| 2006-11-04 14:08:04 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT P1.1A SHOWS A URINAL IN THE WOMEN'S TOILET ROOM. |
| | SUBMIT AN APPROVED MANUF. SUBMITTAL FOR THE URINAL. |
| | |
| | 2. SHT P1.1A SUBMIT A DETAIL FOR THE NEW TOILET ROOMS |
| | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.18, |
| | 11-4.19, & 11-4.22 WITH ALL SUBSECTIONS. |
| | |
| | 3. SHTS P1.1A & P1.1C ALL INDIRECT WASTE SHALL BE |
| | DRAINED INTO A FLOOR SINK, OR A HUB DRAIN. SECTIONS |
| | 802.3 & 802.3.2. THE TRAP SIZE FOR THESE FIXTURES IS 2" |
| | AND THE PIPING LAYOUT SHOW 1" AND 1-1/2" PIPING TO |
| | THESE FIXTURES. TABLE 709.1. PLEASE SHOW MINIMUM SIZES |
| | TO INDIRECT WASTE RECEPTORS. IDENTIFY ALL INDIRECT |
| | WASTE RECEPTORS AND SHOW ALL PIPING FROM THE FIXTURES |
| | TO THE INDIRECT WASTE RECEPTORS. SECTION 104.2.1. |
| | |
| | 4. SHT P1.1AIDENTIFY THE RISER UPSTREAM OF ITEM #26 |
| | INDIRECT WASTE RECEPTOR IN THE GREASE SYSTEM. IDENTIFY |
| | THE WATER RISER ON THE COLD WATER LINE PRIOR TO ITEM |
| | #55. INDICATE WHAT "WWH" WATER LINE SUPPLIES. THIS IS |
| | NOT SHOWN ON THE ABBREVIATIONS. ALSO IT DOES NOT |
| | CONNECT TO ANYTHING. PLEASE CLARIFY.SECTION 104.2.1. |
| | |
| | 5. SHT P1.1A SHEET NOTES 2,3,4 REVISED, BUT ARE NOT |
| | CLOUDED. COLD WATER LOOP SUPPLYING ITEMS 191,196,55, & |
| | 57 DOES NOT CONNECT TO THE WATER MAIN.PLEASE CLARIFY. |
| | SECTION 104.2.1. |
| | |
| | 6. SHT P1.1B CLOUD AND NUMBER REVISIONS. (SEE KEYED |
| | NOTES 10,11,13 AND SHEET NOTES 2 & 3.CLEANOUTS IN THE |
| | WALLS TO BE ACCESSIBLE PER SECTION 708.10. INDICATE HOW |
| | THIS WILL BE COMPLIED WITH. |
| | |
| | 7. SHT P1.1C WAREWASHER TO CONNECT TO THE SANITARY |
| | SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL UTILITY CODE |
| | 90-124(7)(B). |
| | |
| | 8. SHTS P1.1A & P1.1CALL SINKS IN THE FOOD |
| | PREPARATION AREA SHALL BE DRAINED INTO AN INDIRECT |
| | WASTE RECEPTOR. SECTION 802.1. |
| | |
| | 9. SHT P1.1D CLOUD AND NUMBER REVISIONS. (SHEET NOTES & |
| | NUMBER 1). |
| | |
| | 10. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2). |
| | EXPLAIN THE VENT LINES CONNECTING TO THE GAS PIPES. - |
| | INDICATE THE MATERIAL FOR THE VENTS, (SHALL BE |
| | NONCOMBUSTABLE). - MORE INFORMATION IS REQUIRED ON THE |
| | SQUARE BOXES LOCATED IN VARIOUS LOCATIONS IN THE RISER |
| | DIAGRAM. IF THEY ARE REGULATORS, THEY MUST BE LOCATED |
| | DOWNSTREAM OF THE SHUT OFF VALVES. SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE REGULATORS. SPECIFY THE MODEL |
| | NUMBER. REGULATORS SHALL SHOW A LISTING IN |
| | SPECIFICATIONS SHEETS. ALSO SUBMIT THE FOLLOWING |
| | INFORMATION: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW |
| | GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES |
| | IS ALL BUTITEM #4 THE GRIDDLE. |
| | |
| | 11. SHT P5.2 DETAIL #1 THE GREASE RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE RISER AND |
| | THE FLOOR PLAN. |
| | |
| | 12. SHT P5.2 DETAIL #2 WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. ALSO DROPS ARE SHOWN AS RISERS, |
| | AND FULL OPEN VALVES ARE REQUIRED ON ALL WATER |
| | DOWN-FEED PIPES. SECTIONS 104.2.1, 606.1(4). WATER |
| | HAMMER ARRESTORS ARE REQUIRED FOR ALL QUICK CLOSING |
| | VALVES. (WASH MACHINES, ICE MAKERS, DISH WASHERS |
| | ETC.). |
| | |
| | 13. SHT P5.2DETAIL #3 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN, NOR DOES IT MEET CODE REQUIREMENTS.LAVS ARE |
| | NOT VENTED AS SHOWN, AND THE URINAL IS NOT VENTED AS |
| | SHOWN. SECTION 901.2.1. (SEE RED LINE EXAMPLE ON ONE |
| | SEET OF PLAN. |
| | |
| | 14. SHT P5.3 DETAIL #1 SANT. RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. (SEE RED LINE MARKING IN ONE |
| | SET OF PLANS). SECTION 104.2.1. |
| | |
| | 15. SHT P5.3 DETAIL #2 WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. NO WATER SHOWN TO THE STEAM |
| | GENERATOR, OR TO THE MASSAGE SINK. THERE ARE EXTRA LAVS |
| | AND EXTRA FIXTURES PAST THE W/C'S NOT SHOWN ON THE |
| | FLOOR PLAN. PIPE ROUTING DIFFERENT. PLEASE CLARIFY. |
| | PLEASE LABEL THE HOT AND COLD WATER PIPES. SECTION |
| | 104.2.1. |
| | |
| | 16. SHT P5.3,DETAILS 3 & 4 ARE NOT SHOWN ON SHT |
| | P1.1A. PLEASE CLARIFY. SECTION 104.2.1. - DETAIL 5 DOES |
| | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE FLOOR PLAN |
| | AND RISER DIAGRAM. SECTION 104.2.1. |
| | |
| | 17. SHEETS FS1 THRU FS5 SHALL BE SIGNED/SEALED/DATED, |
| | AND THE CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE |
| | TITLE BLOCK OF THE ENGINEER. FAC G1G15-23.002(2), FS |
| | 471.025, AND SECTION 104.2.2. (ONE SET OF FS SHEETS HAS |
| | BEEN RETAINED FOR POSSIBLE REVIEW BY THE FLORIDA BOARD |
| | OF PROFESSIONAL ENGINEERS. |
| | |
| | 18. FS4 ITEM P72 TROUGH DRAIN. NO DRAIN TO THE GREASE |
| | SYSTEM IS INDICATED. PLEASE CLARIFY. SECTION 104.2.1. |
| | |
| | 19. FS4 ITEM P82 ON SHT FS2 INDICATES 1/2"CW & A 1" |
| | INDIRECT WASTE, BUT IS NOT SHOWN ON THE PLUMBING |
| | CONNECTION SCHEDULE. PLEASE CORRELATE EQUIPMENT |
| | SCHEDULES. SECTION 104.2.1. |
| | |
| | 20. ALL GAS HOOD SHEETS 1,2,3 TO BE |
| | SIGNED/SEALED/DATED. SOME SETS OF SHEETS SUBMITTED ARE |
| | COPIES OF SIGNED/SEALED/DATED SHEETS. SECTION 104.2.2, |
| | FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS |
| | TO HELP EXPEDITE REVISIONS. |
| | |
| | REVIEW BY KEN STEVENS |