| Plan Review Notes For Permit 05070627 |
| Permit Number |
05070627 |
|
| Review Stop |
G |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2006-12-02 17:57:14 | REVISION DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM | | | PREVIOUS REVIEW) | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR | | | ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU | | | DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE. | | | ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS | | | RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE | | | INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE | | | SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS | | | APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU | | | LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS | | | INDICATED ON THE GAS RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|