| 2006-08-14 00:00:00 | *** UNSAT *** |
| | |
| | ** PLEASE SEE RISER IS REVISED ALONG |
| | WITH PLANS. |
| | PLEASE SEE THE FOLLOWING COMMENTS. |
| | |
| | |
| | 1) NOTE: PLEASE CORRELATE ALL LOADS |
| | SHOWN ON PANEL SCHEDULES WITH LOADS |
| | SHOWN ON SERVICE LOAD CALCUALITONS. |
| | PLEASE SEE WASHER, DRYER,DISPOSAL, |
| | GARAGE DOOR OPENERS, POOL EQIPMENT ETC. |
| | PLEASE KNOW THIS IS IN NO WAY ALL ITEMS. |
| | PLEASE SEE MANY OF THESE ARE REDLINED. |
| | PLEASE GO THROUGH PLANS. |
| | PLEASE CORRELATE POOL LOADS, AS AMPERAGE |
| | ON POOL PANEL SHOWS "0"? |
| | 106.1.2, 408.4, 220.31 ETC. |
| | |
| | 2) NOTE: PLEASE SEE RISER NOW SHOWS THE |
| | NEW POOL PANEL, HOWEVER PLANS DO NOT |
| | SHOW THIS PANEL? |
| | PLEASE ALSO SEE PLANS SHOWS WHAT APPEARS |
| | TO BE THE NEW MAIN DISCONNECT NEXT TO |
| | METERCAN, HOWEVER THIS IS NOT LABLED. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE FEEDERS FOR POOL |
| | PANEL AS 3-#10'S AND RISER SHOWS 4-#10'S |
| | PLEASE CORRELATE. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE AIC RATINGS |
| | FOR ALL NEW MAINS/BRKRS. THIS |
| | INFORMATION WAS ON ORIGINAL PLANS AS |
| | NOTED. 110.9/90.8 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |