Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop G
Sequence Number 3
Notes
Date Text
2006-08-28 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A. SHT P5.1 GAS RISER DIAGRAM REVISION.
 MORE INFORMATION REQUIRED. THIS IS A
 CHANGE OF GAS APPLIANCES, PIPING LAYOUT,
 BTU AMOUNT, AND DEVELOPED LENGTH. PLEASE
 SUBMIT THE FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - THIS IS
 SHOWN AS BOTH 150' AND 190'. BY
 INDICATING THE LENGTH OF ALL CUT
 SECTIONS FROM THE METER THROUGH OUT THE
 SYSTEM, TOTAL DEVELOPED LENGTH CAN BE
 VERIFIED.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 - THERE
 IS MANY NEW GAS APPIANCES ON THIS
 REVISION. ALL MANUF. SPECIFICATIONS
 SHALL BE SUBMITTED TO VERIFY BTU'S SO
 INDICATE MODELS AND EACH APPLIANCE SHALL
 SHOW LISTING.
  
 REVIEW BY KEN STEVENS