| 2005-07-26 00:00:00 | *********** UNSAT *********** |
| | |
| | PLEASE KNOW, PLANS HAVE BEEN SUBMITTED |
| | FOR "PLAN REVIEW" ONLY AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | |
| | 1)NOTE: PLEASE SEE MISSING REQUIRED |
| | INFORMATION IN TITLE BLOCK AS REQUIRED |
| | UNDER FAC 61G1-16.004 AND FS 481.219. |
| | THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE PROVIDE LAYOUT FOR NEW |
| | ELECTRICAL TO BE INSTALLED. |
| | PLEASE SHOW ALL NEW CIRCUITING AND |
| | CORRELATE WITH PANEL SCHEDULE(S) TO BE |
| | SUBMITTED. |
| | |
| | 3)NOTE: PLEASE SEE 700.12E FOR ANY |
| | EM/EXT LTS BEING INSTALLED. |
| | |
| | 4)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | REQUIRED GFI PROTECTION FOR KITCHEN IN |
| | OTHER THAN DWELLING UNITS. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE COPY OF OLD/VOIDED SHEETS IS |
| | REQUIRED TO BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESOTATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |