| Date |
Text |
| 2007-02-28 16:59:30 | REVISION DENIED |
| | REFERENCE: FBC-2001 FUEL GAS; THE CITY OF WEST PALM |
| | BEACH GAS PERMIT APPLICATION REQUIREMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE. PLEASE NOTE ON THE |
| | SHEET P5.1 THERE IS APPROVED PLUMBING SANITARY AND |
| | WATER RISER DIAGRAMS DATED 4-22-06, BUT ON THE |
| | SUBMITTED REVISION OF SHEET P5.1 THERE IS NO INDICATION |
| | OF THESE SANITARY AND WATER RISER DIAGRAMS. IF IT IS |
| | IMPOSSIBLE TO FIT BOTH THE GAS AND THE PLUMBING ON THE |
| | SAME SHEET IT IS SUGGESTED A NEW SHEET BE DESIGNATED |
| | FOR THE GAS REVISION P5.1A. PLEASE CLARIFY THIS ON THE |
| | RESUBMITTAL. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | THE FOLLOWING ARE FROM THE PREVIOUS REVIEW COMMENTS: |
| | |
| | 1. NO/OK** SHEET P5.1 NEW GAS SERVICE RISER: PLEASE |
| | SUBMIT ALL GAS EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54 AND NFPA 56 AND THE FBC-2001 FUEL GAS |
| | CODE SECTION 402.4. |
| | NOTE: THE SUBMITTED MANUFACTURER SHEETS DO VERIFY THE |
| | BTU LOADS BUT HOWEVER NOT ALL SHEETS INDICATE THAT THE |
| | APPLIANCES ARELISTED. PLEASE REFERENCE THE RED CIRCLE |
| | ON ITEMS #7 AND #8 INDICATING THAT THOSE APPLIANCES ARE |
| | LISTED. THE FOLLOWING IS A LIST OF THE APPLIANCES AND |
| | GAS EQUIPMENT INDICATING WHAT IS REQUIRED. |
| | A} #1- FRYER; NEED LISTING |
| | B} #2 FRYER; NEED LISTING |
| | C} #3- BROILER; NEED LISTING |
| | D} #4-GRIDDLE; NEED LISTING |
| | E} #5-CONVECTION OVEN; NEED LISTING |
| | F} #6-RANGE; NEED LISTING |
| | G} #7-SALAMANDER BROILER; OK |
| | H} #8-PIZZA OVEN; OK |
| | I} #9-STEAMER; NEED LISTING |
| | J} MP REGULATOR (2 PSI TO 0.5 PSI)- MANUFACTURER CUT |
| | SHEET REQUIRED INDICATING MAKE, MODEL NUMBER, AND THIRD |
| | PARTY LISTING. |
| | K} EMERGENCY HOOD SHUT DOWN VALVE- MANUFACTURER CUT |
| | SHEETS REQUIRED INDICATING MAKE, MODEL NUMBER, AND |
| | THIRD PARTY LISTING. |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | |
| | 4. NO**SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | NOTE: THE RESUBMITTED REVISION STILL DOES NOT INDICATE |
| | ALL CORRESPONDING LENGTHS IN LEG #5. THE ONLY LENGTH |
| | INDICATED IS 22'. THE TOTAL DEVELOPED LENGTH OF THE GAS |
| | PIPING FROM THE MP REGULATOR TO THE FARTHEST APPLIANCE |
| | WHICH IS A STEAMER IN THE NEW KITCHEN IS REQUIRED FOR |
| | GAS PLAN REVIEW TO VERIFY CODE COMPLIANCE. |
| | |
| | THE FOLLOWING ARE NEW COMMENTS: |
| | |
| | 5. TYPE OF GAS, (LP OR NATURAL) |
| | NOTE: ON THE APPROVED SHEET P5-1 THE GAS TYPE IS |
| | CLEARLY INDICATED AS NATURAL GAS IN THE GAS SIZING |
| | TABLE CALCULATIONS, BUT ON THE RESUBMITTED REVISION |
| | THERE IS NO GAS TYPE INDICATED. THERE IS A FBC-2004 |
| | FUEL GAS TABLE 402.4(3) REFERENCE WHICH IS FOR NATURAL |
| | GAS BUT THERE IS NO CLEAR INDICATION OF GAS TYPE. IT |
| | CAN NOT BE ASSUMED THAT THE GAS TYPE IS NATURAL GAS. |
| | PLEASE INDICATE THE GAS TYPE ON THE RESUBMITTED |
| | REVISION. |
| | |
| | 6. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | NOTE: ON THE APPROVED SHEET P5-1 IT CLEARLY INDICATES |
| | THE THE EMERGENCY HOOD SHUT OFF VALVE, BUT ON THE |
| | RESUBMITTED REVISION THIS VALVE IS NOT INDICATED. THE |
| | ONLY VALVES INDICATED ON THE RESUBMITTED REVISION ARE A |
| | SHUT OFF VALVE AND A MP REGULATOR (2 PSI TO 0.5 PSI). |
| | PLEASE CLEARLY INDICATE AND IDENTIFY THE SHUT OFF |
| | VALVE, MP REGULATOR, AND ADD THE EMERGENCY SHUT OFF |
| | VALVE ON THE RESUBMITTED REVISION. |
| | |
| | ******IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |