2006-11-04 14:08:04REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P1.1A SHOWS A URINAL IN THE WOMEN'S TOILET ROOM.
 SUBMIT AN APPROVED MANUF. SUBMITTAL FOR THE URINAL.
  
 2. SHT P1.1A SUBMIT A DETAIL FOR THE NEW TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18,
 11-4.19, & 11-4.22 WITH ALL SUBSECTIONS.
  
 3. SHTS P1.1A & P1.1C ALL INDIRECT WASTE SHALL BE
 DRAINED INTO A FLOOR SINK, OR A HUB DRAIN. SECTIONS
 802.3 & 802.3.2. THE TRAP SIZE FOR THESE FIXTURES IS 2"
 AND THE PIPING LAYOUT SHOW 1" AND 1-1/2" PIPING TO
 THESE FIXTURES. TABLE 709.1. PLEASE SHOW MINIMUM SIZES
 TO INDIRECT WASTE RECEPTORS. IDENTIFY ALL INDIRECT
 WASTE RECEPTORS AND SHOW ALL PIPING FROM THE FIXTURES
 TO THE INDIRECT WASTE RECEPTORS. SECTION 104.2.1.
  
 4. SHT P1.1AIDENTIFY THE RISER UPSTREAM OF ITEM #26
 INDIRECT WASTE RECEPTOR IN THE GREASE SYSTEM. IDENTIFY
 THE WATER RISER ON THE COLD WATER LINE PRIOR TO ITEM
 #55. INDICATE WHAT "WWH" WATER LINE SUPPLIES. THIS IS
 NOT SHOWN ON THE ABBREVIATIONS. ALSO IT DOES NOT
 CONNECT TO ANYTHING. PLEASE CLARIFY.SECTION 104.2.1.
  
 5. SHT P1.1A SHEET NOTES 2,3,4 REVISED, BUT ARE NOT
 CLOUDED. COLD WATER LOOP SUPPLYING ITEMS 191,196,55, &
 57 DOES NOT CONNECT TO THE WATER MAIN.PLEASE CLARIFY.
 SECTION 104.2.1.
  
 6. SHT P1.1B CLOUD AND NUMBER REVISIONS. (SEE KEYED
 NOTES 10,11,13 AND SHEET NOTES 2 & 3.CLEANOUTS IN THE
 WALLS TO BE ACCESSIBLE PER SECTION 708.10. INDICATE HOW
 THIS WILL BE COMPLIED WITH.
  
 7. SHT P1.1C WAREWASHER TO CONNECT TO THE SANITARY
 SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL UTILITY CODE
 90-124(7)(B).
  
 8. SHTS P1.1A & P1.1CALL SINKS IN THE FOOD
 PREPARATION AREA SHALL BE DRAINED INTO AN INDIRECT
 WASTE RECEPTOR. SECTION 802.1.
  
 9. SHT P1.1D CLOUD AND NUMBER REVISIONS. (SHEET NOTES &
 NUMBER 1).
  
 10. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2).
 EXPLAIN THE VENT LINES CONNECTING TO THE GAS PIPES. -
 INDICATE THE MATERIAL FOR THE VENTS, (SHALL BE
 NONCOMBUSTABLE). - MORE INFORMATION IS REQUIRED ON THE
 SQUARE BOXES LOCATED IN VARIOUS LOCATIONS IN THE RISER
 DIAGRAM. IF THEY ARE REGULATORS, THEY MUST BE LOCATED
 DOWNSTREAM OF THE SHUT OFF VALVES. SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS. SPECIFY THE MODEL
 NUMBER. REGULATORS SHALL SHOW A LISTING IN
 SPECIFICATIONS SHEETS. ALSO SUBMIT THE FOLLOWING
 INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW
 GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES
 IS ALL BUTITEM #4 THE GRIDDLE.
  
 11. SHT P5.2 DETAIL #1 THE GREASE RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE RISER AND
 THE FLOOR PLAN.
  
 12. SHT P5.2 DETAIL #2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. ALSO DROPS ARE SHOWN AS RISERS,
 AND FULL OPEN VALVES ARE REQUIRED ON ALL WATER
 DOWN-FEED PIPES. SECTIONS 104.2.1, 606.1(4). WATER
 HAMMER ARRESTORS ARE REQUIRED FOR ALL QUICK CLOSING
 VALVES. (WASH MACHINES, ICE MAKERS, DISH WASHERS
 ETC.).
  
 13. SHT P5.2DETAIL #3 RISER DOES NOT REFLECT THE
 FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.LAVS ARE
 NOT VENTED AS SHOWN, AND THE URINAL IS NOT VENTED AS
 SHOWN. SECTION 901.2.1. (SEE RED LINE EXAMPLE ON ONE
 SEET OF PLAN.
  
 14. SHT P5.3 DETAIL #1 SANT. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. (SEE RED LINE MARKING IN ONE
 SET OF PLANS). SECTION 104.2.1.
  
 15. SHT P5.3 DETAIL #2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. NO WATER SHOWN TO THE STEAM
 GENERATOR, OR TO THE MASSAGE SINK. THERE ARE EXTRA LAVS
 AND EXTRA FIXTURES PAST THE W/C'S NOT SHOWN ON THE
 FLOOR PLAN. PIPE ROUTING DIFFERENT. PLEASE CLARIFY.
 PLEASE LABEL THE HOT AND COLD WATER PIPES. SECTION
 104.2.1.
  
 16. SHT P5.3,DETAILS 3 & 4 ARE NOT SHOWN ON SHT
 P1.1A. PLEASE CLARIFY. SECTION 104.2.1. - DETAIL 5 DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE FLOOR PLAN
 AND RISER DIAGRAM. SECTION 104.2.1.
  
 17. SHEETS FS1 THRU FS5 SHALL BE SIGNED/SEALED/DATED,
 AND THE CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE
 TITLE BLOCK OF THE ENGINEER. FAC G1G15-23.002(2), FS
 471.025, AND SECTION 104.2.2. (ONE SET OF FS SHEETS HAS
 BEEN RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA BOARD
 OF PROFESSIONAL ENGINEERS.
  
 18. FS4 ITEM P72 TROUGH DRAIN. NO DRAIN TO THE GREASE
 SYSTEM IS INDICATED. PLEASE CLARIFY. SECTION 104.2.1.
  
 19. FS4 ITEM P82 ON SHT FS2 INDICATES 1/2"CW & A 1"
 INDIRECT WASTE, BUT IS NOT SHOWN ON THE PLUMBING
 CONNECTION SCHEDULE. PLEASE CORRELATE EQUIPMENT
 SCHEDULES. SECTION 104.2.1.
  
 20. ALL GAS HOOD SHEETS 1,2,3 TO BE
 SIGNED/SEALED/DATED. SOME SETS OF SHEETS SUBMITTED ARE
 COPIES OF SIGNED/SEALED/DATED SHEETS. SECTION 104.2.2,
 FAC 61G15-23.002(2) & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS
 TO HELP EXPEDITE REVISIONS.
  