Plan Review Notes
Plan Review Notes For Permit 05070649
Permit Number 05070649
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-29 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR BOTH
 ARCHITECTUAL AND ARCHITECTUAL AND
 INTERIOR DESIGN FIRMS.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR AMES BENNETT
 AND ASSOCIATES AND MISSING ADDRESS ETC
 AS REQUIRED UNDER FAC 61G1-16.004 AND FS
 481.219
 PLEASE ALSO SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER FOR PARKER AND
 COMPANYINTERIOR AND ARCHITECTUAL
 DESIGN. PLEASE SEE NO INFORMATION COULD
 BE LOCATED ON STATE WEBSITE (DEPARTMENT
 OF BUSINESS AND PROFESSIONAL REGULATION)
 FOR THIS FIRM? PLEASE LIST ALL REQUIRED
 LICENSE INFORMATION AS REQUIRED UNDER
 FAC 61G1-16.004 AND FS 481.219
 PLEASE SEE ONE SET OF PLANS ARE BEING
 RETAINED AND SHALL BE SENT TO THE STATE
 LEGAL COUNSEL FOR THE BOARD OF
 ARCHITECTS WITH PREVIOUS FILED PLANS.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 AND ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: FBC 905.2, NFPA-72
 8-1.4.1.6.2, 8-1.4.2
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 5)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MISSING RECEPTS FOR 210.52C1
 AND 210.52C3
 PLEASE ALSO SEE AREA OF WHICH APPEARS TO
 BE KITCHEN COUNTERSPACE?
  
 6)NOTE: PLEASE SUBMIT A PANEL SCHEDULE
 SHOWING ALL MIN CIRCUITS AS REQUIRED
 UNDER 2002 NEC.
 PLEASE INCLUDE, CIRCUIT OVERCURRENT
 PROTECTION FOR EACH, CONDUCTOR SIZES
 ETC.215.5,240.4,310.16 ETC.
 PLEASE SEE COMMENTS:
  
 7)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 SHALL BE #12 AND 20A.
  
 8)NOTE: PLEASE SEE PLANS SHOWS (GDO)
 GARAGE DOOR OPENERS, HOWEVER NONE LISTED
 IN LOAD CALCULATIONS OR LOAD CALCS.
 215.5 PLEASE ALSO LIST ON PANEL SCHEDULE
 TO BE SUBMITTED.
 PLEASE SEE SIZING OF MOTORS LOADS FOR
 BRANCH CIRCUITING. 430.
  
 9)NOTE: PLEASE SEE GARAGE RECEPTS SHALL
 BE SHOWN AS GFI/GFI PROTECTED PER
 210.8A2
  
 10)NOTE: PLEASE SEE MISSING GFI RECEPT
 PER 210.52E,210.8 IN REAR OF DWELLING.
  
 11)NOTE: PLEASE SEE ONLY (2) SMALL
 APPLIANCE CIRCUITS ARE SHOWN ON LOAD
 CALCULATIONS, HOWEVER A 6KW LOAD IS
 SHOWN?? PLEASE SEE 210.11C1 AND 220.16.
 A LOAD OF 1.5KW FRO EACH. IF ADDITIONAL
 CIRCUITS ARE PROVIDED, THEN LOAD SHALL
 BE INDICATED AS 1.5KW FOR EACH. PLEASE
 KNOW THE NUMBER OF CIRCUITS CAN NOT BE
 VERIFIED AT THIS TIME DUE TO MISSING
 PANEL SCHEDULE.
  
 12)NOTE: PLEASE SHOW ALL A/C EQUIPMENT
 AND DISCONNECTS AS REQUIRED PER 440.11
 PLEASESEE ROOM LABLED AS "MECH" DOES
 NOT SHOW ANY AHU? ETC
 PLEASE SEE LOAD CALCULATIONS SHOW 36KW
 OF HEAT, HOWEVER ONLY TWO CU'S AND ONE
 AHU, WAS LOCATED ON PLANS??
 PLEASE SEE 36KW APPEARS TO INDICATE A
 MIN OF 3-4 SYSTEMS??
 PLEASE ALSO SEE 2 CU'S ARE SHOWN ON
 PLANS, HOWEVER ONLY ONE CU DISCONNECT IS
 SHOWN?440.11
 PLEASE ALSO SEE AHU SHOWN INSIDE HOUSE
 W/OUT INDICATION OF DISCONNECT.
 PLEASE SEE IF ROOM WITH ACCESS TO
 EXTERIOR IS INDEED MECH RM, PLEASE SHOW
 ALL EQUIPMENT. PLEASE ALSO SEE MISSING
 RECEPT PER 210.63
  
 13)NOTE: PLEASE SEE WATER HEATER SHOWN
 IN "MECH RM" HOWEVER, NO DISCONNECT IS
 SHOWN. 422.30,422.31
  
 14)NOTE: PLEASE SEE RISER DIAGRAM IS
 MISSING CONDUCTORS FROM MAIN DISCONNECT
 TO SUB PANEL AND FROM METER TO MAIN.
 PLEASE SEE 240.4,310.15B6,310.16.215.5
  
 15)NOTE: PLEASE ALSO SEE MISSING
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANEL. 250.110,250.24 SIZE PER
 250.122
  
 16)NOTE: PLEASE SEE SUB PANEL IS BEING
 SHOWN AS MCB, WHICH IS FINE, HOWEVER
 THIS IS NOT REQUIRED.
 IF SHOWN ON PLANS, THEN A MCB WILL BE
 REQURIED TO BE INSTALLED.
 THIS IS ONLY A NOTE AND NO CORRECTION OR
 CHANGE IS REQUIRED.
  
 17)NOTE: PLEASE SHOW SERVICE EQUIPMENT
 LOCATION ON PLANS. PLEASE SEE ONLY
 SUB-PANEL IS SHOWN ON PLANS.
 PLEASE ALSO INDICATE AMERAGE ON
 METER-CAN.
 215.5,230.70
  
 18)NOTE: PLEASE SEE RECEPTS MISSING PER
 210.52. PLEASE SEE BEDRMS #2 & #3
 UPSTAIRS AND SOME WALLS DOWNSTAIRS.
  
 19)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12.
 PLEASE SEE ALL "OUTLETS" IN BEDROOMS ARE
 REQUIRED TO BE ARC FAULT PROTECTED, THIS
 INCLUDES; RECEPTS,FANS,LTS SD'S ETC.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED AT LOCATIONS FOR NOTES.
 PLEASE KNOW, REDLINES IN NO WAY INDICATE
 ALL LOCATIONS OF NOTES ABOVE.
  
 PLEASE SEE OTHER COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE ZONING COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  