2005-08-02 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTES.
 2.SANITARY RISER DIAGRAM NOT TO CODE.
 KITCHEN SINK TO DISCHARGE DOWN STREAM
 OF FIRST FLOO 1/2 BATH. D/W TO DRAIN
 INDIRECTLY THRU THE KITCHEN SINK TRAP
 NOT TIED DIRECTLY INTO SANITARY SYSTEM.
 KITCHEN SINK IS NOT VENTED.
 1/2 BATH LAV. NOT VENTED.
 W/M AND L/T NOT VENTED.
 BATHROOM 2 TUB IS NOT VENTED.
 A 2 WAY CLEANOUT IS REQUIRED AT THE
 JUNCTION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER.