| 2006-11-28 13:33:52 | REVSION TO PLAN SHEET M1.1A, M1.1B, M1.1C & M1.1D - | | | PLEASE NOTE THE FOLLOWING: | | | | | | PLAN SHEET M1.1A, M1.1C & M1.1D - APPROVED | | | | | | PLAN SHEET M1.1B - APPROVED WITH THE EXCEPTION TO THE | | | 36" X 8" TRANSFER DUCT FROM ROOM #139 TO RM #146.THIS | | | COORIDOR IS FIRE RATED THEREFORE A FIRE DAMPER WILL BE | | | REQUIRED WHERE DUCT PENETRATES EACH ROOM.SHOULD THE | | | CEILING BE RATED FIRE DAMPERS WILL NOT BE REQUIRED BUT | | | THE LIFE SAFETY AND ARCHITECTURAL PLANS NEED TO BE | | | REVISED TO REFLECT THE CHANGE. |
|