Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop M
Sequence Number 5
Notes
Date Text
2006-09-12 00:00:00THE FOLLOWING PLAN SHEETS ARE DENIED:
 M1.1A, M1.1B, & M1.1C
 1.PLANS ARE MISSING FIRE DAMPERS AT
 WALL PENETRATIONS.PER 2001 FMC 607.6,
 SPECIFIC LOATION FOR EACH FIRE DAMPER,
 ACCESS DOOR, CEILING DAMPER OR SMOKE
 DAMPER SHALL BE PROPERLY IDENTIFIED ON
 THE BUILDING PLAN.
  