| Plan Review Notes For Permit 05070627 |
| Permit Number |
05070627 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-04-22 00:00:00 | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P1.1B SHOWING | | | VENT FOR LIFT STATION & ROUTING OF STEAM | | | LINE TO PITCH AWAY FROM THE STEAM | | | GENERATOR TO DRAIN THE CONDENSATE. SEE | | | SHT 8 0F 19 MANUF. SPECIFICATION SHEETS. | | | (I WAS INFORMED BY THE DESIGN | | | PROFESSIONAL THAT THE STEAM GENERATOR | | | WILL BE MOVED) | | | | | | REVISION REQUIRED FOR SHT SHT P5.1 FOR | | | ALL RED LINE CHANGES TO GAS ISOMETRIC & | | | PLUMBING RISERS. | | | | | | REVISION REQUIRED FOR SHEET P5.2 | | | INDICATING THAT A STANDPIPE IS REQUIRED | | | FOR THE DISH WASHER PER SECTION 802.17. | | | | | | ALL REVISIONS SHALL BE SUBMITTED AS SOON | | | AS POSSIBLE TO AVOID A DELAY IN GETTING | | | THE CERTIFICATE OF OCCUPANCY. |
|