| 2005-08-16 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.)PROVIDE A SOILS INVESTIGATION |
| | REPORT, FBC1804.2.2. |
| | |
| | 4.)THE SQUARE FOOTAGE ON THE PLAN AND |
| | ENERGY CALCS ARE NOT CONSISTENT (6569 |
| | ON AS1, 6560 LS1, 6885 ENERGY CALC). |
| | |
| | 5.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 6.)THE SPEC BOOK IS NOT SIGNED AND |
| | SEALED AND DOES NOT HAVE A TITLE BLOCK |
| | IN COMPLIANCE WITH FAC61G1-16.003, 004. |
| | ALSO HALF OF THE PAGES ARE UPSIDE DOWN. |
| | IF YOU WANT FOR THIS TO BE INCORPORATED |
| | INTO THE PERMIT PACKAGE, SUBMIT IN |
| | COMPLIANCE AND IN A READABLE FORMAT. |
| | |
| | 7.)THE ARCHITECTURAL PLANS ARE TO HAVE |
| | A TITLE BLOCK IN COMPLIANCE WITH |
| | FAC61G1-16.003, 004. |
| | |
| | 8.)PLANS PREPARED BY AN ENGINEER ARE |
| | TO HAVE A TITLE BLOCK IN COMPLIANCE WITH |
| | FAC61G15-23.002.A CERTIFICATE OF |
| | AUTHORIZATION IS REQUIRED FOR BUSINESSES |
| | PRACTICING ENGINEERING IN FLORIDA, |
| | FAC61G15-19.001(3). |
| | |
| | 9.)THE MASONRY WALL CALCS PREPARED BY |
| | MR. MITCHELL PE IS: |
| | |
| | A. REQUIRED TO HAVE A TITLE BLOCK IN |
| | COMPLIANCE WITH FAC61G15-23.002. |
| | |
| | B.ILLEGIBLE, APPEARS TO HAVE GREY |
| | LINES (DRAWINGS) WHICH ARE UNREADABLE. |
| | |
| | 10.)LS1 CODE INFORMATION, IV INDICATES |
| | THAT THIS BUILDING WILL BE FULLY |
| | SPRINKLED.SUBMIT SPRINKLER PLANS |
| | FBC104.3.1.1(5). |
| | |
| | 11.)HURRICANE SHUTTER STORAGE IS SHOWN |
| | ON THE PLAN (TIRE STORAGE AREA).SEE |
| | ATTACHED IMPLEMENTATION STANDARD FOR |
| | HURRICANE MISSILE IMPACT PROTECTION, |
| | ITEM #13.SUBMIT A PLAN FOR |
| | INSTALLATION FOR REVIEW. |
| | |
| | 12.)SEE PROCEDURES, ITEM I, ON THE |
| | ATTACHED STANDARD IN REGARDS TO REQUIRED |
| | INFORMATION.A FORM IS ATTACHED FOR |
| | YOUR CONVENIENCE. |
| | |
| | 13.)ONLY ONE ACCESSIBLE EXIT IS SHOWN |
| | FROM THE SERVICE AREA AND THE TIRE |
| | STORAGE FBC11-4.11(3), FBC1004.2.2. |
| | |
| | 14.)PROVIDE A DETAIL FOR THE SALES |
| | COUNTER, FBC11-7.2. |
| | |
| | 15.)SEE ZONING?S COMMENTS IN REGARDS |
| | TO THE STRIPING REQUIREMENTS AND THE |
| | INCONSISTENCY IN THE NUMBER OF PARKING |
| | SPACES FOR THE ACCESSIBLE PARKING. |
| | |
| | 16.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED FAC9B72 IN ADDITION |
| | TO EVALUATION OR TEST REPORT.SUBMIT |
| | FOR THE FOLLOWING: |
| | |
| | ROOF, FLAT |
| | ROOF, TILE |
| | EIFS SYSTEM |
| | OVERHEAD DOOR |
| | METAL DOORS |
| | FIXED GLASS |
| | STOREFRONT |
| | |
| | 17.)THE ROOF PRODUCT APPROVAL |
| | SUBMITTED HAS A DESIGN PRESSURE OF -45 |
| | WITH LIMITATION #9 WHICH DOES NOT ALLOW |
| | ENHANCED FASTENING FOR THE PERIMETER AND |
| | CORNER ZONES. |
| | |
| | 18.)THE TOWER DETAILS SHOW PLYWOOD ON |
| | THE WALLS, S2.WALLS ARE TO BE NON |
| | COMBUSTIBLE FOR TYPE V CONSTRUCTION. |
| | |
| | 19.)PROVIDE DESIGN PRESSURES FOR |
| | COMPONENTS AND CLADDING, ROOF. |
| | |
| | 20.)PROVIDE WIND DESIGN INFORMATION |
| | FBC1606.1.7. |
| | |