Plan Review Notes
Plan Review Notes For Permit 05070649
Permit Number 05070649
Review Stop E
Sequence Number 9
Notes
Date Text
2007-02-18 15:16:39*** UNSAT ***
  
 1) NOTE: PLEASE SEE POOL SUB PANEL WHICH IS BEING SHOWN
 BEING FED FROM TWO SINGLE POLE 20AMP BREAKERS??
 PLEASE SEE THE SPACE (CIRCUITS ABOVE 10/12) SHOW 2-POLE
 25AMP BREAKER?
 PLEASE CORRELATE.
  
 2) NOTE: PLEASE SEE PLANS INDICATE THE DISHWASHER AND
 DISPOSAL AS TWO SEPARATE RECEPTACLE DEVICES, YET PANEL
 SCHEDULE SHOWS A 2-POLE BREAKER FEEDING THESE. PLEASE
 SEE 210.4, IF YOU WERE FEEDING BOTH APPLIANCES THROUGH
 ONE SINGLE DEVICE/YOKE, THEN A 2-POLE BREAKER WOULD BE
 REQUIRED, HOWEVER IF THESE ARE BOTH SEPARATE RECEPT
 DEVICES, THESE WOULD BE SINGLE POLE BREAKERS.
  
 3) NOTE: PLEASE VERIFY THE PANEL *B* WHICH SHOWS THIS
 AS A 125AMP PANEL AND 125A BREAKER ON RISER, YET PANEL
 SCHEDULE SHOWS THIS AS 150AMP PANEL WITH A BACK FED
 125AMP BREAKER? PLEASE BE SURE IF THIS IS A BACK FED
 BREAKER AND IS PRT OF THE SERVICE RATED MAIN DISCONNECT
 THAT THIS BREAKER CONTAINS A REJECTION CLIP. (IF THIS
 IS THE CASE) PLEASE CORRELATE WHAT SIZE PANEL ETC.
 FBC 106.1.2 PLEASE COORDINATE.
  
 4) NOTE: PLEASE SEE MISSING SMOKE ALARM AT THE LOWER
 FLOOR LEVEL IN THE IMMEDIATE VICINITY LEADING TO THE
 FLOOR ABOVE.
 NFPA-72 11.5.1.1
  
 **PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 5) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE
 REFLECTED ON PLANS FOR DESIGN.
 2002 NFPA-70, 2002 NFPA-72
  
 6) NOTE: PLEASE SEE POSSIBLE MISSING RECEPT IN KITCHEN
 FOR 2FT OR MORE OF WALL. THIS IS ONLY NOTED AS WALL
 DIMENSION AND KITCHEN SET UP WILL BE VERIFIED IN FIELD.
 210.52 (REDLINED ON PLAN).
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]