Plan Review Notes
Plan Review Notes For Permit 05070627
Permit Number 05070627
Review Stop B
Sequence Number 2
Notes
Date Text
2006-01-26 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070627
 ADD: 2300 PRESIDENTIAL WAY
 CONT: CONKLING & LEWIS CONST
 TEL: (561)833-4441
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 ***IMPORTANT NOTICE***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE SEE THE FIRST PART OF THIS REVIEW
 ARE COMMENTS FROM THE FIRST REVIEW NOT
 ADDRESSED:
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2A)INDICATE BUILDING TYPE:
 601.2.1 EVERY BUILDING SHALL BE
 CLASSIFIED BY THE BUILDING OFFICIAL
 INTO ONE OF THE TYPES OF CONSTRUCTION
 AS SET FORTH IN THIS SECTION.
  
 TYPE ITYPE V
 TYPE II1-HOUR PROTECTED
 TYPE IIIUNPROTECTED
 TYPE IV TYPE VI
 1-HOUR PROTECTED1-HOUR PROTECTED
 UNPROTECTED UNPROTECTED
  
 2B) A TYPE V BUILDING IS EITHER 1-HR
 RATED OR UNPROTECTED, BUT NOT BOTH.
  
 2C)IF BUILDING IS FIRE SPRINKLERED OR
 NOT?IF FIRE SPRINKLERED PROVIDE FIRE
 SPRINKLER PLANS. BUILDING DESIGN
 INDICATES FIRE SPRINKLERED BUT NO PLANS
 HAVE BEEN SUBMITTED.
  
 2D) PROVIDE TOTAL SQ FT PER FLOOR? WERE
 AREA INCREASES TAKEN?
  
 3) PROVIDE LIFE SAFETY PLAN, ALSO
 PROVIDE THE SEATING FOR RESTARAUNTS OR
 OCCUPANT LOAD WILL BE TAKEN AS 15 NET,
 FOR PREFUNCTION AREAS 7 NET.
  
 4A) PLANS SHEET A5.1 DOOR SCHEDULE, NO
 FIRE RATINGS ASSIGNED TO DOORS, ALSO SEE
 DOOR RATING AS "B" OR "C" SEE TABLE
 705.1.2. FOR MINUTE & HR RATING.
 M1106.4 MACHINE ROOMS REQUIRE 45 MIN
 OPENING PROTECTION.
 M1106.4 OPENING PROTECTIVES. OPENING
 PROTECTION BETWEEN THE MACHINERY
 ROOM AND OTHER OCCUPIED SPACES SHALL BE
 APPROVED, SELF-CLOSING, TIGHT-
 FITTING FIRE DOORS WITH A MINIMUM
 FIRE-RESISTANCE RATING OF 3/4 HOUR.
  
 4B) STAIRWELL DOORS SHOW NO RATING NOR
 DOES ANY STORAGE ROOMS.
  
 4C) DOOR SCHEDULE DOESN'T INDICATE
 HARDWARW GROUPINGS, MAY HAVE MORE
 COMMENTS WITH ACCESSIBILITY.
  
 5) 11-4.3.11 AREAS OF RESCUE ASSISTANCE.
 11-4.3.11.1 LOCATION AND CONSTRUCTION
 PLANS DO NOT PROVIDE FIRE SPRINKLERS,
 PROVIDE DETAILS FOR REQUIRED AREA OF
 RESCUE ASSISTANCE IF FIRE SPRINKLER
 PLANS ARE NOT PROVIDED. THIS BUILDING
 CAN NOT TAKE AREA INCREASES FOR FIRE
 SPRINKLERED BUILDINGS PER TABLE 500
 WITHOUT SPRINKLER PLANS.
  
  
 6) SHEET A8.2 PLANS INDICATE THE USE OF
 IMPACT GLAZING FOR WINDOWS & DOORS, NO
 WIND PRESSURE INFORMATION PROVIDED.
 PROVIDE ELEVATIONS WITH THE ASSOCIATED
 POSITIVE & NEGATIVE PRESSURES INTERIOR
 AND END ZONES.
  
 7) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS- NOT SHOWN MAY HAVE MORE THAN
 ONE TYPE
 B) DOORS ALL EXTERIOR DOORS BEING
 REPLACED, SOLID OR GLAZED
 C) EXTERIOR LOUVERS
 D) MULLIONS
  
 9)OK
  
 10A) IT APPEARS THAT STAIRWELL# 7 HAS
 BEEN DELETED.
 10B) NEW COMMENT 11-4.4.2 HEAD ROOM.
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS,
 AILES OR OTHER CIRCULATION SPACES SHALL
 HAVE 80 INCHES MINIMUM CLEAR HEAD ROOM
 (SEE FIGURE 8(A)). IF VERTICAL CLEARENCE
 OF AN AREA ADJOINING AN ACCESSIBLE ROUTE
 IS REDUCED TO LESS THAN 80 IN. (NOMINAL
 DIMENSION), A BARRIER TO WARN BLIND OR
 VISUALLY- IMPARED PERSONS SHALL BE
 PROVIDED. (SEE FIGURE 8(C-1)).
  
 11)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. CLEAR 18"LOCK SIDE.
 EVEN IF DOORS ARE EXISTING,
 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 BROKE DOWN BY SHEET:
 11A) A1.3 DOOR# 115, DOOR # 130- NO
 HARDWARE SCHEDULE, SEE INTERIOR SIDE
  
 11B) A1.4 DOOR# 142A, DOOR# 157- CLEAR
 FLOOR SPACE REQUIRED FOR FIXTURES,
 URANIAL
  
 11C) A1.5 DOOR# 154
  
 11D) A1.6 DOOR# 119, DOOR# 125
  
 11E) A1.7 DOOR# 214
  
 11F) A1.8 DOOR# 241
  
 11G) A1.9 DOOR# 240, DOOR# 241
  
 11H) DOOR# 200, DOOR# 203, DOOR# 204
 DOOR# 218AB,C&D, DOOR# 222C NOT LABELED
 DOOR# 224-A NOT LABELED
  
 12) OK.
  
 13) 1204.2 SURROUNDING MATERIALS. THE
 WALLS AND FLOORS OF ALL PUBLIC REST
 ROOMS SHALL BE LINED WITH NONABSORBENT
 MATERIAL TO A HEIGHT OF 4 FT (1219
 MM) ABOVE THE FLOOR.
  
 14) PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION TABLE 803.3.
  
 *********
 NEW COMMENTS
 15)A1.4 ROOM BY DOOR# 141 DOESN'T SHOW
 USEAGE?
  
 16) A1.6 ROOM# 133 INDICATES IT IS A
 STORAGE AND MECHANICAL ROOM?
  
 17) A1.6 LOCATED IN KITCHEN THERE IS A
 ROOM NO LABELED, POSSIBLY A WALK IN
 COOLER?
  
 18) A1.6 STAIRWELL# 2 FIRST FLOOR OPENS
 AND DUMPS UOT RIGHT IN FRONT OF THE
 GENERATOR. THE EXIT DISCHARGE MUST
 MAINTAIN A SAFE ROUTE TO THE RIGHT OF
 WAY.
  
 19) ALL STAIRWELLS DO NOT INDICATE
 GAURDRAILS AT THE TOP OF THE LANDING.
  
 20) A1.9 DOOR# 233 IS MISSING
 INFORMATION ON GAURDRAIL?
  
 ADDITIONAL COMMENTS MAY APPEAR SINCE A
 COMPLETE SET OF PLANS WERE NOT PROVIDED
 FOR THIS REVIEW.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved