Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop M
Sequence Number 3
Notes
Date Text
2006-04-10 00:00:00PROVISO:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 WITH MECHANICAL PERMIT APPLICATION FOR
 THE HOOD. PLANS SUBMITTED BY CAPTIVE AIR
 INDICATES SUPPRESSION FOR THE HOOD.
 PLEASE PROVIDE ADDITIONAL PLANS FOR THE
 GREASE DUCT.INDICATE DUCT LAYOUT,
 MATERIAL AND CLEARANCE TO COMBUSTIBLES.
 INDICATE EXHAUST TERMINTATION PROVIDE
 DISTANCE FROM PROPERTY LINES AND FRESH
 AIR INTAKES SHOW COMPLIANCE WITH NFPA 96
 & 2001 FMC 506.
  
 PLEASE PROVIDE MANUFACTURERS CUT SHEETS
 & INSTALLATION INTRUCTIONS WITH
 MECHANICAL PERMIT FOR THE WALK-IN
 COOLER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  