Plan Review Notes
Plan Review Notes For Permit 05070649
Permit Number 05070649
Review Stop E
Sequence Number 2
Notes
Date Text
2005-09-08 00:00:00*********** UNSAT 2ND REVIEW **********
  
 PLEASE SEE THERE ARE SOME NOTES FROM
 PREVIOUS REVIEW AND SOME NEW NOTES DUE
 TO CHANGES MADE TO PLANS.
  
  
 1)NOTE: PLEASE SEE PANEL SCHEDULES WITH
 OCP, AWG ETC IS NOW SUBMITTED.
 PLEASE CORRELATE ITEMS ON LOAD
 CALCULATIONS AND ITEMS ON PANEL
 SCHEDULE:
 SEE WASHER, DRYER, WHIRLPOOL TUB, TWO
 POOL PUMPS, POOL LIGHTING, EXHASUT HOOD,
 ALL SHOWN ON LOAD CALCS, BUT NOT ON
 PANEL SCHEDULES.
 215.5, 240.4,220.31,310.16 ETC.
  
 2)NOTE: PLEASE CORRELATE HEATING LOADS
 FOR AHU'S,PLEASE SEE LOAD CALCS INDICATE
 10KW , HOWEVER OCP AND AWG ON PANEL
 SCHEDULE IS NOT LARGE ENOUGH FOR 10KW
 UNITS.
 PLEASE SEE 424.3B , 125% MIN OCP FOR
 10KW HEAT.
 PLEASE SEE 310.16 FOR MIN AWG TO
 CORRELATE WITH OCP ABOVE.
  
 3)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210.52, UPSTAIRS AND DOWNSTAIRS.
  
 4)NOTE: PLEASE SEE NEW SERVICE IS NOW
 SHOWN.
 PLEASE SEE NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED FROM METER TO
 FIRST MEANS OF DISCONNECT.
 250.6,250.24
  
 5)NOTE:PLEASE SEE 250.50 FOR MIN TO BE
 REQUIRED AS PART OF THE GROUNDING
 ELECTRODE SYSTEM.
 PLEASE SEE FOOTER STEEL(SHOWN AND COLD
 WATER PIPE REQUIRED, (IF METAL).
  
 6)NOTE: PLEASE SEE SEE MECHANICAL RM
 WHICH WAS SHOWN ON ORIGINAL PLANS IS NOW
 SHOWN AS A "STORAGE RM"PLEASE SEE
 WATER HEATER MUST HAVE PERMANANT
 SEPARATION FROM COMBUSTIBLES FROM
 STORAGE AREAS OR WH MUST BE PLACED
 OUTSIDE STORAGE AREA.
 422.17
  
 7)NOTE: PLEASE SEEEQUIPMENT GROUNDING
 CONDUCTOR MISSING FROM MAIN PANEL TO
 SUB-PANEL.
 250.110.,250.122
  
 8)NOTE: PLEASE SEE BATH RECEPTS FOR
 BATHS 2 AND 3 ARE SHOWN WITH AFCI
 PROTECTION. PLEASE SEE 210.8 WHICH
 REQUIRESBATH RECEPTS TO BE GFI
 PROTECTED.
  
 9)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS . THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  