| Plan Review Notes For Permit 05070668 |
| Permit Number |
05070668 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-22 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} NOTES TO INDICATE CODE COMPLIANCE DO | | | NOT MEET REQUIREMENTS FOR SHOWING INTENT | | | OF WORK ON THE PLANS. SEE 104.2.1. | | | | | | 2} THE TITLE BLOCK OF A CORPORATION MUST | | | CONTAIN THE CERTIFICATE OF AUTHORIZATION | | | NUMBER ISSUED BY THE STATE. SEE | | | 61G15-23.002(2). FAC. | | | | | | 3} SHOW ALL DEVICE LOCATIONS, NEW AND | | | EXISTING IN THE AREAS WORK IS BEING DONE | | | UNDER THIS APPLICATION. | | | | | | 4} INDICATE THE LOCATION OF THE SERVICE | | | ON THE PLAN IF NEW OR RELOCATED. | | | | | | 5} INDICATE THE AIC RATING OF THE | | | SERVICE EQUIPMENT BEING INSTALLED PER | | | 110.9 & 10. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|