| 2005-07-23 00:00:00 | PLUMBING PLANREVIEW FBC 2001 DENIED. |
| | PROVIDE INFORMATION ON CLOTHES DRYER |
| | EXHAUST, PER THE FOLLOWING MECHANICAL |
| | CODE SECTIONS, SEPERATE MECHANICAL |
| | PERMIT REQUIRED. |
| | |
| | ?M504.4 EXHAUST INSTALLATION. DRYER |
| | EXHAUST DUCTS FOR CLOTHES DRYERS |
| | SHALL TERMINATE ON THE OUTSIDE OF THE |
| | BUILDING AND SHALL BE EQUIPPED WITH A |
| | BACKDRAFT DAMPER.SCREENS SHALL NOT BE |
| | INSTALLED AT THE DUCT TERMINATION. |
| | DUCTS SHALL NOT BE CONNECTED OR |
| | INSTALLED WITH SHEET METAL SCREWS OR |
| | OTHER |
| | FASTENERS THAT WILL OBSTRUCT THE FLOW. |
| | CLOTHES DRYER EXHAUST DUCTS SHALL |
| | NOT BE CONNECTED TO A GAS VENT |
| | CONNECTOR, GAS VENT OR CHIMNEY.CLOTHES |
| | DRYER EXHAUST DUCTS SHALL NOT EXTEND |
| | INTO OR THROUGH DUCTS OR PLENUMS. |
| | |
| | ?M504.5 MAKEUP AIR. INSTALLATIONS |
| | EXHAUSTING MORE THAN 200 CFM (0.09 |
| | M^3/S) SHALL BE PROVIDED WITH MAKEUP |
| | AIR.WHERE A CLOSET IS DESIGNED FOR |
| | THE INSTALLATION OF A CLOTHES DRYER, AN |
| | OPENING HAVING AN AREA OF NOT LESS |
| | THAN 100 SQUARE INCHES (0.0645 M^2) |
| | SHALL BE PROVIDED IN THE CLOSET |
| | ENCLOSURE. |