| Date |
Text |
| 2005-08-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-1 FINISH SCHEDULE SHOWS GYP-BD |
| | PAINTED FOR THE WALLS OF THE TOILET |
| | ROOMS. PLEASE INDICATE HOW THIS WILL |
| | COMPLY WITH THE REQUIREMENT FOR THE |
| | WALLS TO BE NONABSORBENT UP TO 4' IN |
| | PUBLIC TOILET ROOMS. SECTION 1204.2 |
| | FBC-2001 BUILDING. |
| | 2. SHT A-3 SUBMIT CALCULATIONS FOR THE |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | THE TOTAL SF OF THE ROOF AND SHOW 1/2 |
| | AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS PLUS THE AREA OF ROOFS THAT |
| | DRAIN ONTO THE ROOF FROM ABOVE. INDICATE |
| | THE TOTAL AREA DRAINING INTO EACH DRAIN. |
| | SECTIONS 1106 & 1107. IF PRIMARY AND |
| | SECONDARY ROOF DRAINS ARE COMBINED INTO |
| | ONE OPENING, THE SIZE SHALL BE PER |
| | SECTION 1107.3, 3 TIMES THE CROSS |
| | SECTIONAL AREA OF THE PRIMARY DRAIN PLUS |
| | THE AREA OF THE PRIMARY DRAIN. SHOW THE |
| | SIZE OF ALL DOWNSPOUTS. |
| | 3. SHT A-7 ALL TOILET ROOMS, (INCLUDING |
| | EMPLOYEES), SHALL BE ACCESSIBLE. SHOW |
| | THE FOLLOWING: |
| | FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAVS: |
| | C. 11-4.19.2 HEIGHT & CLEARANCES |
| | D. 11-4.19.3 CLEAR FLOOR SPACE |
| | E. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | F. 11-4.19.5 FAUCETS |
| | G. 11-4.19.6 MIRRORS |
| | FOR TOILET ROOMS: |
| | 11-4.22.3 UNOBSTRUCTED TURNING AREA - |
| | FOR EMPLOYEES TOILET ROOM. |
| | 4. SHTS P-1 & P-3 THE OIL SEPARATOR |
| | SHALL BE SIZED BY LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE |
| | CONTACT HER AT (561) 822-2271, FAX (561) |
| | 822-2279, OR E-MAIL [email protected]. |
| | WASTE ORD. #3434. |
| | 5. RPZ BACKFLOW SHALL BE INSTALLED ON |
| | THE WATER SERVICE AS CLOSE TO THE METER |
| | AS POSSIBLE. PER UTILITY DEPT. |
| | 6. P-3 INDICATE MATERIAL TYPE FOR |
| | COMPRESSED AIR SYSTEM PIPING. PVC NOT |
| | APPROVED FOR COMPRESSED AIR PER MANUF. |
| | INSTALLATION REQUIREMENTS. TYPICAL AIR |
| | LINE RISER SHOWS 2" PVC TO LIFT. THIS IS |
| | NOT APPROVED. |
| | 7. ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS AND LICENSE NUMBER |
| | AS WELL AS THE CERTIFICATE OF |
| | AUTHORIZATION OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. FAC |
| | 6115-23.002(2) & FS 471.025 |
| | 8. THE PRINTED NAME OF THE PERSON |
| | SEALING ALL ARCHITECTURAL SHEET SHALL BE |
| | IN THE TITLE BLOCK OF EACH SHEET SIGNED, |
| | SEALED, AND DATED. FAC 61G1-16.004(6) & |
| | FS 481.2055 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |