Plan Review Notes
Plan Review Notes For Permit 05070632
Permit Number 05070632
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-03 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE CONDUCTOR AND CONDUIT
 SIZES AND TYPE ON THE RISER DIAGRAM. SEE
 445.13 FOR GEN FEEDER.
  
 2} THE PERSON RESPONSIBLE FOR THE
 DRAWING MUST PRINT AND SIGN NAME TO
 SAME, 104.2.1 FBC.
  
 3} PLEASE SUBMIT A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF THESERVICE
 EQUIPMENT AND THE EMERGENCY EQUIPMENT SO
 THAT COMPLIANCE WITH 225.31 THROUGH
 225.37 CAN BE DETERMINED.
  
 4} PLEASE SUBMIT TWO COPIES OF ALL
 DOCUMENTS PER 104.2.1 FBC.
  
 5} INDICATE THE PRIME MOVER (FUEL
 SOURCE) FOR THE GENERATOR.
  
 6) THE VALUE OF THE PROJECT INDICATED ON
 THE APPLICATION MUST INCLUDE THE VALUE
 OF ALL THE EQUIPMENT BEING INSTALLED AND
 LABOR PER 104.6.5.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved