| Plan Review Notes For Permit 05070627 |
| Permit Number |
05070627 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-08-28 00:00:00 | THE REVISIONS FOR THE FOLLOWING SHEETS | | | HAVE BEEN APPROVED. P1.1A, P1.1B, P1.1D, | | | AND P5.3. | | | | | | REVISION DENIED | | | | | | 1. SHT P5.1 (SEE GAS REVIEW) | | | | | | 2. SHT P5.2, FITTINGS SHALL BE INSTALLED | | | TO GUIDE SEWAGE AND WASTE IN THE | | | DIRECTION OF FLOW. (SEE NEW FLOOR DRAINS | | | IN GREASE RISER. - SEE ALL FIXTURES IN | | | DETAIL #3 FOR BACK TO BACK TOILET ROOMS. | | | - A TRAP IS REQUIRED FOR THE WASH | | | MACHINE, AND THE VENT CAN NOT CONNECT TO | | | THE WASH MACHINE BOX. - THE URINALS ARE | | | NOT VENTED AS SHOWN. - (SEE RED LINE | | | CORRECTION FOR EXAMPLES). SECTIONS | | | 706.3, 901.2.1, 1002.1. | | | | | | 3. NOTE: A REVISION TO FLOOR PLAN MAY BE | | | REQUIRED FOR THE CHANGES SHOWN SO THAT | | | THE FLOOR PLAN AND THE RISER DIAGRAM | | | REFLECT EACH OTHER. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|