2008-05-04 16:15:36** DENIED REVIEW **
  
  
 1) NOTE: PLEASE KNOW THE GENERATOR WAS NOT INCLUDED IN
 THE BASE BUILDING INTERIOR RENOVATIONS AND MAY NOT BE A
 REVISION TO THE RENOVATION PERMIT.
 ALL WORK SHALL BE UNDER SEPARATE PERMITS, PLANS, FEES.
 PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR NEW
 GENERATOR TO INCLUDE ALL REQUIRED FOR MINIMUM DESIGN
 PER NFPA-70, 101, 72, 110 AS APPLICABLE.
 PLEASE SEE FBC CHAPTER 27, NFPA-70, NFPA-110 FOR
 REQUIRED SYSTEMS.
 PLEASE SUBMIT COMPLETE LAYOUT OF THE LOCATION ON PLANS
 FOR SITE, ELEVATION IF LOCATED IN FLOOD ZONE,
 STRUCTURAL CONNECTIONS ETC
 PLEASE SEE NFPA-110, CHAPTER 6 AND 7.
  
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 2) NOTE: PLEASE SUBMIT COMPLETE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED GENERATOR, TRANSFER EQUIPMENT,
 FUEL TANKS ETC.
 PLEASE KNOW THE FUEL TANK WILL BE REVIEW BY OTHER
 TRADES.
 90.7, 110.3, ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE KNOW FOR INFORMATION PLEASE SEE NEC
 225.31-225.39, 702.11, 700.12B6, 70111B5. AS THE SYSTEM
 IS NOT SPECIFIED ALL THREE CODED SECTIONS WERE GIVEN.
 ALL APPLY TO THE SAME REQUIREMENT.
  
 4) NOTE: PLEASE KNOW IT IS IMPORTANT TO KNOW AS THERE
 ARE NUMEROUS ITEMS MISSING FOR CODE COMPLIANCE REVIEW,
 WHEN ALL PLANS, DOCUMENTS ETC ARE SUBMITTED FOR REVIEW
 THERE MAY VERY WELL BE NEW REVIEW COMMENTS WHICH CAN
 NOT POSSIBLY BE MADE AT THIS TIME. THE PLANS SUBMITTED
 ARE NOT COMPLETE AND IS MISSING A SUBSTANTIAL AMOUNT OF
 INFORMATION NEEDED FOR REVIEW.
  
 5) NOTE: PLEASE KNOW THE COMPLETE VALUE FOR PROPOSED
 SCOPE OF WORK SHALL BE DECLARED ON PERMIT APPLICATION.
 PLEASE KNOW WORK FOR
 WALLS/SLAB/GENERATOR/EQUIPMENT/ELECTRICAL ETC SHALL ALL
 BE INCLUDE WHETHER OR NOT ANY OF THESE ITEMS SUCH AS
 EQUIPMENT IS OWNER SUPPLIED.
 THIS INCLUDES GENERATOR, ATS, TANK, ETC.
 FBC 108.3
  
 6) NOTE: PLANS AS SUBMITTED DO NOT COORDINATE.
 FOR EXAMPLE:
 PLEASE SEE PLANS SHOWS NEW CHAIN LINK FENCE AROUND THE
 GENERATOR YET NOTES CLEARLY STATE THERE IS GOING TO BE
 A NEW BLOCK ENCLOSURE?
 PLEASE BE SURE ALL MINIMUM CLEARANCES AND VENTILATION
 PER NFPA-110 CHAPTER 7 AND NEC 110.26 ARE MET ALONG
 WITH MINIMUM REQUIRED PER MANUFACTURE.
  
 7) NOTE: WHEN NEW PLANS ARE COMPLETED PLEASE BE SURE
 THE ADDRESS OF THE PROJECT COORDINATES WITH THE APPLIED
 LOCATION.
 FOR EXAMPLE:
 PLEASE SEE PLANS CALL FOR 230 PRESIDENTIAL WAY NOT
 2300.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.5
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved