2006-08-14 00:00:00*** UNSAT ***
  
 ** PLEASE SEE RISER IS REVISED ALONG
 WITH PLANS.
 PLEASE SEE THE FOLLOWING COMMENTS.
  
  
 1) NOTE: PLEASE CORRELATE ALL LOADS
 SHOWN ON PANEL SCHEDULES WITH LOADS
 SHOWN ON SERVICE LOAD CALCUALITONS.
 PLEASE SEE WASHER, DRYER,DISPOSAL,
 GARAGE DOOR OPENERS, POOL EQIPMENT ETC.
 PLEASE KNOW THIS IS IN NO WAY ALL ITEMS.
 PLEASE SEE MANY OF THESE ARE REDLINED.
 PLEASE GO THROUGH PLANS.
 PLEASE CORRELATE POOL LOADS, AS AMPERAGE
 ON POOL PANEL SHOWS "0"?
 106.1.2, 408.4, 220.31 ETC.
  
 2) NOTE: PLEASE SEE RISER NOW SHOWS THE
 NEW POOL PANEL, HOWEVER PLANS DO NOT
 SHOW THIS PANEL?
 PLEASE ALSO SEE PLANS SHOWS WHAT APPEARS
 TO BE THE NEW MAIN DISCONNECT NEXT TO
 METERCAN, HOWEVER THIS IS NOT LABLED.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE FEEDERS FOR POOL
 PANEL AS 3-#10'S AND RISER SHOWS 4-#10'S
 PLEASE CORRELATE.
  
 4) NOTE: PLEASE SUBMIT THE AIC RATINGS
 FOR ALL NEW MAINS/BRKRS. THIS
 INFORMATION WAS ON ORIGINAL PLANS AS
 NOTED. 110.9/90.8
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  