| Date |
Text |
| 2005-09-08 00:00:00 | *********** UNSAT 2ND REVIEW ********** |
| | |
| | PLEASE SEE THERE ARE SOME NOTES FROM |
| | PREVIOUS REVIEW AND SOME NEW NOTES DUE |
| | TO CHANGES MADE TO PLANS. |
| | |
| | |
| | 1)NOTE: PLEASE SEE PANEL SCHEDULES WITH |
| | OCP, AWG ETC IS NOW SUBMITTED. |
| | PLEASE CORRELATE ITEMS ON LOAD |
| | CALCULATIONS AND ITEMS ON PANEL |
| | SCHEDULE: |
| | SEE WASHER, DRYER, WHIRLPOOL TUB, TWO |
| | POOL PUMPS, POOL LIGHTING, EXHASUT HOOD, |
| | ALL SHOWN ON LOAD CALCS, BUT NOT ON |
| | PANEL SCHEDULES. |
| | 215.5, 240.4,220.31,310.16 ETC. |
| | |
| | 2)NOTE: PLEASE CORRELATE HEATING LOADS |
| | FOR AHU'S,PLEASE SEE LOAD CALCS INDICATE |
| | 10KW , HOWEVER OCP AND AWG ON PANEL |
| | SCHEDULE IS NOT LARGE ENOUGH FOR 10KW |
| | UNITS. |
| | PLEASE SEE 424.3B , 125% MIN OCP FOR |
| | 10KW HEAT. |
| | PLEASE SEE 310.16 FOR MIN AWG TO |
| | CORRELATE WITH OCP ABOVE. |
| | |
| | 3)NOTE: PLEASE SEE SOME RECEPTS MISSING |
| | PER 210.52, UPSTAIRS AND DOWNSTAIRS. |
| | |
| | 4)NOTE: PLEASE SEE NEW SERVICE IS NOW |
| | SHOWN. |
| | PLEASE SEE NO EQUIPMENT GROUNDING |
| | CONDUCTOR IS INSTALLED FROM METER TO |
| | FIRST MEANS OF DISCONNECT. |
| | 250.6,250.24 |
| | |
| | 5)NOTE:PLEASE SEE 250.50 FOR MIN TO BE |
| | REQUIRED AS PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. |
| | PLEASE SEE FOOTER STEEL(SHOWN AND COLD |
| | WATER PIPE REQUIRED, (IF METAL). |
| | |
| | 6)NOTE: PLEASE SEE SEE MECHANICAL RM |
| | WHICH WAS SHOWN ON ORIGINAL PLANS IS NOW |
| | SHOWN AS A "STORAGE RM"PLEASE SEE |
| | WATER HEATER MUST HAVE PERMANANT |
| | SEPARATION FROM COMBUSTIBLES FROM |
| | STORAGE AREAS OR WH MUST BE PLACED |
| | OUTSIDE STORAGE AREA. |
| | 422.17 |
| | |
| | 7)NOTE: PLEASE SEEEQUIPMENT GROUNDING |
| | CONDUCTOR MISSING FROM MAIN PANEL TO |
| | SUB-PANEL. |
| | 250.110.,250.122 |
| | |
| | 8)NOTE: PLEASE SEE BATH RECEPTS FOR |
| | BATHS 2 AND 3 ARE SHOWN WITH AFCI |
| | PROTECTION. PLEASE SEE 210.8 WHICH |
| | REQUIRESBATH RECEPTS TO BE GFI |
| | PROTECTED. |
| | |
| | 9)NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS . THIS IS |
| | ONLY A NOTICE GIVEN AT THIS TIME |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |