| Date |
Text |
| 2006-04-11 00:00:00 | ADD: 2300 PRESIDENTIAL WAY |
| | CONT: CONKLING & LEWIS CONST |
| | TEL: (561)833-4441 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | ***IMPORTANT NOTICE*** |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE SEE THE FIRST PART OF THIS REVIEW |
| | ARE COMMENTS FROM THE FIRST REVIEW NOT |
| | ADDRESSED: |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) COMMENT 4B FROM THE PREVIOUS |
| | REVIEW,STAIRWELL DOORS SHOW NO RATING |
| | NOR DOES ANY STORAGE ROOM DOORS. |
| | RESPONSE: SEE ATTACHED LIFE SAFETY |
| | DRAWINGS. EXISTING STAIRWELL DOORS ARE |
| | FIRE RATED. STORAGE ROOM DOORS ARE NOT |
| | REQUIRED TO BE FIRE RATED PER FBC 704.1.2.2(4).STORAGE |
| | IS FOR |
| | NON-HAZARDOUS MATERIALS, AND DOES NOT |
| | EXCEED 1/3RD OF THE MAJOR OCCUPANCY |
| | FLOOR AREA. |
| | |
| | THE EXIT DOORS MAY BE EXISTING DOORS BUT |
| | WITH THE ASSEMBLY OCCUPANCY EXIT DOORS |
| | REQUIRE A 1 1/2 HR RATING. TABLE |
| | 705.1.2ASSEMBLY BUILDINGS SEE NOTE (2). |
| | ALL EXITS AND STAIRWAYS IN GROUP A AND H OCCUPANCIES |
| | SHALL BE 2 HOURS WITH 1-1/2 |
| | HOUR DOOR ASSEMBLIES. |
| | |
| | THE ABOVE CODE SECTION IS CORRECT FOR |
| | STORAGE ROOMS WITHIN THE OCCUPANCY |
| | (GROUP A, GROUP B, GROUP E, GROUP M AND |
| | GROUP R). THE AREAS IN QUESTION ARE |
| | STORAGE CLOSETS THAT ARE ON AN EXIT |
| | ACCESS CORRIDOR.SEE TABLE 704.2.4 FIRE RESISTANCE |
| | RATING OF EXIT ACCESS |
| | CORRIDORS, FOOTNOTE (4). IN BUILDINGS |
| | PROTECTED THROUGHOUT WITH AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM, EXIT ACCESS |
| | CORRIDOR WALLS NOT REQUIRED TO BE RATED |
| | SHALL, IN CONJUNCTION WITH OPENINGS |
| | THEREIN AND CEILINGS AT WHICH THEY |
| | TERMINATE, RESIST THE PASSAGE OF SMOKE. |
| | |
| | ALTHOUGH THE DOORS NEED NOT HAVE A FIRE |
| | RATING BECAUSE OF THE APPROVED FIRE |
| | SPRINKLERS, WE DO NEED TO HAVE |
| | INFORMATION AS TO HOW THEY WILL RESIST |
| | THE PASSAGE OF SMOKE. |
| | |
| | 3) COMMENT# 11 FROM THE PREVIOUS REVIEW, |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | BROKE DOWN BY SHEET: |
| | 11A) COMPLIED |
| | |
| | 11B) A1.4 DOOR# 142A, DOOR# 157- CLEAR |
| | FLOOR SPACE REQUIRED FOR FIXTURES, |
| | URANIAL, DOOR REMOVED SEE 11-4.17.5 THE |
| | SAME LEVEL OF PRIVACY TO BE PROVIDED TO |
| | THE HANDICAPPED STALL AS THE REST OF THE |
| | RESTROOM.11-2.2 EQUIVALENT FACILITATION. |
| | |
| | 11C) A1.5 DOOR# 154 |
| | |
| | 11D) A1.6 COMPLIED |
| | |
| | 11E) A1.7 DOOR# 214 |
| | |
| | 11F)A1.8 COMPLIED |
| | |
| | 11G) A1.9 COMPLIED |
| | |
| | 4) NEW COMMENT, SHEET A1.8 MULTI PURPOSE |
| | ROOM 232 INDICATES A REVISION# 2 |
| | INDICATING CHANGES TO THIS WALL. PLANS |
| | INDICATE THIS WALL IS A TYPE"H" WHEN |
| | REFERING BACK TO A8.1 FOR WALL RATINGS |
| | THIS WALL IS A INTERIOR FOLDING |
| | PARTITION. NOT A 2 HR RATED WALL? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |