2006-08-28 00:00:00THE REVISIONS FOR THE FOLLOWING SHEETS
 HAVE BEEN APPROVED. P1.1A, P1.1B, P1.1D,
 AND P5.3.
  
 REVISION DENIED
  
 1. SHT P5.1 (SEE GAS REVIEW)
  
 2. SHT P5.2, FITTINGS SHALL BE INSTALLED
 TO GUIDE SEWAGE AND WASTE IN THE
 DIRECTION OF FLOW. (SEE NEW FLOOR DRAINS
 IN GREASE RISER. - SEE ALL FIXTURES IN
 DETAIL #3 FOR BACK TO BACK TOILET ROOMS.
 - A TRAP IS REQUIRED FOR THE WASH
 MACHINE, AND THE VENT CAN NOT CONNECT TO
 THE WASH MACHINE BOX. - THE URINALS ARE
 NOT VENTED AS SHOWN. - (SEE RED LINE
 CORRECTION FOR EXAMPLES). SECTIONS
 706.3, 901.2.1, 1002.1.
  
 3. NOTE: A REVISION TO FLOOR PLAN MAY BE
 REQUIRED FOR THE CHANGES SHOWN SO THAT
 THE FLOOR PLAN AND THE RISER DIAGRAM
 REFLECT EACH OTHER. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]