| 2007-01-08 14:10:11 | GAS REVISION DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS |
| | PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1.SHEET P5.1 NEW GAS SERVICE RISER: PLEASE SUBMIT ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54 AND NFPA 56 AND THE FBC-2001 FUEL GAS CODE SECTION |
| | 402.4. |
| | NOTE:NEED MANUFACTURER CUT SHEETS FOR ALL NEW GAS |
| | EQUIPMENT INCLUDING THE NEW MP REGULATOR (2PSI TO |
| | 0.5PSI) FOR THE NEW KITCHEN. THE SUBMITTED MANUFACTURER |
| | CUT SHEETS SHALL SHOW A LISTING, MODEL NUMBER, AND BTU |
| | LOAD. MANUFACTURER SHEETS SHALL REFLECT THE BTU LOADS |
| | INDICATED ON THE NEW GAS RISER DIAGRAM. IT IS NOTED ON |
| | THE REVISION SUBMITTAL FORM THAT THE ARCHITECT E-MAILED |
| | THE EQUIPMENT INFORMATION TO K.STEVENS. IN CHECKING |
| | WITH K.STEVENS HE HAS NO RECORD OF THIS INFOMATION. |
| | PLEASE REMEMBER WHEN ITEMS ARE E-MAILED THEY GO THROUGH |
| | A MIS SCREENING PROCESS AND MAY TAKE WEEKS TO CLEAR |
| | THAT PROCESS. IT IS BETTER TO SUBMIT TWO COPIES OF |
| | MANUFACTURER CUT SHEETS WITH THE RESUBMITTAL TO ADVOID |
| | E-MAIL SCREENING PROBLEMS. |
| | |
| | THE FOLLOWING ARE NEW COMMENTS THAT ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 2. SHEET P5.1 NEW GAS SERVICE RISER: THE EXISTING BTU |
| | LOAD AND THE GAS SIZING CALCULATION TABLE INDICATING |
| | THE EXISTING BTU LOADS DO NOT MATCH. ON THE NEW GAS |
| | SERVICE RISER THE EXISTING INDICATES THREE DRYERS AT |
| | 165,000 BTU/HR EACH WITH A TOTAL OF 495,000 BTU/HR, THE |
| | TWO EXISTING KITCHEN MANIFOLDS INDICATE 825,000 BTU/HR |
| | WITH A TOTAL OF 1,650,000 BTU/HR, AND THE THREE |
| | EXISTING BOILERS ARE INDICATED AT 250,000 BTU/HR WITH A |
| | TOTAL OF 750,000 BTU/HR. THE ADDED TOTAL SUM OF THE |
| | EXISTINGBTU'S IS 2,895,000. THE GAS CALCULATION TABLE |
| | INDICATES AN EXISTING BTU OF 2,070,000 WITH A |
| | DIFFERENCE OF 825,000 BTU'S BETWEEN THE TWO. THE TOTAL |
| | BTU'S OF THE EXISTING AND NEW SHOULD BE 3,861,000 NOT |
| | THE INDICATED 3,036,000. PLEASE CORRECT AND CORRELATE |
| | THE BTU'S ON THE RESUBMITTAL. |
| | |
| | 3. SHEET P5.1 NEW GAS RISER: PLEASE CLARIFY IF THIS |
| | SYMBOL IS THE POINT OF DELIVERY (METER) ON THE |
| | RESUBMITTAL. |
| | |
| | 4. WHAT IS THE TOTAL DEVELOPED LENGTH OF THE GAS PIPING |
| | FROM THE MP REGULATOR TO THE FARTHEST APPLIANCE IN THE |
| | NEW KITCHEN. THE ONLY INDICATED LENGTH IS 22'. TO |
| | ADVOID CONFUSSION ALL CUT SECTIONS AND CORRESPONDING |
| | LENGTHS SHOULD BE INDICATED ON THE NEW GAS SERVICE |
| | RISER FOR THE NEW KITCHEN FOR THE RESUBMITTAL. |
| | |
| | ***************IMPORTANT INFORMATION |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |