| Plan Review Notes For Permit 05070627 |
| Permit Number |
05070627 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-04-10 00:00:00 | PROVISO: | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION FOR | | | THE HOOD. PLANS SUBMITTED BY CAPTIVE AIR | | | INDICATES SUPPRESSION FOR THE HOOD. | | | PLEASE PROVIDE ADDITIONAL PLANS FOR THE | | | GREASE DUCT.INDICATE DUCT LAYOUT, | | | MATERIAL AND CLEARANCE TO COMBUSTIBLES. | | | INDICATE EXHAUST TERMINTATION PROVIDE | | | DISTANCE FROM PROPERTY LINES AND FRESH | | | AIR INTAKES SHOW COMPLIANCE WITH NFPA 96 | | | & 2001 FMC 506. | | | | | | PLEASE PROVIDE MANUFACTURERS CUT SHEETS | | | & INSTALLATION INTRUCTIONS WITH | | | MECHANICAL PERMIT FOR THE WALK-IN | | | COOLER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|