| Plan Review Notes For Permit 05070668 |
| Permit Number |
05070668 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-27 00:00:00 | SECOND MECH. REVIEW RESUB. | | | | | | A/C PLAN UNCOMPLETE. | | | | | | 1. R/A NOT REFLECTED ON PLAN A-4 . | | | | | | 2. BEDROOMS--KITCHEN REQUIRE R/A 2003 | | | FBC/M 601.4 . | | | | | | 3. BATHROOMS REQUIRE EXHAUST FANS. | | | 2000 FBC/M 402.3.1 REFEAR TO 403 | | | MECH. VENTILATION. | | | | | | 4. NO DETAIL ON AHU LAYOUT. REFEAR TO | | | MECH. CODE 2000 FBC SECTION 307 | | | CONDENSATE DISPOSAL. | | | | | | 5. NO DUCT WORK REFLECTED FOR SECOND | | | FLOOL. | | | | | | 6. REFEAR TO FIRST MECH. PLAN REVIEW | | | 8/2/05 . | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. | | | |
|