Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop G
Sequence Number 6
Notes
Date Text
2006-12-02 17:57:14REVISION DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM
 PREVIOUS REVIEW)
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR
 ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU
 DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE.
 ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS
 RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE
 INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE
 SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS
 APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU
 LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS
 INDICATED ON THE GAS RISER DIAGRAM.
  