Plan Review Notes
Plan Review Notes For Permit 05070628
Permit Number 05070628
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-29 00:00:00*********** UNSAT ************
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON BOTH TITLE BLOCKS FOR
 ARCHITECT AND ENGINEERING FIRM.
 PLEASE SEE MISSING LICENSE INFORMAITON
 AS REQUIRED UNDER FS 481.219 AND 471.023
 PLEASE SEE ALL INFORMATION REQUIRED PER
 61G1-16.004 (ARCH'S) AND 61G15-23.002
 (ENG'S).
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWERS.
  
 2)NOTE: PLEASE SEE GFI PROTECTION
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
 COULD NOTLOCATE REFERENCE TO GFI
 PROTECTION.
  
 3)NOTE: PLEASE PROVIDE LOAD ON EXISTING
 MDP WITH ADDED LOADS FROM NEW PANEL.
  
 *** PLEASE KNOW, PLANS ARE ONLY IN FOR
 "PLAN REVIEW " AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  