2006-04-11 00:00:00ADD: 2300 PRESIDENTIAL WAY
 CONT: CONKLING & LEWIS CONST
 TEL: (561)833-4441
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
 ***IMPORTANT NOTICE***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE SEE THE FIRST PART OF THIS REVIEW
 ARE COMMENTS FROM THE FIRST REVIEW NOT
 ADDRESSED:
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT 4B FROM THE PREVIOUS
 REVIEW,STAIRWELL DOORS SHOW NO RATING
 NOR DOES ANY STORAGE ROOM DOORS.
 RESPONSE: SEE ATTACHED LIFE SAFETY
 DRAWINGS. EXISTING STAIRWELL DOORS ARE
 FIRE RATED. STORAGE ROOM DOORS ARE NOT
 REQUIRED TO BE FIRE RATED PER FBC 704.1.2.2(4).STORAGE
 IS FOR
 NON-HAZARDOUS MATERIALS, AND DOES NOT
 EXCEED 1/3RD OF THE MAJOR OCCUPANCY
 FLOOR AREA.
  
 THE EXIT DOORS MAY BE EXISTING DOORS BUT
 WITH THE ASSEMBLY OCCUPANCY EXIT DOORS
 REQUIRE A 1 1/2 HR RATING. TABLE
 705.1.2ASSEMBLY BUILDINGS SEE NOTE (2).
 ALL EXITS AND STAIRWAYS IN GROUP A AND H OCCUPANCIES
 SHALL BE 2 HOURS WITH 1-1/2
 HOUR DOOR ASSEMBLIES.
  
 THE ABOVE CODE SECTION IS CORRECT FOR
 STORAGE ROOMS WITHIN THE OCCUPANCY
 (GROUP A, GROUP B, GROUP E, GROUP M AND
 GROUP R). THE AREAS IN QUESTION ARE
 STORAGE CLOSETS THAT ARE ON AN EXIT
 ACCESS CORRIDOR.SEE TABLE 704.2.4 FIRE RESISTANCE
 RATING OF EXIT ACCESS
 CORRIDORS, FOOTNOTE (4). IN BUILDINGS
 PROTECTED THROUGHOUT WITH AN APPROVED
 AUTOMATIC SPRINKLER SYSTEM, EXIT ACCESS
 CORRIDOR WALLS NOT REQUIRED TO BE RATED
 SHALL, IN CONJUNCTION WITH OPENINGS
 THEREIN AND CEILINGS AT WHICH THEY
 TERMINATE, RESIST THE PASSAGE OF SMOKE.
  
 ALTHOUGH THE DOORS NEED NOT HAVE A FIRE
 RATING BECAUSE OF THE APPROVED FIRE
 SPRINKLERS, WE DO NEED TO HAVE
 INFORMATION AS TO HOW THEY WILL RESIST
 THE PASSAGE OF SMOKE.
  
 3) COMMENT# 11 FROM THE PREVIOUS REVIEW,
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
 BROKE DOWN BY SHEET:
 11A) COMPLIED
  
 11B) A1.4 DOOR# 142A, DOOR# 157- CLEAR
 FLOOR SPACE REQUIRED FOR FIXTURES,
 URANIAL, DOOR REMOVED SEE 11-4.17.5 THE
 SAME LEVEL OF PRIVACY TO BE PROVIDED TO
 THE HANDICAPPED STALL AS THE REST OF THE
 RESTROOM.11-2.2 EQUIVALENT FACILITATION.
  
 11C) A1.5 DOOR# 154
  
 11D) A1.6 COMPLIED
  
 11E) A1.7 DOOR# 214
  
 11F)A1.8 COMPLIED
  
 11G) A1.9 COMPLIED
  
 4) NEW COMMENT, SHEET A1.8 MULTI PURPOSE
 ROOM 232 INDICATES A REVISION# 2
 INDICATING CHANGES TO THIS WALL. PLANS
 INDICATE THIS WALL IS A TYPE"H" WHEN
 REFERING BACK TO A8.1 FOR WALL RATINGS
 THIS WALL IS A INTERIOR FOLDING
 PARTITION. NOT A 2 HR RATED WALL?
  