| 2006-01-17 00:00:00 | DENIED: |
| | THE FOLLOWING COMMENT FROM REVIEW DATED |
| | 8-2-05 BY HAROLD MOSER WAS NOT |
| | ADDRESSED: |
| | |
| | COMMENT 3:PLEASE PROVIDE INFORMATION |
| | ON THE PIPING MATERIAL TO BE INSTALLED |
| | FOR NEW CHILLED WATER LINES AS INDICATED |
| | ON PLAN SHEET M1.1AKEYED NOTE #4. |
| | |
| | PLEASE PROVIDE DETAIL FOR NEW CHILLED |
| | WATER LINES.INDICATE ANY NEW SHUT |
| | OFF/ISOLATION, CONTROL/BYPASS VALVES |
| | THAT MAY BE INSTALLED. |
| | |
| | **************NEW COMMENT************ |
| | 1.PLEASE PROVIDE ENGINEER'S LICENCE |
| | NUMBER ON PLANS PER FAC61G15-23.002. |
| | |
| | 2.PLAN SHEET M8.3 A/C UNIT SCHEDULE |
| | THE NOTE DOES NOT INDICATE AHU-13 HAVING |
| | A DUCT SMOKE DETECTOR.SYSTEMS THAT ARE |
| | GREATER THAN 2,000 CFM ARE REQUIRED TO |
| | HAVE FAN SHUTDOWN BY DUCT SMOKE |
| | DETECTORS WITH NOTIFICATION TO |
| | ALARM/STROBE IN NORMALLY OCCUPIED AREAS |
| | PER 2004 FMC 606.2.1. |
| | |
| | 3.ADDITIONAL PERMITS REQUIRED FOR |
| | WALK-IN COOLERS/FREEZERS, HOODS AND FIRE |
| | SUPPRESSION.PLEASE PROVIDE PLANS AND |
| | MANUFACTURER'S SUBMITTAL DATA WITH |
| | PERMIT APPLICATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |
| | |
| | |
| | |