| Plan Review Notes For Permit 05070649 |
| Permit Number |
05070649 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-11-09 00:00:00 | ********* PROVISO/REVISION ********* | | | | | | | | | PLEASE SEE SOME NOTES FROM PREVIOUS TWO | | | REVIEWS NEED TO BE ADDRESSED. | | | | | | | | | 1)NOTE: PLEASE SEE ITEMS SHOWN ON LOAD | | | CALCULATIONS WHICH ARE NOT SHOWN ON | | | PANEL SCHEDULES WITH AWG, OCP. | | | DRYER, WASHER. LAUNDRY CIR, MICROWAVE,,, | | | 215.5,240.4,310.16 | | | BOTH PREVIOUS REVIEWS. | | | | | | 2)NOTE: PLEASE SEE THERE ARE SOME | | | RECEPTS MISSING PER 210.52. | | | THESE ARE REDLINED . | | | BOTH PREVIOUS REVIEWS. | | | | | | 3)NOTE: PLEASE SEE SERVICE NOW INDICATES | | | AN "EQUIPMENT GROUNDING CONDUCTOR" FROM | | | METER TO PANEL "A". PLEASE SEE | | | "EQUIPMENT GRNDS" ARE ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNNECT. | | | 250.6,250.24. | | | | | | 4)NOTE: PLEASE SEE REDLINED 422.17 FOR | | | WATER HEATER LOCATION. | | | | | | PLEASE MAKE ALL OF THE ABOVE CORRECTIONS | | | AND SUBMIT FOR REVIEW AND STAMPING | | | BEFORE ROUGH ELECTRICAL INSPECTION. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-10-21 00:00:00 | IN ELEC FOR REVIEW, FROM ZONING ON | | | 10/18/05 |
|