| 2007-01-10 17:37:47 | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE CORRELATE ALL OF THE ITEMS ON THE |
| | PANEL SCHEDULES WITH THE LOAD CALCULATIONS. PLEASE SEE |
| | MANY OF THE ITEMS BELOW WHICH MAY HELP. |
| | |
| | A) PLEASE SEE SPRINKLER PUMP ON LOAD CALCULATIONS |
| | INDICATE 1800VA AND PANEL SCHEDULE SHOWS 300VA. PLEASE |
| | ALSO SEE MISSING OVER CURRENT PROTECTION SIZE ON PANEL |
| | SCHEDULE. |
| | |
| | B) PLEASE SEE LOAD ON POOL PANEL IS SHOWN AS 3.7KW AND |
| | PANEL A SHOWS A LOAD OF 3.4.KW |
| | PLEASE SEE THIS WILL CHANGE IF THE SPRIKLER PUMP IS |
| | REMOVED? |
| | |
| | C) PLEASE SEE A RANGE IS SHOWN ON PANEL AND OVEN ON |
| | LOAD CALCULATIONS, IS THIS SAME OR IS THERE AN ELECTRIC |
| | OVEN? PANEL SCHEDULE SHOWS THIS RANGE AS GAS, HOWEVER |
| | ALSO SHOWS ELECTRIC AS 50A BREAKER WITH #6 CONDUCTORS. |
| | PLEASE SEE PLANS ALSO INDICATE A 220V OUTLET. |
| | |
| | D) PLEASE SEE THE SAME IS IN QUESTION FOR THE DRYER? IS |
| | THIS ELECTRIC OR GAS? PLEASE SEE PLANS DESIGNATE WHAT |
| | APPEARS TO BE THE WASHER AS A DRYER AND THE DRYER AS |
| | THE WASHER? PLEASE SEE THE WASHER SHOWN WITH THE W |
| | SHOWS A 220V RECEPT. 220.18 |
| | |
| | E) PLEASE SEE THE WATER HEATER IS BEING SHOWN AS GAS, |
| | YET ALSO SHOWS 220V/30A RATED BRANCH CIRCUIT. PLEASE |
| | SEE PLANS SHOWS A J-BOX? NO RECEPT, DISCONNECT ETC? |
| | 422.31 ETC |
| | |
| | F) PLEASE SEE WHIRLPOOL BRANCH CIRCUIT IS SHOWN ON |
| | PANEL SCHEDULE; HOWEVER NO RECEPT IS BEING SHOWN ON |
| | PLANS. THE LOCATION FOR THIS IS BEING ASSUMED TO BE AT |
| | THE MASTER BATH, HOWEVER PLEASE SEE PLANS. PLEASE ALSO |
| | SEE MISSING GFI PROTECTION EITHER AT THE UNIT OR AS THE |
| | BREAKER WHICH FEEDS THIS IS REQUIRED. 680.71 |
| | |
| | * ABOVE PER 408.4, 220, 310.16, 240.4, ETC |
| | FBC 106.1.2, 106.3.5.4 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION AND FOR CORRELATION OF SAID PLANS. |
| | |
| | 2) NOTE: PLEASE SEE RISER SHOWS THE PANEL B CONTAINING |
| | A 125A MAIN BREAKER; HOWEVER THE PANEL SCHEDULE SHOWS |
| | THIS CONTAINING A 100A MAIN BREAKER. |
| | |
| | 3) NOTE: PLEASE SEE LOCATION OF RECEPT IN FAMILY ROOM |
| | IS NOT WITHIN 6FT OF DOOR ON PLANS, PLEASE VERIFY AND |
| | CORRECT LOCATION AS NEEDED. PLEASE SEE REDLINED PLANS. |
| | THIS LOCATION IN THE FIELD MAY VERY WELL BE OK. 210.52 |
| | |
| | 4) NOTE: PLEASE KNOW THE PANEL B ON THE NEW CABANA |
| | PLANS FEEDS A NEW PANEL FOR THE CABANA; HOWEVER THERE |
| | IS NO INDICATION ON PANEL B SCHEDULE FOR THIS SUB FEED |
| | TO THE OTHER PANEL WHICH IS BEING INSTALLED AT THIS |
| | TIME UNDER PERMIT # 06061694. |
| | PLEASE REVISE PANEL SCHEDULE FOR B, PLEASE REVISE LOAD |
| | ON B, AND PLEASE REVISE LOAD CALCULATIONS FOR MAIN |
| | SERVICE. |
| | PLEASE KNOW, WHEN ADDING HEAT LOADS AND LOADS TO AN |
| | EXISTING SERVICE 220.31B IS REQUIRED FOR LOAD |
| | CALCULATIONS. AS THE NEW BUILDING WAS ADDED TO THE |
| | EXISTING SERVICE UNDER THE MAIN HOUSE, PLEASE SEE THE |
| | SECTION ABOVE IF ADDING THE LOADS MENTIONED AS THIS |
| | WILL AFFECT THE LOADS ON THE MAINS SERVICE. |
| | PLEASE INCLUDE FEEDERS, ETC. |
| | 408.4, 310.16, 250.32, 225.31, ETC |
| | IT IS RECOMMENDED THAT COORDINATION IS DONE BETWEEN THE |
| | MAIN HOUSE ELECTRICAL CONTRACTOR AND THAT OF THE |
| | CONTRACTOR FOR THE REAR CABANA BUILDING TO OBTAIN AND |
| | PROVIDE THE LATEST INFORMATION TO THE DESIGNER FOR THE |
| | MAIN HOUSE. |
| | ANY CHANGES ON THE DETACHED CABANA WILL ALSO BE |
| | REQUIRED TO BE REVISED AT A LATER DATE BEFORE FINAL CAN |
| | BE GIVEN OR POWER IS TURNED ON. |
| | |
| | |
| | ** PLEASE KNOW AS A SIDE NOTE, PLEASE VERIFY AND |
| | COORDINATE WITH THE ELECTRICAL INSPECTOR AND MOST |
| | IMPORTANTLY THE MECHANICAL INSPECTOR AS TO WHEN POWER |
| | CAN BE TURNED ON. POWER RELEASE TO CONDITION SPACE |
| | BEFORE ALL SANDING AND PAINTING ETC IS COMPLETE IS NOT |
| | PERMITTED NOT TO MENTION COMPLETION OF THE ELECTRICAL |
| | SYSTEMS FOR LIFE SAFETY. |
| | THIS IS ONLY A NOTE AND DOES NOT HAVE AN AFFECT ON THE |
| | ELECTRICAL REVISIONS AS SUBMITTED. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |