| Plan Review Notes For Permit 05070627 |
| Permit Number |
05070627 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-01-04 00:00:00 | 1. ALL EXIT DOORS SHALL BE PROPERLY | | | IDENTIFIED BY ILLUMINATED EXIT SIGNS. | | | | | | 2. SUFFICIENT EMERGENCY LIGHTS SHALL BE | | | PROVIDED THROUGHOUT THE CLUBHOUSE. | | | | | | 3. IT APPEARS THAT NO PREVIOUS COMMENTS | | | FROM FIRE RESCUE WERE ADDRESSED. | | | | | | 4. THE RELOCATION OF THE FIRE ALARM | | | CONTROL PANEL, DIALER, AND NEW EQUIPMENT | | | REQUIRES A PERMIT. | | | | | | 5. ANY PENETRATIONS IN REQUIRED FIRE | | | WALS MUST BE PROPERLY SEALED IN AN | | | APPROVED MANNER. | | | | | | 6. THE RELOCATION OF THE FIRE ALARM | | | PANEL AND DIALER SHOULD BE SCHEDULED TO | | | PREVENT LONG PERIODS OF WITHOUT | | | PROTECTION. | | | | | | 7. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR THE REQUIRED HOOD, DUCT, AND FIRE | | | SUPPRESSION SYSTEM. | | | | | | 8. COULD NOT LOCATE ANY INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 9. ANY NEW SOFFITS SHALL NOT INTERFERE | | | WITH ANY REQUIRED FIRE SPRINKLER HEADS. | | | | | | 10. DOOR SCHEDULE ON PAGE A5.1 DOES NOT | | | DISPLAY ANY FIRE RATING. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|