Plan Review Notes
Plan Review Notes For Permit 05070649
Permit Number 05070649
Review Stop E
Sequence Number 6
Notes
Date Text
2006-08-20 00:00:00REDLINED,
  
 POOL PANEL STILL SHOWES ONLY 3#10'S AND
 RISER SHOWS 4. (SEE RISER) INSTALL 4.
  
 PANEL "A" SHOWS TWO SEPARATE GDO
 CIRCUITS AT 1700VA EACH, YET LOAD
 CALCULATIONS SHOWS 2, YET BOTH ARE
 INCLUDED AT THE 1700VA.
  
 BOTH WERE REDLINED AND NOTED ON PREVIOUS
 REVIEW.