Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop P
Sequence Number 4
Notes
Date Text
2006-04-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEWS. COMMENT
 NUMBERS SHALL REMAIN THE SAME:
  
 2. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTELS AND RESTURANTS FOR
 REVIEW. ALL SETS OF PLANS SHALL BE
 REVIEWED AND STAMPED WITH TWO PAGE
 "WORKSHEETS" ATTACHED TO EACH SET PRIOR
 TO RESUBMITTING TO CITY WPB FOR REVIEW.
 SECTION 101.4.7. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 RESPONSE NOTED BUT,
 - ONLY ONE SET OF PLANS WAS STAMPED.
 EACH SET OF PLANS REQUIRES A SET OF
 STAMPED PLANS FROM DBPR. ALSO THE TWO
 PAGE "WORKSHEETS" HAVE NOT BEEN ATTACHED
 TO EACH SET OF PLANS FROM DBPR. MINIMUM
 OF TWO SETS OF PLANS REQUIRED. (PLANS
 NOT SIGNED & SEALED SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1) ALL FS SHEETS SHALL COMPLY.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 NO RESPONSE FROM ARCHITECT:
 NEW FS-1 THRU FS-8 SHEETS SUBMITTED WITH
 THE DBPR STAMP. THE TWO PAGE "WORKSHEETS
 WERE NOT ATTACHED TO EACH SET. (I COPIED
 THE WORKSHEETS AND ADDED ONE SET TO OUR
 FILE COPY). PRINTED NAME AND SIGNATURE
 REQUIRED BY SECTION 104.2.1 NOT ON
 SHEETS. PLEASE COMPLY.
  
 3. SHT A1.1 STEAM ROOMS 160 AND 163.
 SUBMIT A DETAIL INDICATING WHERE THE
 STEAM UNITS FOR THESE ROOMS IS LOCATED.
 SHOW ALL PIPEING FOR STEAM LINES SHOWING
 ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS
 IF LOCATED ABOVE THE CEILING AND
 INDICATE HOW THE P/T LINE WILL BE
 INSTALLED. SECTION 104.2.1. (THIS HAS
 BEEN CHANGED TO ONE STEAM ROOM, #154,
 BUT COMMENT STILL NOT ADDRESSED).
 ***************************************
 RESPONSE INDICATES ROOM #152-B IS THE
 LOCATION OF THE STEAM GENERATOR. THIS
 ROOM HAS NOT BEEN LOCATED ON SHT A1.1.
 PLEASE CLARIFY. - 2 DIFFERENT STEAM
 GENERATORS SPECIFICATION SHEETS HAVE
 BEEN SUBMITTED. PLEASE INDICATE WHICH
 GENERATOR WILL BE USED. (SUANATEC (NO
 LISTING SHOWN) OR AMEREC). - SAFETY
 VALVE LINE, DRAIN LINE, AND PAN DRAIN
 LINE DISCHARGE PIPING IS NOT SHOWN.
 PLEASE INDICATE HOW THE PIPING FOR THESE
 WILL BE RUN, AND SHOW COMPLIANCE WITH
 SECTION 701.1. (SEE PAGE 8 OF 19 MANUF.
 SPECIFICATION SHEETS). SHOW TERMINATION
 OF ALL LINES.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: PLANS SHOW A REVISION
 THAT WAS PENCILED IN WHICH IS NOT
 APPROVED. PLEASE RESUBMIT NEW SHEETS FOR
 ALL CHANGES. NO PIPING IS SHOWN FOR THE
 DRAIN LINE FROM THE STEAM GENERATOR AS
 REQUIRED IN PAGE 8 OF 19 IN THE MANUF.
 SPECIFICATION SHEETS.. THERE IS NO
 DRAINAGE PIPING TO COOLING TANK FROM THE
 SANT. SYSTEM.
  
 14. SUBMIT A GREASE ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, ECT.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 SHT P5.2 RESPONSE NOTED BUT,
 THE GREASE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. A TRENCH DRAIN
 AND A FLOOR SINK ARE MISSING. ALSO A DRY
 HORIZONTAL VENT IS SHOWN ON THE END OF
 ONE RUN PAST A FLOOR SINK. SECTIONS
 104.2.1, 905.3 & 905.4. - THE DISHWASHER
 SHALL CONNECT THE THE SANITARY SYSTEM
 PER MUNICIPAL CODE SECTION 90-124(7)(B)
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: HAND DRAWN CHANGES IN
 PENCIL ARE NOT APPROVED. SUBMIT NEW
 SHEETS FOR ALL CHANGES MADE ON THE
 PLANS. EXTEND CHANGE TO PICK UP RISER TO
 SECOND FLOOR. (NUMBER 9). - DISHWASHER
 DELETED FROM THE GREASE SYSTEM IS NOT
 SHOWN ON THE SANITARY. SYSTEM. (SHTS
 P5.1 AND P5.2)
  
 16. A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ***************************************
 SHT P5.1 RESPONSE NOTED BUT,
 AN ISOMETRIC SHOWING PIPING FOR THE NEW
 PIPE WITH ALL PIPE SIZES, VALVES, DRIPS,
 BTU'S SHOWN AT EACH APPLIANCE, ETC. -
 FOR EXISTING PIPING THE SIZE PER TABLE
 402(2) FOR 2,495 CU FT/HR @ 195FT IS 4",
 AND FOR 1,895 CU FT/HR @ 195FT IS 3".
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: SHOW ALL PIPE SIZES PER
 TABLE 402(2) FOR NEW PIPE.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***************************************
 RESPONSE NOTED BUT,
 THE MANUF. SPECIFICATIONS SHEETS FOR
 ITEM2 CHAR-BROILER, ITEM 3 GRIDDLE, AND
 ITEM 6 DOUBLE CONVECTION OVENS DO NOT
 CORRELATE WITH THE BTU'S INDICATED ON
 THE GAS RISER DIAGRAM. INDICATE MODEL
 NUMBER OF EACH NEW GAS APPLIANCE AND
 MAKE SURE IT CORRELATES WITH THE GAS
 RISER DIAGRAM.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: SHT P5.1, THE GAS SIZING
 CALCULATION INFORMATION INDICATES NEW
 GAS EQUIPMENT AT 788,000 BTU'S, THE THE
 GAS FIRE KITCHEN EQUIPMENT LIST
 INDICATES 779,500 BTU'S, BUT THE MANUF.
 SPECIFICATION SHEETS INDICATE 879,500
 BTU'S. PLEASE CORRELATE ALL GAS
 INFORMATION.
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ***************************************
 RESPONSE NOTED BUT,
 THIS SHALL BE SHOWN ON THE RISER DIAGRAM
 WITH THE VALVES & UNION PLACED AS
 INDICATED.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 RESPONSE NOTED: PLEASE INDICATE THAT THE
 EMERGENCY SHUT OFF VALVE SHALL BE
 INSTALLED BETWEEN 42" AND 48" ABOVE THE
 FLOOR PER NFPA-96 SECTION 10.5.1 AND
 NFPA-1 SECTION 50.4.7.1.
  
 ****NEW COMMENT****
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL, AND FS
 553.80.(2)(B)
  
 ****NEW COMMENT*****
 1C. SHT P1.1B REVISED SHEET REQUIRED TO
 REFLECT CHANGES MADE TO RISER DIAGRAM.
 (DRY HORIZONTAL VENT REMOVAL).
 2C. SHT P1.1C REVISED SHEET REQUIRED RO
 REFLECT HAND DRAWN CHANGES MADE TO
 SHEET. (REV-11)
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 SUBMIT ONE COPY OF PLANS FROM PREVIOUS
 REVIEW WHEN RESUBMITTING.
 ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
 OLD VOIDED SHEETS WERE NOT REMOVED, AND
 NEW SHEETS WERE NOT ATTACHED TO THE SET
 OF PLANS. PLEASE SUBMIT TWO SETS OF
 PLANS FOR REVIEW. SECTIONS 104.2.1. AND
 104.2.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved