| 2005-08-29 00:00:00 | *********** UNSAT ************ |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON BOTH TITLE BLOCKS FOR |
| | ARCHITECT AND ENGINEERING FIRM. |
| | PLEASE SEE MISSING LICENSE INFORMAITON |
| | AS REQUIRED UNDER FS 481.219 AND 471.023 |
| | PLEASE SEE ALL INFORMATION REQUIRED PER |
| | 61G1-16.004 (ARCH'S) AND 61G15-23.002 |
| | (ENG'S). |
| | PLEASE SEE THIS IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWERS. |
| | |
| | 2)NOTE: PLEASE SEE GFI PROTECTION |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | COULD NOTLOCATE REFERENCE TO GFI |
| | PROTECTION. |
| | |
| | 3)NOTE: PLEASE PROVIDE LOAD ON EXISTING |
| | MDP WITH ADDED LOADS FROM NEW PANEL. |
| | |
| | *** PLEASE KNOW, PLANS ARE ONLY IN FOR |
| | "PLAN REVIEW " AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |