Plan Review Notes
Plan Review Notes For Permit 05070649
Permit Number 05070649
Review Stop E
Sequence Number 8
Notes
Date Text
2007-02-03 13:16:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE THAT THE PLANS SUBMITTED ARE COPIES
 OF PLANS WHICH WERE DONE BY THE ARCHITECT OF RECORD.
 PLEASE KNOW IF A NEW DESIGNER OF RECORD IS TAKING OVER
 PROJECT THIS PERSON MAY NOT USE PLANS DONE BY THE
 ARCHITECT. THEY ARE REQUIRED TO BE RE-DRAWN, CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE NEW DESIGNER OF
 RECORD.
 THE ARCHITECT'S PLANS OF RECORD ARE PROTECTED UNDER
 FLORIDA STATUTES 481.
  
 2) NOTE: PLEASE SEE THE LETTER FROM THE OWNER IS
 REQUIRED TO BE AN ORIGINAL SIGNED LETTER, WITH AN
 ORIGINAL NOTARY;MAY NOT BE A PHOTO-COPY.
 FS117.05
  
 3) NOTE: PLEASE SEE MULTIPLE COMMENTS FROM PREVIOUS
 REVIEW WERE NOT CORRECTED.
 PLEASE SEE THE RISER AND PANEL SCHEDULES FOR SIZE AND
 SERVICE ENTRANCE CONDUCTORS, MAINS, MISSING PANELS,
 MISSING LOADS ETC.
  
 ***PLEASE SEE COMMENTS ATTACHED FROM PREVIOUS REVIEW.
 PLEASE SEE THE PLANS SUBMITTED CAN NOT CONTAIN A FULL
 REVIEW FOR CODE COMPLIANCE AS THE PLANS SUBMITTED ARE
 PLANS NOT SIGNED, DATED AND SEALED BY THE ARCHITECT OF
 RECORD WHICH IS STILL LEGALLY THE DESIGNER OF RECORD.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]