Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop P
Sequence Number 6
Notes
Date Text
2006-07-15 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 UNSAT
 SEE PREVIOUS PROVISO NOTES BELOW
 DATED 4-26-06 BY KEN STEVENS
  
 PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P1.1B SHOWING
 VENT FOR LIFT STATION & ROUTING OF STEAM
 LINE TO PITCH AWAY FROM THE STEAM
 GENERATOR TO DRAIN THE CONDENSATE. SEE
 SHT 8 0F 19 MANUF. SPECIFICATION SHEETS.
 (I WAS INFORMED BY THE DESIGN
 PROFESSIONAL THAT THE STEAM GENERATOR
 WILL BE MOVED)
  
 REVISION REQUIRED FOR SHT SHT P5.1 FOR
 ALL RED LINE CHANGES TO GAS ISOMETRIC &
 PLUMBING RISERS.
  
 REVISION REQUIRED FOR SHEET P5.2
 INDICATING THAT A STANDPIPE IS REQUIRED
 FOR THE DISH WASHER PER SECTION 802.17.
  
 ALL REVISIONS SHALL BE SUBMITTED AS SOON
 AS POSSIBLE TO AVOID A DELAY IN GETTING
 THE CERTIFICATE OF OCCUPANCY.
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  