2006-10-18 13:50:30PROVISO:
 1.PLAN SHEET M1.1A , M1.1C, AND M1.1D NOTE 15 & M1.1
 NOTE 16, INDICATE ALL FLEXIBLE EXHAUST DUCTING SHALL BE
 HEAVY GAUGE CORREGATED STEEL DUCTWORK. PER 2004 FMC
 501.4 EXHAUST DUCTS SHALL BE OF METAL & SUCH
 CONSTRUCTION SHALL COMPLY WITH CHAPTER 6.
  
 2.PLEASE PROVIDE MANUFACTURE SUBMITTAL DATA ONTHE
 CORREGATED STEEL DUCT.
  
 3.PLEASE NOTE, CORRIGATED DUCT CAN NOT BE UTILIZED
 WITH THE DRYER EXHAUST SHALL HAVE A SMOOTH INTERIOR
 FINISH PER 2004 FMC 504.6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].