| 2006-07-15 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC2001 FUEL GAS CODEPLAN REVIEW |
| | FBC 2001 PLUMBING CODEPLAN REVIEW |
| | FBC 2001 FL ACESSIBILITY CODE PLAN |
| | REVIEW |
| | UNSAT |
| | SEE PREVIOUS PROVISO NOTES BELOW |
| | DATED 4-26-06 BY KEN STEVENS |
| | |
| | PASSED/PROVISO |
| | |
| | REVISION REQUIRED FOR SHT P1.1B SHOWING |
| | VENT FOR LIFT STATION & ROUTING OF STEAM |
| | LINE TO PITCH AWAY FROM THE STEAM |
| | GENERATOR TO DRAIN THE CONDENSATE. SEE |
| | SHT 8 0F 19 MANUF. SPECIFICATION SHEETS. |
| | (I WAS INFORMED BY THE DESIGN |
| | PROFESSIONAL THAT THE STEAM GENERATOR |
| | WILL BE MOVED) |
| | |
| | REVISION REQUIRED FOR SHT SHT P5.1 FOR |
| | ALL RED LINE CHANGES TO GAS ISOMETRIC & |
| | PLUMBING RISERS. |
| | |
| | REVISION REQUIRED FOR SHEET P5.2 |
| | INDICATING THAT A STANDPIPE IS REQUIRED |
| | FOR THE DISH WASHER PER SECTION 802.17. |
| | |
| | ALL REVISIONS SHALL BE SUBMITTED AS SOON |
| | AS POSSIBLE TO AVOID A DELAY IN GETTING |
| | THE CERTIFICATE OF OCCUPANCY. |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |
| | |
| | |
| | |