Plan Review Notes
Plan Review Notes For Permit 05070668
Permit Number 05070668
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} NOTES TO INDICATE CODE COMPLIANCE DO
 NOT MEET REQUIREMENTS FOR SHOWING INTENT
 OF WORK ON THE PLANS. SEE 104.2.1.
  
 2} THE TITLE BLOCK OF A CORPORATION MUST
 CONTAIN THE CERTIFICATE OF AUTHORIZATION
 NUMBER ISSUED BY THE STATE. SEE
 61G15-23.002(2). FAC.
  
 3} SHOW ALL DEVICE LOCATIONS, NEW AND
 EXISTING IN THE AREAS WORK IS BEING DONE
 UNDER THIS APPLICATION.
  
 4} INDICATE THE LOCATION OF THE SERVICE
 ON THE PLAN IF NEW OR RELOCATED.
  
 5} INDICATE THE AIC RATING OF THE
 SERVICE EQUIPMENT BEING INSTALLED PER
 110.9 & 10.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  