Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop P
Sequence Number 3
Notes
Date Text
2006-04-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. FROM PREVIOUS REVIEWS. COMMENT
 NUMBERS SHALL REMAIN THE SAME:
  
 2. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTELS AND RESTURANTS FOR
 REVIEW. ALL SETS OF PLANS SHALL BE
 REVIEWED AND STAMPED WITH TWO PAGE
 "WORKSHEETS" ATTACHED TO EACH SET PRIOR
 TO RESUBMITTING TO CITY WPB FOR REVIEW.
 SECTION 101.4.7. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 RESPONSE NOTED BUT,
 - ONLY ONE SET OF PLANS WAS STAMPED.
 EACH SET OF PLANS REQUIRES A SET OF
 STAMPED PLANS FROM DBPR. ALSO THE TWO
 PAGE "WORKSHEETS" HAVE NOT BEEN ATTACHED
 TO EACH SET OF PLANS FROM DBPR. MINIMUM
 OF TWO SETS OF PLANS REQUIRED. (PLANS
 NOT SIGNED & SEALED SHALL BEAR THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SECTION
 104.2.1) ALL FS SHEETS SHALL COMPLY.
  
 3. SHT A1.1 STEAM ROOMS 160 AND 163.
 SUBMIT A DETAIL INDICATING WHERE THE
 STEAM UNITS FOR THESE ROOMS IS LOCATED.
 SHOW ALL PIPEING FOR STEAM LINES SHOWING
 ALL PIPE SIZES. SHOW PAN FOR STEAM UNITS
 IF LOCATED ABOVE THE CEILING AND
 INDICATE HOW THE P/T LINE WILL BE
 INSTALLED. SECTION 104.2.1. (THIS HAS
 BEEN CHANGED TO ONE STEAM ROOM, #154,
 BUT COMMENT STILL NOT ADDRESSED).
 ***************************************
 RESPONSE INDICATES ROOM #152-B IS THE
 LOCATION OF THE STEAM GENERATOR. THIS
 ROOM HAS NOT BEEN LOCATED ON SHT A1.1.
 PLEASE CLARIFY. - 2 DIFFERENT STEAM
 GENERATORS SPECIFICATION SHEETS HAVE
 BEEN SUBMITTED. PLEASE INDICATE WHICH
 GENERATOR WILL BE USED. (SUANATEC (NO
 LISTING SHOWN) OR AMEREC). - SAFETY
 VALVE LINE, DRAIN LINE, AND PAN DRAIN
 LINE DISCHARGE PIPING IS NOT SHOWN.
 PLEASE INDICATE HOW THE PIPING FOR THESE
 WILL BE RUN, AND SHOW COMPLIANCE WITH
 SECTION 701.1. (SEE PAGE 8 OF 19 MANUF.
 SPECIFICATION SHEETS). SHOW TERMINATION
 OF ALL LINES.
  
 12. SHT P1.1C KEYED NOTES #3 SUBMIT A
 DETAIL FOR THE VENT CAP. VENT SHALL
 TERMINATE IN COMPLIANCE WITH SECTION
 904.5. SUBMIT AN ELEVATION FOR THE TRASH
 AREA TO DETERMINE IF VENT WILL BE
 APPROVED IN AREA WITHOUT TERMINATING
 ABOVE THE ROOF OF THE TRASH AREA.
 SECTION 104.2.1. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 RESPONSE NOTED BUT,
 NOW THE FLOOR DRAIN HAS NOT VENT AS
 REQUIRED IN SECTION 901.2.1 - FLOOR
 DRAIN SHOULD BE CONNECTED TO THE GREASE
 WASTE SYSTEM SO IT WILL BE EASY TO
 CONNECT TO THE LINE GOING TO THE FLOOR
 DRAIN NEAR THE EMPLOYEE RESTROOM.
  
 13. SUBMIT A SANITARY ISOMETRIC RISER
 DIAGRAM SHOWING ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, AND DFU'S
 AS THEY ACCUMULATE IN THE DRAINAGE
 SYSTEM. SECTION 104.3.1.1. (NO RESPONSE,
 NOT ADDRESSED).
 ***************************************
 SHT P5.1 RESPONSE NOTED BUT,
 PAST BOTH SETS OF W/C'S IS A DRY
 HORIZONTAL VENT. THIS IS NOT APPROVED
 PER SECTIONS 905.3 & 905.4.
  
 14. SUBMIT A GREASE ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, TRAPS,
 VENTS, POINTS OF CONNECTION, ECT.
 SECTION 104.3.1.1. (NO RESPONSE, NOT
 ADDRESSED).
 ***************************************
 SHT P5.2 RESPONSE NOTED BUT,
 THE GREASE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. A TRENCH DRAIN
 AND A FLOOR SINK ARE MISSING. ALSO A DRY
 HORIZONTAL VENT IS SHOWN ON THE END OF
 ONE RUN PAST A FLOOR SINK. SECTIONS
 104.2.1, 905.3 & 905.4. - THE DISHWASHER
 SHALL CONNECT THE THE SANITARY SYSTEM
 PER MUNICIPAL CODE SECTION 90-124(7)(B)
  
 15. SUBMIT A WATER ISOMETRIC RISER
 DIAGRAM, SHOWING ALL PIPE SIZES, VALVES,
 WATER HAMMER ARRESTORS, (REQD. BY
 SECTION 604.9), AND LOCATED NEAR THE
 FIXTURES AS REQUIRED BY PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS, AND
 POINTS OF CONNECTION. SECTION 104.3.1.1.
 (NO RESPONSE, NOT ADDRESSED).
 ***************************************
 SHTS P5.1 & P5.2 RESPONSE NOTED BUT,
 WATER HAMMER ARRESTORS ARE REQUIRED AT
 THE DISH WASHER, AND AT ICE MAKERS PER
 SECTION 604.9. AIR CHAMBERS ARE NOT
 APPROVED AND SHALL BE DELETED FROM THE
 RISER DIAGRAMS INCLUDING DETAIL #4 SHT
 P5.2.
  
 16. A SEPARATE GAS PERMIT IS REQUIRED.
 SUBMIT THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ***************************************
 SHT P5.1 RESPONSE NOTED BUT,
 AN ISOMETRIC SHOWING PIPING FOR THE NEW
 PIPE WITH ALL PIPE SIZES, VALVES, DRIPS,
 BTU'S SHOWN AT EACH APPLIANCE, ETC. -
 FOR EXISTING PIPING THE SIZE PER TABLE
 402(2) FOR 2,495 CU FT/HR @ 195FT IS 4",
 AND FOR 1,895 CU FT/HR @ 195FT IS 3".
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***************************************
 RESPONSE NOTED BUT,
 THE MANUF. SPECIFICATIONS SHEETS FOR
 ITEM2 CHAR-BROILER, ITEM 3 GRIDDLE, AND
 ITEM 6 DOUBLE CONVECTION OVENS DO NOT
 CORRELATE WITH THE BTU'S INDICATED ON
 THE GAS RISER DIAGRAM. INDICATE MODEL
 NUMBER OF EACH NEW GAS APPLIANCE AND
 MAKE SURE IT CORRELATES WITH THE GAS
 RISER DIAGRAM.
  
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ***************************************
 RESPONSE NOTED BUT,
 THIS SHALL BE SHOWN ON THE RISER DIAGRAM
 WITH THE VALVES & UNION PLACED AS
 INDICATED.
  
  
 ****NEW COMMENT****
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL, AND FS
 553.80.(2)(B)
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 SUBMIT ONE COPY OF PLANS FROM PREVIOUS
 REVIEW WHEN RESUBMITTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved