| 2007-02-18 15:16:39 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE POOL SUB PANEL WHICH IS BEING SHOWN |
| | BEING FED FROM TWO SINGLE POLE 20AMP BREAKERS?? |
| | PLEASE SEE THE SPACE (CIRCUITS ABOVE 10/12) SHOW 2-POLE |
| | 25AMP BREAKER? |
| | PLEASE CORRELATE. |
| | |
| | 2) NOTE: PLEASE SEE PLANS INDICATE THE DISHWASHER AND |
| | DISPOSAL AS TWO SEPARATE RECEPTACLE DEVICES, YET PANEL |
| | SCHEDULE SHOWS A 2-POLE BREAKER FEEDING THESE. PLEASE |
| | SEE 210.4, IF YOU WERE FEEDING BOTH APPLIANCES THROUGH |
| | ONE SINGLE DEVICE/YOKE, THEN A 2-POLE BREAKER WOULD BE |
| | REQUIRED, HOWEVER IF THESE ARE BOTH SEPARATE RECEPT |
| | DEVICES, THESE WOULD BE SINGLE POLE BREAKERS. |
| | |
| | 3) NOTE: PLEASE VERIFY THE PANEL *B* WHICH SHOWS THIS |
| | AS A 125AMP PANEL AND 125A BREAKER ON RISER, YET PANEL |
| | SCHEDULE SHOWS THIS AS 150AMP PANEL WITH A BACK FED |
| | 125AMP BREAKER? PLEASE BE SURE IF THIS IS A BACK FED |
| | BREAKER AND IS PRT OF THE SERVICE RATED MAIN DISCONNECT |
| | THAT THIS BREAKER CONTAINS A REJECTION CLIP. (IF THIS |
| | IS THE CASE) PLEASE CORRELATE WHAT SIZE PANEL ETC. |
| | FBC 106.1.2 PLEASE COORDINATE. |
| | |
| | 4) NOTE: PLEASE SEE MISSING SMOKE ALARM AT THE LOWER |
| | FLOOR LEVEL IN THE IMMEDIATE VICINITY LEADING TO THE |
| | FLOOR ABOVE. |
| | NFPA-72 11.5.1.1 |
| | |
| | **PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | 5) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE |
| | REFLECTED ON PLANS FOR DESIGN. |
| | 2002 NFPA-70, 2002 NFPA-72 |
| | |
| | 6) NOTE: PLEASE SEE POSSIBLE MISSING RECEPT IN KITCHEN |
| | FOR 2FT OR MORE OF WALL. THIS IS ONLY NOTED AS WALL |
| | DIMENSION AND KITCHEN SET UP WILL BE VERIFIED IN FIELD. |
| | 210.52 (REDLINED ON PLAN). |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |