Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop M
Sequence Number 8
Notes
Date Text
2006-11-28 13:33:52REVSION TO PLAN SHEET M1.1A, M1.1B, M1.1C & M1.1D -
 PLEASE NOTE THE FOLLOWING:
  
 PLAN SHEET M1.1A, M1.1C & M1.1D - APPROVED
  
 PLAN SHEET M1.1B - APPROVED WITH THE EXCEPTION TO THE
 36" X 8" TRANSFER DUCT FROM ROOM #139 TO RM #146.THIS
 COORIDOR IS FIRE RATED THEREFORE A FIRE DAMPER WILL BE
 REQUIRED WHERE DUCT PENETRATES EACH ROOM.SHOULD THE
 CEILING BE RATED FIRE DAMPERS WILL NOT BE REQUIRED BUT
 THE LIFE SAFETY AND ARCHITECTURAL PLANS NEED TO BE
 REVISED TO REFLECT THE CHANGE.