| Date |
Text |
| 2005-07-29 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCK FOR BOTH |
| | ARCHITECTUAL AND ARCHITECTUAL AND |
| | INTERIOR DESIGN FIRMS. |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR AMES BENNETT |
| | AND ASSOCIATES AND MISSING ADDRESS ETC |
| | AS REQUIRED UNDER FAC 61G1-16.004 AND FS |
| | 481.219 |
| | PLEASE ALSO SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER FOR PARKER AND |
| | COMPANYINTERIOR AND ARCHITECTUAL |
| | DESIGN. PLEASE SEE NO INFORMATION COULD |
| | BE LOCATED ON STATE WEBSITE (DEPARTMENT |
| | OF BUSINESS AND PROFESSIONAL REGULATION) |
| | FOR THIS FIRM? PLEASE LIST ALL REQUIRED |
| | LICENSE INFORMATION AS REQUIRED UNDER |
| | FAC 61G1-16.004 AND FS 481.219 |
| | PLEASE SEE ONE SET OF PLANS ARE BEING |
| | RETAINED AND SHALL BE SENT TO THE STATE |
| | LEGAL COUNSEL FOR THE BOARD OF |
| | ARCHITECTS WITH PREVIOUS FILED PLANS. |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| | AND ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER: FBC 905.2, NFPA-72 |
| | 8-1.4.1.6.2, 8-1.4.2 |
| | |
| | 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 5)NOTE: PLEASE SEE RECEPTS SERVING |
| | KITCHEN COUNTERSPACE TO MEET 210.52C- |
| | SEC'S 1,2,3,4 AND 5 |
| | PLEASE SEE MISSING RECEPTS FOR 210.52C1 |
| | AND 210.52C3 |
| | PLEASE ALSO SEE AREA OF WHICH APPEARS TO |
| | BE KITCHEN COUNTERSPACE? |
| | |
| | 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE |
| | SHOWING ALL MIN CIRCUITS AS REQUIRED |
| | UNDER 2002 NEC. |
| | PLEASE INCLUDE, CIRCUIT OVERCURRENT |
| | PROTECTION FOR EACH, CONDUCTOR SIZES |
| | ETC.215.5,240.4,310.16 ETC. |
| | PLEASE SEE COMMENTS: |
| | |
| | 7)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | SHALL BE #12 AND 20A. |
| | |
| | 8)NOTE: PLEASE SEE PLANS SHOWS (GDO) |
| | GARAGE DOOR OPENERS, HOWEVER NONE LISTED |
| | IN LOAD CALCULATIONS OR LOAD CALCS. |
| | 215.5 PLEASE ALSO LIST ON PANEL SCHEDULE |
| | TO BE SUBMITTED. |
| | PLEASE SEE SIZING OF MOTORS LOADS FOR |
| | BRANCH CIRCUITING. 430. |
| | |
| | 9)NOTE: PLEASE SEE GARAGE RECEPTS SHALL |
| | BE SHOWN AS GFI/GFI PROTECTED PER |
| | 210.8A2 |
| | |
| | 10)NOTE: PLEASE SEE MISSING GFI RECEPT |
| | PER 210.52E,210.8 IN REAR OF DWELLING. |
| | |
| | 11)NOTE: PLEASE SEE ONLY (2) SMALL |
| | APPLIANCE CIRCUITS ARE SHOWN ON LOAD |
| | CALCULATIONS, HOWEVER A 6KW LOAD IS |
| | SHOWN?? PLEASE SEE 210.11C1 AND 220.16. |
| | A LOAD OF 1.5KW FRO EACH. IF ADDITIONAL |
| | CIRCUITS ARE PROVIDED, THEN LOAD SHALL |
| | BE INDICATED AS 1.5KW FOR EACH. PLEASE |
| | KNOW THE NUMBER OF CIRCUITS CAN NOT BE |
| | VERIFIED AT THIS TIME DUE TO MISSING |
| | PANEL SCHEDULE. |
| | |
| | 12)NOTE: PLEASE SHOW ALL A/C EQUIPMENT |
| | AND DISCONNECTS AS REQUIRED PER 440.11 |
| | PLEASESEE ROOM LABLED AS "MECH" DOES |
| | NOT SHOW ANY AHU? ETC |
| | PLEASE SEE LOAD CALCULATIONS SHOW 36KW |
| | OF HEAT, HOWEVER ONLY TWO CU'S AND ONE |
| | AHU, WAS LOCATED ON PLANS?? |
| | PLEASE SEE 36KW APPEARS TO INDICATE A |
| | MIN OF 3-4 SYSTEMS?? |
| | PLEASE ALSO SEE 2 CU'S ARE SHOWN ON |
| | PLANS, HOWEVER ONLY ONE CU DISCONNECT IS |
| | SHOWN?440.11 |
| | PLEASE ALSO SEE AHU SHOWN INSIDE HOUSE |
| | W/OUT INDICATION OF DISCONNECT. |
| | PLEASE SEE IF ROOM WITH ACCESS TO |
| | EXTERIOR IS INDEED MECH RM, PLEASE SHOW |
| | ALL EQUIPMENT. PLEASE ALSO SEE MISSING |
| | RECEPT PER 210.63 |
| | |
| | 13)NOTE: PLEASE SEE WATER HEATER SHOWN |
| | IN "MECH RM" HOWEVER, NO DISCONNECT IS |
| | SHOWN. 422.30,422.31 |
| | |
| | 14)NOTE: PLEASE SEE RISER DIAGRAM IS |
| | MISSING CONDUCTORS FROM MAIN DISCONNECT |
| | TO SUB PANEL AND FROM METER TO MAIN. |
| | PLEASE SEE 240.4,310.15B6,310.16.215.5 |
| | |
| | 15)NOTE: PLEASE ALSO SEE MISSING |
| | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN |
| | TO SUB PANEL. 250.110,250.24 SIZE PER |
| | 250.122 |
| | |
| | 16)NOTE: PLEASE SEE SUB PANEL IS BEING |
| | SHOWN AS MCB, WHICH IS FINE, HOWEVER |
| | THIS IS NOT REQUIRED. |
| | IF SHOWN ON PLANS, THEN A MCB WILL BE |
| | REQURIED TO BE INSTALLED. |
| | THIS IS ONLY A NOTE AND NO CORRECTION OR |
| | CHANGE IS REQUIRED. |
| | |
| | 17)NOTE: PLEASE SHOW SERVICE EQUIPMENT |
| | LOCATION ON PLANS. PLEASE SEE ONLY |
| | SUB-PANEL IS SHOWN ON PLANS. |
| | PLEASE ALSO INDICATE AMERAGE ON |
| | METER-CAN. |
| | 215.5,230.70 |
| | |
| | 18)NOTE: PLEASE SEE RECEPTS MISSING PER |
| | 210.52. PLEASE SEE BEDRMS #2 & #3 |
| | UPSTAIRS AND SOME WALLS DOWNSTAIRS. |
| | |
| | 19)NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS PER 2002 NEC |
| | 210.12. |
| | PLEASE SEE ALL "OUTLETS" IN BEDROOMS ARE |
| | REQUIRED TO BE ARC FAULT PROTECTED, THIS |
| | INCLUDES; RECEPTS,FANS,LTS SD'S ETC. |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED AT LOCATIONS FOR NOTES. |
| | PLEASE KNOW, REDLINES IN NO WAY INDICATE |
| | ALL LOCATIONS OF NOTES ABOVE. |
| | |
| | PLEASE SEE OTHER COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE SEE ZONING COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |