| Plan Review Notes For Permit 05070627 |
| Permit Number |
05070627 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-10-18 13:50:30 | PROVISO: | | | 1.PLAN SHEET M1.1A , M1.1C, AND M1.1D NOTE 15 & M1.1 | | | NOTE 16, INDICATE ALL FLEXIBLE EXHAUST DUCTING SHALL BE | | | HEAVY GAUGE CORREGATED STEEL DUCTWORK. PER 2004 FMC | | | 501.4 EXHAUST DUCTS SHALL BE OF METAL & SUCH | | | CONSTRUCTION SHALL COMPLY WITH CHAPTER 6. | | | | | | 2.PLEASE PROVIDE MANUFACTURE SUBMITTAL DATA ONTHE | | | CORREGATED STEEL DUCT. | | | | | | 3.PLEASE NOTE, CORRIGATED DUCT CAN NOT BE UTILIZED | | | WITH THE DRYER EXHAUST SHALL HAVE A SMOOTH INTERIOR | | | FINISH PER 2004 FMC 504.6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|