| Plan Review Notes For Permit 05070627 |
| Permit Number |
05070627 |
|
| Review Stop |
G |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-11-04 14:28:42 | REVISION DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2). EXPLAIN | | | THE VENT LINES CONNECTING TO THE GAS PIPES. - INDICATE | | | THE MATERIAL FOR THE VENTS, (SHALL BE NONCOMBUSTABLE). | | | - MORE INFORMATION IS REQUIRED ON THE SQUARE BOXES | | | LOCATED IN VARIOUS LOCATIONS IN THE RISER DIAGRAM. IF | | | THEY ARE REGULATORS, THEY MUST BE LOCATED DOWNSTREAM OF | | | THE SHUT OFF VALVES. SUBMIT MANUF. SPECIFICATIONS FOR | | | THE REGULATORS. SPECIFY THE MODEL NUMBER. REGULATORS | | | SHALL SHOW A LISTING IN SPECIFICATIONS SHEETS. ALSO | | | SUBMIT THE FOLLOWING INFORMATION: | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN. | | | SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW | | | GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES | | | IS ALL BUTITEM #4 THE GRIDDLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|