Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop E
Sequence Number 8
Notes
Date Text
2006-09-30 00:00:00*** UNSAT FOR REV #6 **
  
 1) NOTE: PLEASE SEE "PLAN/REVISION FORM
 AS BEING SUBMITTED AND FILLED OUT BY
 CONTRACTOR IS FROM "2001" PLEASE OBTAIN
 NEW FORM ONLINE OR IN OUR OFFICE AS THE
 FEES REPRESENTED ON THESE OLD FORMS ARE
 NO LONGER VALID.
  
 2) NOTE: PLEASE SEE SCOPE OF WORK AT THE
 LOCATION OF THIS JOB WAS ORIGINALLY
 SUBMITTED AS 1.1 MIL AND DUE TO CHANGES
 IN SCOPE AND WORK BEING PERFORMED,
 PLEASE ADJUST THE APPLIED VALUE FOR
 SCOPE OF WORK BASED ON ACTUAL VALUE.
 IT HAS COME TO THE ATTENTION OF THIS
 OFFICE THE VALUE HAS EXCEEDED THE OLD
 VALUE SUBSTANTIALLY. PLEASE ADJUSTOR
 PROVIDE ALL SIGNED CONTRACTS FOR ALL
 TRADES AND SCOPES AS STATED IN THE FBC
 108.3(2004) OR 106.3.5 (2001) .
  
 3) NOTE: PLEASE SEE REVISED RISER IS NOW
 INDICATING A NEW ATS WHICH WAS NOT PART
 OF THE ORIGINAL SCOPE INFACT THE SYSTEM
 WAS STATED AS BEING REMOVED. PLEASE
 SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR
 THIS EQUIPMENT FOR REVIEW. PLEASE ALSO
 KNOW, ANY PERMIT FOR A GENERATOR WILL BE
 REQUIRED TO BE SUBMITTED SEPARATELY AND
 WILL ALSO REQUIRE THE SAME SPECS.
 110.3, 90.7,
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE CORRELATE RISER WITH
 PANEL FOR NEW FEED TO PANEL "N" FROM
 "DPB". PLEASE SEE OCP.
 106.1.2
  
 5) NOTE: PLEASE ALSO KNOW, THE PANEL "N"
 COULD NOT BE LOCATED ON POWER PLANS
 SUBMITTED. THIS REVIEWER HAS LOOKED
 THREE TIMES, AS RISER SHOWS THIS LOCATE
 DON THE FIRST FLR. PLEASE INFORM WHERE
 THIS IS IN A REPSONSE LTR, OR PLEASE
 INDICATE ON PLANS.
 106.1.2
  
 6) NOTE: PLEASE LABEL AND SHOW ALL PANEL
 SIZE ON BOTH RISERS ON 5.1.1, AND 5.2.
 AS OTHERS ARE SHOWN . (100A, 300A ETC ).
  
 7) NOTE: PLEASE SEE PLANS INDICATE A
 "SERVER ROOM"? IS THIS INDEED AN "IT"
 ROOM?
 PLEASE SEE CHAPTER 2 OF NFPA-75 FOR
 CLASSIFICATION REQUIREMENTS AND IF AN IT
 ROOM PLEASE SEE ALL REQUIREMENTS IN
 NFPA-75 AND SEE NEC 645.
  
 *** PLEASE KNOW, PLANS ARE BEING ROUTED
 TO FIRE MARSHAL'S OFFICE FOR FIRE
 REVIEW, PLEASE BE AWARE IF LIGHTING
 PLANS ARE OK WITH FIRE REVIEW, THEN
 THOSE SHEETS WILL BE STAMPED, HOWEVER
 RISER , PANEL SCHEDULE, AND POWER PLANS
 NEED TO BE REVISED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  