| 2006-08-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | A. SHT P5.1 GAS RISER DIAGRAM REVISION. |
| | MORE INFORMATION REQUIRED. THIS IS A |
| | CHANGE OF GAS APPLIANCES, PIPING LAYOUT, |
| | BTU AMOUNT, AND DEVELOPED LENGTH. PLEASE |
| | SUBMIT THE FOLLOWING: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - THIS IS |
| | SHOWN AS BOTH 150' AND 190'. BY |
| | INDICATING THE LENGTH OF ALL CUT |
| | SECTIONS FROM THE METER THROUGH OUT THE |
| | SYSTEM, TOTAL DEVELOPED LENGTH CAN BE |
| | VERIFIED. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 - THERE |
| | IS MANY NEW GAS APPIANCES ON THIS |
| | REVISION. ALL MANUF. SPECIFICATIONS |
| | SHALL BE SUBMITTED TO VERIFY BTU'S SO |
| | INDICATE MODELS AND EACH APPLIANCE SHALL |
| | SHOW LISTING. |
| | |