Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop G
Sequence Number 5
Notes
Date Text
2006-11-04 14:28:42REVISION DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P5.1 NEW GAS SERVICE RISER, (DETAIL #2). EXPLAIN
 THE VENT LINES CONNECTING TO THE GAS PIPES. - INDICATE
 THE MATERIAL FOR THE VENTS, (SHALL BE NONCOMBUSTABLE).
 - MORE INFORMATION IS REQUIRED ON THE SQUARE BOXES
 LOCATED IN VARIOUS LOCATIONS IN THE RISER DIAGRAM. IF
 THEY ARE REGULATORS, THEY MUST BE LOCATED DOWNSTREAM OF
 THE SHUT OFF VALVES. SUBMIT MANUF. SPECIFICATIONS FOR
 THE REGULATORS. SPECIFY THE MODEL NUMBER. REGULATORS
 SHALL SHOW A LISTING IN SPECIFICATIONS SHEETS. ALSO
 SUBMIT THE FOLLOWING INFORMATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. RISER DOES NOT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES FOR ALL SECTIONS OF PIPE
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. THIS IS FOR ALL NEW
 GAS EQUIPMENT, WHICH BY LOOKING AT THE BTU DIFFERENCES
 IS ALL BUTITEM #4 THE GRIDDLE.
  