2006-01-04 00:00:001. ALL EXIT DOORS SHALL BE PROPERLY
 IDENTIFIED BY ILLUMINATED EXIT SIGNS.
  
 2. SUFFICIENT EMERGENCY LIGHTS SHALL BE
 PROVIDED THROUGHOUT THE CLUBHOUSE.
  
 3. IT APPEARS THAT NO PREVIOUS COMMENTS
 FROM FIRE RESCUE WERE ADDRESSED.
  
 4. THE RELOCATION OF THE FIRE ALARM
 CONTROL PANEL, DIALER, AND NEW EQUIPMENT
 REQUIRES A PERMIT.
  
 5. ANY PENETRATIONS IN REQUIRED FIRE
 WALS MUST BE PROPERLY SEALED IN AN
 APPROVED MANNER.
  
 6. THE RELOCATION OF THE FIRE ALARM
 PANEL AND DIALER SHOULD BE SCHEDULED TO
 PREVENT LONG PERIODS OF WITHOUT
 PROTECTION.
  
 7. SEPERATE PLANS AND PERMITS REQUIRED
 FOR THE REQUIRED HOOD, DUCT, AND FIRE
 SUPPRESSION SYSTEM.
  
 8. COULD NOT LOCATE ANY INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 9. ANY NEW SOFFITS SHALL NOT INTERFERE
 WITH ANY REQUIRED FIRE SPRINKLER HEADS.
  
 10. DOOR SCHEDULE ON PAGE A5.1 DOES NOT
 DISPLAY ANY FIRE RATING.
  