| 2006-08-01 00:00:00 | *********** UNSAT ************** |
| | |
| | 1) NOTE: PLEASE CORRELATE PLANS, RISER |
| | AND PANEL SCHEDULES. |
| | |
| | A)PLEASE SEE PANEL "B" DOES NOT INDICATE |
| | AMPERAGE RATING. RISER NOTE MENTIONS TO |
| | SEE PANEL, HOWEVER PANEL "B" IS SHOWN AS |
| | "1"AMO RATED??? |
| | B) PLEASE SEE RISER NOTE THREE SEEMS TO |
| | INDICATE THE SEC'S GOING INTO MAIN FOR |
| | PANEL "B", YET PLEASE SEE 230.7. |
| | C) PLEASE SEE RISER NOTES MENTIONS |
| | FEEDERS FOR PANEL "B" AS 2/0'S, YET |
| | PANEL "B" SHOWS 3-#3'S ALONG WITH RISER |
| | NOTE #3. |
| | D) PLEASE SEE NUMEROUS ITEMS SHOWN ON |
| | PANEL SCHEDULE FOR SM APPL, DISHWASHER, |
| | DISPOSAL ETC WHICH INDICATE #6 AND #8 |
| | CONDUCTORS. PLEASE VERIFY AS CONDUCTORS |
| | ARE PERMITTED TO GO HIGHER THAN MINIMUM |
| | HOWEVER #6'S AND #8'S WILL NOT FIT INOT |
| | 20A BREAKERS. IF PLANS SHOW THESE SIZES, |
| | THEN THIS IT WHAT IS REQUIRED TO BE |
| | INSTALLED. |
| | E) PLEASE SEE POOL PANEL IS NOT SHOWN ON |
| | PLANS OR ON RISER. |
| | F)PLEASE SEE SEC'S OR FEEDERS FOR PANEL |
| | "A" DO NOT CORRELATE WITH PANEL "A". |
| | G) PLEASE VERIFY WHERE MAIN IS FOR PANEL |
| | "B". GROUPING, OCP ETC. |
| | PLEASE SEE THIS IS ONLY FOR RISER, RISER |
| | NOTES, PLANS AND PANELS WHICH DO NOT |
| | CORRELATE. |
| | 240.4,230.70,230.72,215.5,310.16,250.50, |
| | 240.21 ETC |
| | |
| | 2) NOTE: PLEASE VERIFY SEC'S FROM FPL AS |
| | THESE ARE STILL SHOWN AS 3/0'S. PLEASE |
| | SEE ORIGINAL PLANS WAS FOR A 200A |
| | SERVICE AND NOW HAS BEEN ADJUSTED TO |
| | 300A'S. |
| | PLEASE KNOW, IF THE SEC'S ARE INSTALLED |
| | BY FPL ALL THE WAY UP TO THE METERCAN, |
| | THEN THESE CONDUCTOR SIZES NEED NOT BE |
| | SHOWN, HOWEVER IF THESE CONDUCTORS ARE |
| | INSTALLED OUT TO A FPL HAND-HOLE, THEN |
| | THE SIZES SHALL BE SIZED AT A MIN PER |
| | 310.15B6, (250MCM). |
| | |
| | 3) NOTE: PLEASE SEE 250.66 FOR MIN |
| | SIZING OF THE GROUNDING ELECTRODE |
| | CONDUCTOR AS SERVICE HAS NOW BEEN |
| | INCREASED AND THE GEC IS SIZED BASED ON |
| | NEW SEC'S. |
| | |
| | 4) NOTE: PLEASE COMPLETE LOAD |
| | CALCULATIONS FOR PANEL "B". WHERE ARE |
| | THE LOADS FOR A/C'S 1 AND 2 CU'S?? |
| | 220, 240.4, 310.16 |
| | |
| | 5) NOTE: PLEASE SEE PROVIDE THE |
| | COMPLETED PANEL SCHEDULE FOR POOL PANEL |
| | WITH NEW CIRCUITS, LOADS ETC FUTURE? |
| | SHOWS 10.2 KW ON PANEL "A" HOWEVER IT IS |
| | UNCLEAR WHERE LOADS ARE DERIVED FROM?? |
| | PLEASE CLARIFYAND SHOW ALL CONTINOUS |
| | LOADS AT 125% |
| | 215.5, 220, 215.3, 230.42 |
| | |
| | 6) NOTE: PLEASE SEE ONE SHEET CONTAIN A |
| | TITLE BLOCK FOR "PARKER AND COMPANY" |
| | WHICH WAS REMOVED FROM RECORD SET AND |
| | FROM OTHER SHEET SUBMITTED. |
| | THIS WAS CONFIRMED WITH THE STATE'S |
| | LEGAL COUSEL TO THE BOARD OF |
| | ARCHITECT'S. |
| | FAC 61G1-16.004, FS481.219 |
| | |
| | 7) NOTE: PLEASE VERIFY THE KW RATING FOR |
| | AHU'S AS 9KW FOR EACH DOES NOT APPEAR TO |
| | BE A COMMON KW RATING. PLEASE VERIFY IF |
| | 10KW AND ADJUST CALCULATIONS AS NEEDED. |
| | PLEASE SEE 220 |
| | |
| | 8) NOTE: PLEASE SEE FS 481.221(4). |
| | PLANS ARE BEING RETAINED. |
| | |
| | ** PLEASE KNOW THESE PLANS WERE REVIEWED |
| | THREE TIME BEFORE THIS REVIEW. THE |
| | PREVIOUS REVIEW WAS DONE WITH A |
| | "PROVISO" TO ADDRESS CERTAIN ITEMS |
| | BEFORE ROUGH. PLEASE SEE PLANS HAVE NOW |
| | BEEN REVISED TO COMPLETELY CHNAGE THE |
| | ELECTRICAL SERVICE AS PREVIOUSLY |
| | SUBMITTED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |