| Date |
Text |
| 2006-04-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A. FROM PREVIOUS REVIEWS. COMMENT |
| | NUMBERS SHALL REMAIN THE SAME: |
| | |
| | 2. PLANS SHALL BE ROUTED TO DBPR |
| | DIVISION OF HOTELS AND RESTURANTS FOR |
| | REVIEW. ALL SETS OF PLANS SHALL BE |
| | REVIEWED AND STAMPED WITH TWO PAGE |
| | "WORKSHEETS" ATTACHED TO EACH SET PRIOR |
| | TO RESUBMITTING TO CITY WPB FOR REVIEW. |
| | SECTION 101.4.7. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | *************************************** |
| | RESPONSE NOTED BUT, |
| | - ONLY ONE SET OF PLANS WAS STAMPED. |
| | EACH SET OF PLANS REQUIRES A SET OF |
| | STAMPED PLANS FROM DBPR. ALSO THE TWO |
| | PAGE "WORKSHEETS" HAVE NOT BEEN ATTACHED |
| | TO EACH SET OF PLANS FROM DBPR. MINIMUM |
| | OF TWO SETS OF PLANS REQUIRED. (PLANS |
| | NOT SIGNED & SEALED SHALL BEAR THE |
| | PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. SECTION |
| | 104.2.1) ALL FS SHEETS SHALL COMPLY. |
| | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ |
| | NO RESPONSE FROM ARCHITECT: |
| | NEW FS-1 THRU FS-8 SHEETS SUBMITTED WITH |
| | THE DBPR STAMP. THE TWO PAGE "WORKSHEETS |
| | WERE NOT ATTACHED TO EACH SET. (I COPIED |
| | THE WORKSHEETS AND ADDED ONE SET TO OUR |
| | FILE COPY). PRINTED NAME AND SIGNATURE |
| | REQUIRED BY SECTION 104.2.1 NOT ON |
| | SHEETS. PLEASE COMPLY. |
| | |
| | 3. SHT A1.1 STEAM ROOMS 160 AND 163. |
| | SUBMIT A DETAIL INDICATING WHERE THE |
| | STEAM UNITS FOR THESE ROOMS IS LOCATED. |
| | SHOW ALL PIPEING FOR STEAM LINES SHOWING |
| | ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS |
| | IF LOCATED ABOVE THE CEILING AND |
| | INDICATE HOW THE P/T LINE WILL BE |
| | INSTALLED. SECTION 104.2.1. (THIS HAS |
| | BEEN CHANGED TO ONE STEAM ROOM, #154, |
| | BUT COMMENT STILL NOT ADDRESSED). |
| | *************************************** |
| | RESPONSE INDICATES ROOM #152-B IS THE |
| | LOCATION OF THE STEAM GENERATOR. THIS |
| | ROOM HAS NOT BEEN LOCATED ON SHT A1.1. |
| | PLEASE CLARIFY. - 2 DIFFERENT STEAM |
| | GENERATORS SPECIFICATION SHEETS HAVE |
| | BEEN SUBMITTED. PLEASE INDICATE WHICH |
| | GENERATOR WILL BE USED. (SUANATEC (NO |
| | LISTING SHOWN) OR AMEREC). - SAFETY |
| | VALVE LINE, DRAIN LINE, AND PAN DRAIN |
| | LINE DISCHARGE PIPING IS NOT SHOWN. |
| | PLEASE INDICATE HOW THE PIPING FOR THESE |
| | WILL BE RUN, AND SHOW COMPLIANCE WITH |
| | SECTION 701.1. (SEE PAGE 8 OF 19 MANUF. |
| | SPECIFICATION SHEETS). SHOW TERMINATION |
| | OF ALL LINES. |
| | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ |
| | RESPONSE NOTED: PLANS SHOW A REVISION |
| | THAT WAS PENCILED IN WHICH IS NOT |
| | APPROVED. PLEASE RESUBMIT NEW SHEETS FOR |
| | ALL CHANGES. NO PIPING IS SHOWN FOR THE |
| | DRAIN LINE FROM THE STEAM GENERATOR AS |
| | REQUIRED IN PAGE 8 OF 19 IN THE MANUF. |
| | SPECIFICATION SHEETS.. THERE IS NO |
| | DRAINAGE PIPING TO COOLING TANK FROM THE |
| | SANT. SYSTEM. |
| | |
| | 14. SUBMIT A GREASE ISOMETRIC RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, TRAPS, |
| | VENTS, POINTS OF CONNECTION, ECT. |
| | SECTION 104.3.1.1. (NO RESPONSE, NOT |
| | ADDRESSED). |
| | *************************************** |
| | SHT P5.2 RESPONSE NOTED BUT, |
| | THE GREASE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. A TRENCH DRAIN |
| | AND A FLOOR SINK ARE MISSING. ALSO A DRY |
| | HORIZONTAL VENT IS SHOWN ON THE END OF |
| | ONE RUN PAST A FLOOR SINK. SECTIONS |
| | 104.2.1, 905.3 & 905.4. - THE DISHWASHER |
| | SHALL CONNECT THE THE SANITARY SYSTEM |
| | PER MUNICIPAL CODE SECTION 90-124(7)(B) |
| | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ |
| | RESPONSE NOTED: HAND DRAWN CHANGES IN |
| | PENCIL ARE NOT APPROVED. SUBMIT NEW |
| | SHEETS FOR ALL CHANGES MADE ON THE |
| | PLANS. EXTEND CHANGE TO PICK UP RISER TO |
| | SECOND FLOOR. (NUMBER 9). - DISHWASHER |
| | DELETED FROM THE GREASE SYSTEM IS NOT |
| | SHOWN ON THE SANITARY. SYSTEM. (SHTS |
| | P5.1 AND P5.2) |
| | |
| | 16. A SEPARATE GAS PERMIT IS REQUIRED. |
| | SUBMIT THE FOLLOWING INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | *************************************** |
| | SHT P5.1 RESPONSE NOTED BUT, |
| | AN ISOMETRIC SHOWING PIPING FOR THE NEW |
| | PIPE WITH ALL PIPE SIZES, VALVES, DRIPS, |
| | BTU'S SHOWN AT EACH APPLIANCE, ETC. - |
| | FOR EXISTING PIPING THE SIZE PER TABLE |
| | 402(2) FOR 2,495 CU FT/HR @ 195FT IS 4", |
| | AND FOR 1,895 CU FT/HR @ 195FT IS 3". |
| | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ |
| | RESPONSE NOTED: SHOW ALL PIPE SIZES PER |
| | TABLE 402(2) FOR NEW PIPE. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. |
| | *************************************** |
| | RESPONSE NOTED BUT, |
| | THE MANUF. SPECIFICATIONS SHEETS FOR |
| | ITEM2 CHAR-BROILER, ITEM 3 GRIDDLE, AND |
| | ITEM 6 DOUBLE CONVECTION OVENS DO NOT |
| | CORRELATE WITH THE BTU'S INDICATED ON |
| | THE GAS RISER DIAGRAM. INDICATE MODEL |
| | NUMBER OF EACH NEW GAS APPLIANCE AND |
| | MAKE SURE IT CORRELATES WITH THE GAS |
| | RISER DIAGRAM. |
| | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ |
| | RESPONSE NOTED: SHT P5.1, THE GAS SIZING |
| | CALCULATION INFORMATION INDICATES NEW |
| | GAS EQUIPMENT AT 788,000 BTU'S, THE THE |
| | GAS FIRE KITCHEN EQUIPMENT LIST |
| | INDICATES 779,500 BTU'S, BUT THE MANUF. |
| | SPECIFICATION SHEETS INDICATE 879,500 |
| | BTU'S. PLEASE CORRELATE ALL GAS |
| | INFORMATION. |
| | |
| | J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | *************************************** |
| | RESPONSE NOTED BUT, |
| | THIS SHALL BE SHOWN ON THE RISER DIAGRAM |
| | WITH THE VALVES & UNION PLACED AS |
| | INDICATED. |
| | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ |
| | RESPONSE NOTED: PLEASE INDICATE THAT THE |
| | EMERGENCY SHUT OFF VALVE SHALL BE |
| | INSTALLED BETWEEN 42" AND 48" ABOVE THE |
| | FLOOR PER NFPA-96 SECTION 10.5.1 AND |
| | NFPA-1 SECTION 50.4.7.1. |
| | |
| | ****NEW COMMENT**** |
| | 1B. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL, AND FS |
| | 553.80.(2)(B) |
| | |
| | ****NEW COMMENT***** |
| | 1C. SHT P1.1B REVISED SHEET REQUIRED TO |
| | REFLECT CHANGES MADE TO RISER DIAGRAM. |
| | (DRY HORIZONTAL VENT REMOVAL). |
| | 2C. SHT P1.1C REVISED SHEET REQUIRED RO |
| | REFLECT HAND DRAWN CHANGES MADE TO |
| | SHEET. (REV-11) |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | SUBMIT ONE COPY OF PLANS FROM PREVIOUS |
| | REVIEW WHEN RESUBMITTING. |
| | ^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^ |
| | OLD VOIDED SHEETS WERE NOT REMOVED, AND |
| | NEW SHEETS WERE NOT ATTACHED TO THE SET |
| | OF PLANS. PLEASE SUBMIT TWO SETS OF |
| | PLANS FOR REVIEW. SECTIONS 104.2.1. AND |
| | 104.2.1.3. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |