2005-08-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SHOW RECEPTACLE SPACING
 REQUIREMENTS PER 210.52(C) IN THE
 KITCHEN, AND GFI PROTECTION PER
 210.8(A)(6).
  
 2} SHOW RECEPTACLES IN THE BEDROOM PER
 210.52(A) FOR SPACING, 210.12 PER ARC
 FAULT REQUIREMENTS, AND 8-1.4.1.6.2
 NFPA-72, SMOKE DETECTORS.
  
 3} THE FIRMS CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED UNDER
 471.023(2) FS MUST BE INCLUDED ON THE
 TITLE BLOCK PER 61G15-23.002 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW