Plan Review Notes
Plan Review Notes For Permit 05070670
Permit Number 05070670
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-02 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 IT IS NOTED ON RISER, HOWEVER PLEASE
 INDICATE ON PLANS.
 215.5
  
 3)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A AND #12 AWG.
  
 4 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E, MISSING REAR.
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE. PLEASE SEE
 POSSIBLE MISSING PER 2' OF WALL.
  
 6)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12, 2002 NEC.
  
 7)NOTE: PLEASE SHOWS REQ'D DISC'S FOR
 A/C EQUIPMENT. PER 440.11
 PLEASE SEE A "RECEPT" FOR 220V IS SHOWN
 FOR DISCONNECT.
  
 8)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 KITCHEN COUNTERSPACE RECEPTS REQUIRED.
  
 9)NOTE: PLEASE SEE RISER AND PLANS
 INDICATE PANEL AS BEING FED THROUGH
 WALL? PLEASE SEE 230.70, NO MORE THAN 8'
 OF UNPROTECTED CONDUCTORS MAY BE
 INSTALLED INSIDE A BLDG W/OUT AMEANS
 OF DISCONNECT OUTSIDE WITH OVER CURRENT
 PROTECTION.230.6,215.5
  
 10)NOTE: PLEASE SEE MISSING FOOTER STEEL
 AAS REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
  
 11)NOTE: PLEASE VERIFY A/C HEAT ONLY
 SHOWN AS 5KW? THIS SEEMS SMALL FOR A
 HOUSE THIS SIZE?
 PLEASE SEE 424.3B FOR THE MIN OCP, AMIN
 125%.
  
 12)NOTE: PLEASE SEE ONLY ONE SMALL
 APPLIANCE CIRCUIT IS SHOWN, WHERE NEC
 210.52B, 210.11C1, 220.16 REQUIRES A MIN
 OF TWO. PLEASE ALSO SEE MIN LOAD (KVA)
 FOR EACH. PLEASE ADJUST LOAD
 CALCULATIONS A NESS.
  
 13)NOTE: PLEASE SEE BY PANEL SCHEDULE
 SUBMITTED, PANEL INDICATE "ONE CIRCUIT"
 FOR "ALL" RECEPTS IN THIS HOUSE???
 215.5
  
 14)NOTE: PLEASE SEE "IF" ANY LV
 ELECTRICAL SYSTEMS ARE TO BE INSTALLED
 UNDER THIS PLAN REVIEW,IE: CATV< PHONE
 ETC, PLEASE SHOW AT THIS TIME. IF ALL OF
 THESE ITEMS ARE NOT SHOWN ON PLANS, THIS
 MAY NOT BE REVISED AT A LATER DATE AND
 WILL REQUIRE SEPARATE PLANS AND PERMITS
 FOR ALL OTHER LV SYSTEMS.
 PLEASE NOTE: ALL LV ALARM FOR A SFR
 SHALL BE UNDER A SEPARATE PERMIT.
  
 15)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 BEDRM? SHOWS A SWITH TO A FAN, HOWEVER
 NEC 210.70, LS 101 5-8 REQUIRES A MIN OF
 ONE "LIGHTING OUTLET".
  
 16)NOTE: PLEASE PROVIDE ALL ROOM/AREA
 DESIGNATIONS ON PLANS.
 215.5
  
 PLEASE BE AWARE OF ANY POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW INTO SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  