| 2006-09-30 00:00:00 | *** UNSAT FOR REV #6 ** |
| | |
| | 1) NOTE: PLEASE SEE "PLAN/REVISION FORM |
| | AS BEING SUBMITTED AND FILLED OUT BY |
| | CONTRACTOR IS FROM "2001" PLEASE OBTAIN |
| | NEW FORM ONLINE OR IN OUR OFFICE AS THE |
| | FEES REPRESENTED ON THESE OLD FORMS ARE |
| | NO LONGER VALID. |
| | |
| | 2) NOTE: PLEASE SEE SCOPE OF WORK AT THE |
| | LOCATION OF THIS JOB WAS ORIGINALLY |
| | SUBMITTED AS 1.1 MIL AND DUE TO CHANGES |
| | IN SCOPE AND WORK BEING PERFORMED, |
| | PLEASE ADJUST THE APPLIED VALUE FOR |
| | SCOPE OF WORK BASED ON ACTUAL VALUE. |
| | IT HAS COME TO THE ATTENTION OF THIS |
| | OFFICE THE VALUE HAS EXCEEDED THE OLD |
| | VALUE SUBSTANTIALLY. PLEASE ADJUSTOR |
| | PROVIDE ALL SIGNED CONTRACTS FOR ALL |
| | TRADES AND SCOPES AS STATED IN THE FBC |
| | 108.3(2004) OR 106.3.5 (2001) . |
| | |
| | 3) NOTE: PLEASE SEE REVISED RISER IS NOW |
| | INDICATING A NEW ATS WHICH WAS NOT PART |
| | OF THE ORIGINAL SCOPE INFACT THE SYSTEM |
| | WAS STATED AS BEING REMOVED. PLEASE |
| | SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR |
| | THIS EQUIPMENT FOR REVIEW. PLEASE ALSO |
| | KNOW, ANY PERMIT FOR A GENERATOR WILL BE |
| | REQUIRED TO BE SUBMITTED SEPARATELY AND |
| | WILL ALSO REQUIRE THE SAME SPECS. |
| | 110.3, 90.7, |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE CORRELATE RISER WITH |
| | PANEL FOR NEW FEED TO PANEL "N" FROM |
| | "DPB". PLEASE SEE OCP. |
| | 106.1.2 |
| | |
| | 5) NOTE: PLEASE ALSO KNOW, THE PANEL "N" |
| | COULD NOT BE LOCATED ON POWER PLANS |
| | SUBMITTED. THIS REVIEWER HAS LOOKED |
| | THREE TIMES, AS RISER SHOWS THIS LOCATE |
| | DON THE FIRST FLR. PLEASE INFORM WHERE |
| | THIS IS IN A REPSONSE LTR, OR PLEASE |
| | INDICATE ON PLANS. |
| | 106.1.2 |
| | |
| | 6) NOTE: PLEASE LABEL AND SHOW ALL PANEL |
| | SIZE ON BOTH RISERS ON 5.1.1, AND 5.2. |
| | AS OTHERS ARE SHOWN . (100A, 300A ETC ). |
| | |
| | 7) NOTE: PLEASE SEE PLANS INDICATE A |
| | "SERVER ROOM"? IS THIS INDEED AN "IT" |
| | ROOM? |
| | PLEASE SEE CHAPTER 2 OF NFPA-75 FOR |
| | CLASSIFICATION REQUIREMENTS AND IF AN IT |
| | ROOM PLEASE SEE ALL REQUIREMENTS IN |
| | NFPA-75 AND SEE NEC 645. |
| | |
| | *** PLEASE KNOW, PLANS ARE BEING ROUTED |
| | TO FIRE MARSHAL'S OFFICE FOR FIRE |
| | REVIEW, PLEASE BE AWARE IF LIGHTING |
| | PLANS ARE OK WITH FIRE REVIEW, THEN |
| | THOSE SHEETS WILL BE STAMPED, HOWEVER |
| | RISER , PANEL SCHEDULE, AND POWER PLANS |
| | NEED TO BE REVISED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |