| Plan Review Notes For Permit 05070691 |
| Permit Number |
05070691 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-18 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE NOTE FOR REF:, LIFE SAFETY TO | | | COMPLY WITH NFPA 101, AND NFPA 1, 2003 | | | EDITION IN ADDITION TO OTHER APPLICABLE | | | CODES. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM SYSTEMS. | | | | | | 3) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS IN | | | TERMS OF CLASS A,B OR C. | | | | | | 4) AN ADDRESS IS REQUIRED ON THE | | | BUILDING TO BE AT LEAST 6" IN HEIGHT AND | | | CONRASTING TO THE BACKGROUND. | | | | | | 5) WHEN A FIRE ALARM SYSTEM IS PROVIDED, | | | IN ACCORDANCE WITH LOCAL REQUIREMENTS, | | | DUCT SMOKE DETECTORS SHALL BE WIRED INTO | | | SYSTEM TO CAUSE A GENERAL FIRE ALARM | | | WHEN ACTIVATED. | | | | | | 6) PLEASE SEE OTHER REVIEW COMMENTS IN | | | REGARDS TO FS AND FAC REQUIREMENTS FOR | | | PLANS. | | | | | | 7) PLANS SHOW 1 HOUR RATED WALLS, | | | HOWEVER NO MENTION REGARDING DOORS OR | | | CLOSERS ON DOOR SHEDULE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|