| 2005-08-02 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SHOW RECEPTACLE SPACING | | | REQUIREMENTS PER 210.52(C) IN THE | | | KITCHEN, AND GFI PROTECTION PER | | | 210.8(A)(6). | | | | | | 2} SHOW RECEPTACLES IN THE BEDROOM PER | | | 210.52(A) FOR SPACING, 210.12 PER ARC | | | FAULT REQUIREMENTS, AND 8-1.4.1.6.2 | | | NFPA-72, SMOKE DETECTORS. | | | | | | 3} THE FIRMS CERTIFICATE OF | | | AUTHORIZATION NUMBER REQUIRED UNDER | | | 471.023(2) FS MUST BE INCLUDED ON THE | | | TITLE BLOCK PER 61G15-23.002 FAC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|