Notes
Date Text
2006-12-02 17:54:56REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SHTS P1.1A, P1.1C & P5.2 VENTING FOR FLOOR DRAINS
 AND FLOOR SINKS. EVERY DRY VENT SHALL RISE VERTICALLY
 TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION
 905.4. VENTS BELOW THE SLAB ARE NOT APPROVED.- FLOOR
 DRAIN AND FLOOR SINK IN THE KITCHEN VESTIBULE AREA
 SHALL CONNECT TO THE VENTED BRANCH LINE SEPARATELY, OR
 SHALL BE VENTED.SECTION 912.2.2. -FLOOR DRAIN
 UPSTREAM OF FIXTURE 55 ON THE GREASE DRAINAGE SYSTEM
 SHOWS A VENT ON THE FLOOR PLAN THAT IS NOT SHOWN ON THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION 104.2.1. -
 MAXIMUM 3 FU ON A 2" COMBINATION WASTE AND VENT BRANCH
 LINE. TABLE 912.3.CHECK BRANCH LINES WITH TWO OR MORE
 FLOOR DRAINS AND/OR FLOOR SINKS WITH A 2" BRANCH LINE.
  
 2. (FROM PREVIOUS REVIEW) SUBMIT A DETAIL FOR THE NEW
 TOILET ROOMS SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.18, 11-4.19 AND 11-4.22 WITH ALL SUBSECTIONS.
 ****RESPONSE NOTED, THIS HAS NOT BEEN ADDRESSED.
  
 3. SHTS P1.1C & P5.2 FIXTURE 1.1 IS NOT VENTED AS SHOWN
 ON THE FLOOR PLAN, NOR ON THE RISER DIAGRAM. PLEASE
 IDENTIFY FIXTURE 1.1. SECTIONS 905.4 AND 104.2.1.
  
 4. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM
 PREVIOUS REVIEW)
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR
 ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU
 DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE.
 ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS
 RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE
 INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE
 SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS
 APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU
 LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS
 INDICATED ON THE GAS RISER DIAGRAM.
  
 5. SHT P5.2 WATER RISER DIAGRAMS INDICATE WATER HAMMER
 ARRESTORS INSTALLED UPSIDE DOWN. PLEASE SUBMIT MANUF.
 SPECIFICATION/INSTALLATION REQUIREMENTS FOR THE WATER
 HAMMER ARRESTORS INDICATING APPROVED INSTALLATION
 METHOD. SECTION 104.2.1. ALL WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS. (ALSO SEE SHT
 P5.3 DETAIL 2 WATER RISER DIAGRAM).
  
 6. SHT P5.3 DETAIL 1 SANT RISER DIAGRAM. HLAV IN WOMENS
 TOILET ROOM IS NOT VENTED AS SHOWN. ("S" TRAP). SEE RED
 LINE EXAMPLE FOR CORRECTION. SECTIONS 901.2.1 & 1002.3.
 - FLOOR DRAIN NOT VENTED PROPERLY. SECTION 905.4.
  
 7. PLEASE INDICATE WHAT THE LARGE AMOUNT OF SHEETS
 SUBMITTED WITH PLANS ARE FOR. IF THESE ARE SUBMITTALS,
 SUBMIT THEM SEPARATELY. IF THEY WERE TO REPRESENT THE
 GAS APPLIANCE MANUF. SPECIFICATIONS REQUIRED, THEY ARE
 NOT APPROVED. THE MANUF. SHEETS FOR THE GAS APPLIANCES
 SHALL SHOW A LISTING, THE MODEL NUMBER INDICATED AND
 THE BTU LOAD INDICATED THAT REFLECTS THE GAS RISER
 DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS
 TO HELP EXPEDITE THE REVISIONS. (THIS WAS NOT ADDRESS
 WHEN THESE REVISIONS WERE SUBMITTED).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  