| 2008-05-04 16:15:36 | ** DENIED REVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THE GENERATOR WAS NOT INCLUDED IN |
| | THE BASE BUILDING INTERIOR RENOVATIONS AND MAY NOT BE A |
| | REVISION TO THE RENOVATION PERMIT. |
| | ALL WORK SHALL BE UNDER SEPARATE PERMITS, PLANS, FEES. |
| | PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR NEW |
| | GENERATOR TO INCLUDE ALL REQUIRED FOR MINIMUM DESIGN |
| | PER NFPA-70, 101, 72, 110 AS APPLICABLE. |
| | PLEASE SEE FBC CHAPTER 27, NFPA-70, NFPA-110 FOR |
| | REQUIRED SYSTEMS. |
| | PLEASE SUBMIT COMPLETE LAYOUT OF THE LOCATION ON PLANS |
| | FOR SITE, ELEVATION IF LOCATED IN FLOOD ZONE, |
| | STRUCTURAL CONNECTIONS ETC |
| | PLEASE SEE NFPA-110, CHAPTER 6 AND 7. |
| | |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE PROPOSED GENERATOR, TRANSFER EQUIPMENT, |
| | FUEL TANKS ETC. |
| | PLEASE KNOW THE FUEL TANK WILL BE REVIEW BY OTHER |
| | TRADES. |
| | 90.7, 110.3, ETC |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE KNOW FOR INFORMATION PLEASE SEE NEC |
| | 225.31-225.39, 702.11, 700.12B6, 70111B5. AS THE SYSTEM |
| | IS NOT SPECIFIED ALL THREE CODED SECTIONS WERE GIVEN. |
| | ALL APPLY TO THE SAME REQUIREMENT. |
| | |
| | 4) NOTE: PLEASE KNOW IT IS IMPORTANT TO KNOW AS THERE |
| | ARE NUMEROUS ITEMS MISSING FOR CODE COMPLIANCE REVIEW, |
| | WHEN ALL PLANS, DOCUMENTS ETC ARE SUBMITTED FOR REVIEW |
| | THERE MAY VERY WELL BE NEW REVIEW COMMENTS WHICH CAN |
| | NOT POSSIBLY BE MADE AT THIS TIME. THE PLANS SUBMITTED |
| | ARE NOT COMPLETE AND IS MISSING A SUBSTANTIAL AMOUNT OF |
| | INFORMATION NEEDED FOR REVIEW. |
| | |
| | 5) NOTE: PLEASE KNOW THE COMPLETE VALUE FOR PROPOSED |
| | SCOPE OF WORK SHALL BE DECLARED ON PERMIT APPLICATION. |
| | PLEASE KNOW WORK FOR |
| | WALLS/SLAB/GENERATOR/EQUIPMENT/ELECTRICAL ETC SHALL ALL |
| | BE INCLUDE WHETHER OR NOT ANY OF THESE ITEMS SUCH AS |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | THIS INCLUDES GENERATOR, ATS, TANK, ETC. |
| | FBC 108.3 |
| | |
| | 6) NOTE: PLANS AS SUBMITTED DO NOT COORDINATE. |
| | FOR EXAMPLE: |
| | PLEASE SEE PLANS SHOWS NEW CHAIN LINK FENCE AROUND THE |
| | GENERATOR YET NOTES CLEARLY STATE THERE IS GOING TO BE |
| | A NEW BLOCK ENCLOSURE? |
| | PLEASE BE SURE ALL MINIMUM CLEARANCES AND VENTILATION |
| | PER NFPA-110 CHAPTER 7 AND NEC 110.26 ARE MET ALONG |
| | WITH MINIMUM REQUIRED PER MANUFACTURE. |
| | |
| | 7) NOTE: WHEN NEW PLANS ARE COMPLETED PLEASE BE SURE |
| | THE ADDRESS OF THE PROJECT COORDINATES WITH THE APPLIED |
| | LOCATION. |
| | FOR EXAMPLE: |
| | PLEASE SEE PLANS CALL FOR 230 PRESIDENTIAL WAY NOT |
| | 2300. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | FBC 106.5 |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |