Plan Review Notes
Plan Review Notes For Permit 05070691
Permit Number 05070691
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-08-18 00:00:00******DENIED******
  
 1) PLEASE NOTE FOR REF:, LIFE SAFETY TO
 COMPLY WITH NFPA 101, AND NFPA 1, 2003
 EDITION IN ADDITION TO OTHER APPLICABLE
 CODES.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN
 TERMS OF CLASS A,B OR C.
  
 4) AN ADDRESS IS REQUIRED ON THE
 BUILDING TO BE AT LEAST 6" IN HEIGHT AND
 CONRASTING TO THE BACKGROUND.
  
 5) WHEN A FIRE ALARM SYSTEM IS PROVIDED,
 IN ACCORDANCE WITH LOCAL REQUIREMENTS,
 DUCT SMOKE DETECTORS SHALL BE WIRED INTO
 SYSTEM TO CAUSE A GENERAL FIRE ALARM
 WHEN ACTIVATED.
  
 6) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 7) PLANS SHOW 1 HOUR RATED WALLS,
 HOWEVER NO MENTION REGARDING DOORS OR
 CLOSERS ON DOOR SHEDULE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722