Review Notes
Plan Review Notes For Permit 05070691
Permit Number 05070691
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW; NUMBERING
 REMAINING THE SAME TO MAINTAIN
 CONSISTENCY.
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025 FOR MORE
 INFORMATION.
  
 3.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15-23.002.
 PHOTOCOPIES WERE SUBMITTED.
  
 4.)THE SQUARE FOOTAGE ON THE PLAN AND
 ENERGY CALCS ARE NOT CONSISTENT (6569
 ON AS1, 6560 LS1, 6885 ENERGY CALC).
  
 AS1 AND LS1 WERE REVISED TO SHOW 6626,
 BUT THE ENERGY CALCS STILL STATE 6885
 AND 1-AS1 SHOWS 6569.
  
 5.)ADDRESSED; OWNER/AGENT LINE OF
 ENERGY CALC SIGNED.HOWEVER, IF THE
 CALCS ARE REVISED PLEASE PROVIDE
 REQUIRED SIGNATURES ON THE NEW ENERGY
 CALCS.
  
 6.)THE SPEC BOOK IS NOT SIGNED AND
 SEALED AND DOES NOT HAVE A TITLE BLOCK
 IN COMPLIANCE WITH FAC61G1-16.003, 004.
 ALSO HALF OF THE PAGES ARE UPSIDE DOWN.
 IF YOU WANT FOR THIS TO BE INCORPORATED
 INTO THE PERMIT PACKAGE, SUBMIT IN
 COMPLIANCE AND IN A READABLE FORMAT.
  
 THE TITLE BLOCKS ARE NOT COMPLIANT WITH
 FAC RULES FOR ARCHITECTS AND ENGINEERS.
 NOTE THAT THIS PACKAGE IS NOT REQUIRED
 FOR PERMITTING.
  
 7.)ADDRESSED.
  
 8.)PLANS PREPARED BY AN ENGINEER ARE
 TO HAVE A TITLE BLOCK IN COMPLIANCE WITH
 FAC61G15-23.002.A CERTIFICATE OF
 AUTHORIZATION IS REQUIRED FOR BUSINESSES
 PRACTICING ENGINEERING IN FLORIDA,
 FAC61G15-19.001(3).
  
 THE CA HAS BEEN APPLIED FOR STRUCTURAL
 INTEGRITY, INC.THE CA NUMBER IS
 REQUIRED TO PRACTICE ENGINEERING AS A
 BUSINESS ORGANIZATION, FS471.023.
  
 9.)THE MASONRY WALL CALCS PREPARED BY
 MR. MITCHELL PE IS:
  
 A. REQUIRED TO HAVE A TITLE BLOCK IN
 COMPLIANCE WITH FAC61G15-23.002.
  
 B.ILLEGIBLE, APPEARS TO HAVE GREY
 LINES (DRAWINGS) WHICH ARE UNREADABLE.
  
 THE REVISED MASONRY CALCS ARE NOT
 SEALED.IT HAS A TITLE BLOCK FOR
 STRUCTURAL INTEGRITY INC. WHICH DOES NOT
 HAVE A VALID CA NUMBER.WHEN SEALED,
 THE TITLE BLOCK IS TO INCLUDE THE
 PRINTED NAME AND LICENSE NUMBER OF THE
 INDIVIDUAL SEALING THE DOCUMENT.
 FAC61G15-23.002.THE CALCS REFER TO THE
 2003 FBC, GOVERNING CODE IS FBC2001.
  
 10.)LS1 CODE INFORMATION, IV INDICATES
 THAT THIS BUILDING WILL BE FULLY
 SPRINKLED.SUBMIT SPRINKLER PLANS
 FBC104.3.1.1(5).
  
 SPRINKLER PLANS NOT PROVIDED.SEE
 FBC104.3.1.1(5) AND ATTACHED LETTER FROM
 DCA IN REGARDS TO SPRINKLER PLANS
 REQUIRED AT TIME OF PERMITTING.
  
 11.)HURRICANE SHUTTER STORAGE IS SHOWN
 ON THE PLAN (TIRE STORAGE AREA).SEE
 ATTACHED IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13.SUBMIT A PLAN FOR
 INSTALLATION FOR REVIEW.
  
 NOT ADDRESSED.USE OF REMOVABLE
 SHUTTERS AND THE INSTALLATION PLAN IS TO
 BE APPROVED BY THE BUILDING OFFICIAL.
  
  
 12.)SEE PROCEDURES, ITEM I, ON THE
 ATTACHED STANDARD IN REGARDS TO REQUIRED
 INFORMATION.A FORM IS ATTACHED FOR
 YOUR CONVENIENCE.
  
 NOT ADDRESSED.FORM WAS RETURNED BLANK.
  
 13.)ONLY ONE ACCESSIBLE EXIT IS SHOWN
 FROM THE SERVICE AREA AND THE TIRE
 STORAGE FBC11-4.11(3), FBC1004.2.2.
  
 SAME PLANS PROVIDED.NOTE THAT EXIT 2
 HAS A RAMP, EXITS 3 AND 4 HAVE STEPS.
 THE TRANSMITTAL LETTER STATES THAT DOORS
 107 AND 108 ARE ACCESSIBLE EGRESS DOORS.
 DOOR 107 IS AN INTERIOR DOOR, IS NOT AN
 EXIT.DOOR 108 HAS A STEP DOWN, NOT AN
 ACCESSIBLE EXIT.
  
 14.)PROVIDE A DETAIL FOR THE SALES
 COUNTER, FBC11-7.2.
  
 NOT ADDRESSED.THE TRANSMITTAL LETTER
 STATES THAT THE DETAIL WILL BE PROVIDED
 BY THE FIRE PROTECTION CONSULTANT.THIS
 IS BEING REQUESTED TO DETERMINE CODE
 COMPLIANCE AND IS REQUIRED AS A PART OF
 THE PERMITTED SET OF PLANS.ALSO IT IS
 UNCLEAR TO ME AS TO WHY A FIRE SPRINKLER
 ENGINEER WOULD BE DESIGNING CABINETRY.
  
 15.)ADDRESSED.
  
 16.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FAC9B72 IN ADDITION
 TO EVALUATION OR TEST REPORT.SUBMIT
 FOR THE FOLLOWING:
  
 ROOF, FLAT
 ROOF, TILE
 EIFS SYSTEM
 OVERHEAD DOOR
 METAL DOORS
 FIXED GLASS
 STOREFRONT
  
 WWW.FLORIDABUILDING.ORG
  
 THE TRANSMITTAL LETTER STATES THAT FIXED
 GLASS AND STOREFRONT WERE NOT ATTACHED
 DUE TO THE USE OF HURRICANE SHUTTERS.
 ALL COMPONENTS AND CLADDING STILL
 REQUIRE PRODUCT APPROVALS AS THEY STILL
 MUST MEET DESIGN PRESSURE REQUIREMENTS
 REGARDLESS OF WHETHER GLAZED COMPONENTS
 ARE IMPACT GLASS OR HAVE IMPACT
 PROTECTION.SEE FBC1606.2.2, 1606.2.5,
 1707.4.2.
  
 THE HURRICANE SHUTTER PRODUCT APPROVALS
 SUBMITTED MUST INCLUDE THE SCHEDULE FOR
 INSTALLATION, SEE ITEM 12.
  
 THE ROOF TILE NOA IS MISSING STATE
 PRODUCT APPROVAL.INCLUDE DOCUMENTS
 FROM STATE WEBSITE.
  
 THE BENCHMARK DOORS STATE PRODUCT
 APPROVAL HAS SEVERAL PRODUCTS INCLUDED.
 CIRCLE WHICH PRODUCT YOU ARE USING AND
 SUBMIT MANUFACTURER SPECS/INSTALLATION
 INSTRUCTIONS SO THAT CODE COMPLIANCE CAN
 BE DETERMINED.
  
 THE PRODUCT APPROVALS FOR THE CLOPAY
 OVERHEAD DOORS HAS A DESIGN PRESSURE
 LIMITATION OF +37/-42.ALSO STATES ON
 THE SPEC SHEET THAT IT IS COMPLIANT FOR
 150MPH EXPOSURE B, YOUR BUILDING HAS
 BEEN DECLARED AS EXPOSURE D.
  
 17.)THE ROOF PRODUCT APPROVAL
 SUBMITTED HAS A DESIGN PRESSURE OF -45
 WITH LIMITATION #9 WHICH DOES NOT ALLOW
 ENHANCED FASTENING FOR THE PERIMETER AND
 CORNER ZONES.
  
 ON THE NEW ROOF PRODUCT APPROVAL
 SUBMITTED, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE INSTALLING.
  
 18.)ADDRESSED.
  
 19.)PROVIDE DESIGN PRESSURES FOR
 COMPONENTS AND CLADDING, ROOF.
  
 THIS BUILDING HAS BEEN DECLARED AS
 150MPH EXPOSURE D DESIGN.THE DESIGN
 PRESSURE FOR A FLAT ROOF, ZONE 3, 150,
 EXPOSURE B IS -102.2.SEE FBC TABLE
 1606.2B, FBC1606.2D.THE DESIGN
 PRESSURES YOU HAVE PROVIDED ON S0, 59
 FOR END ZONES FOR OPENINGS, 68 FOR END
 ZONES FOR ROOF, ARE NOT COMPLIANT FOR
 150MPH EXPOSURE D.PLEASE REVISE OR
 CLARIFY AS TO HOW YOU HAVE ARRIVED AT
 THESE DESIGN PRESSURES.
  
 20.)PROVIDE WIND DESIGN INFORMATION
 FBC1606.1.7.
  
 I WAS UNABLE TO LOCATE THE INFORMATION.
 SOME OF THE INFORMATION IS ON THE PLAN
 IN VARIOUS PLACES BUT OTHER ITEMS ARE
 MISSING.
  
 NEW COMMENTS:
  
 21.)LS1 STATES THAT THIS IS S1 AND M
 OCCUPANCY.PLEASE READ FBC305.1.2,
 FBC404.3.PLEASE REVISE AFFECTED LIFE
 SAFETY REQUIREMENTS.
  
 SEE ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED AS REQUIRED
 BY FLORIDA STATE STATUTE IF ITEMS ARE
 NOT CORRECTLY ADDRESSED ON THE NEXT
 REVIEW.
  
  
  