| 2006-12-02 17:54:56 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1. SHTS P1.1A, P1.1C & P5.2 VENTING FOR FLOOR DRAINS |
| | AND FLOOR SINKS. EVERY DRY VENT SHALL RISE VERTICALLY |
| | TO A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE |
| | HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. SECTION |
| | 905.4. VENTS BELOW THE SLAB ARE NOT APPROVED.- FLOOR |
| | DRAIN AND FLOOR SINK IN THE KITCHEN VESTIBULE AREA |
| | SHALL CONNECT TO THE VENTED BRANCH LINE SEPARATELY, OR |
| | SHALL BE VENTED.SECTION 912.2.2. -FLOOR DRAIN |
| | UPSTREAM OF FIXTURE 55 ON THE GREASE DRAINAGE SYSTEM |
| | SHOWS A VENT ON THE FLOOR PLAN THAT IS NOT SHOWN ON THE |
| | RISER DIAGRAM. PLEASE CORRELATE. SECTION 104.2.1. - |
| | MAXIMUM 3 FU ON A 2" COMBINATION WASTE AND VENT BRANCH |
| | LINE. TABLE 912.3.CHECK BRANCH LINES WITH TWO OR MORE |
| | FLOOR DRAINS AND/OR FLOOR SINKS WITH A 2" BRANCH LINE. |
| | |
| | 2. (FROM PREVIOUS REVIEW) SUBMIT A DETAIL FOR THE NEW |
| | TOILET ROOMS SHOWING COMPLIANCE WITH SECTIONS 11-4.16, |
| | 11-4.18, 11-4.19 AND 11-4.22 WITH ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, THIS HAS NOT BEEN ADDRESSED. |
| | |
| | 3. SHTS P1.1C & P5.2 FIXTURE 1.1 IS NOT VENTED AS SHOWN |
| | ON THE FLOOR PLAN, NOR ON THE RISER DIAGRAM. PLEASE |
| | IDENTIFY FIXTURE 1.1. SECTIONS 905.4 AND 104.2.1. |
| | |
| | 4. SHT P5.1 NEW GAS SERVICE RISER. (COMMENT #10 FROM |
| | PREVIOUS REVIEW) |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | THE FBC-2001 FUEL GAS CODE SECTION 402.2. THIS IS FOR |
| | ALL THE NEW GAS EQUIPMENT, WICH BY LOOKING AT THE BTU |
| | DIFFERENCES IS ALL BUT ITEM #4, THE GRIDDLE. |
| | ****RESPONSE NOTED, BUT IN ORDER TO APPROVE THE GAS |
| | RISER DIAGRAM, AND ULTIMATELY ISSUE THE GAS PERMIT, THE |
| | INFORMATION IS REQUIRED. PLEASE SUBMIT ALL MANUFACTURE |
| | SHEETS WITH THE GAS RISER DIAGRAM FOR APPROVAL. ALL GAS |
| | APPLIANCES SHALL SHOW A LISTING, MODEL NUMBER AND BTU |
| | LOAD. MANUF. SHEETS SHALL REFLECT THE BTU LOADS |
| | INDICATED ON THE GAS RISER DIAGRAM. |
| | |
| | 5. SHT P5.2 WATER RISER DIAGRAMS INDICATE WATER HAMMER |
| | ARRESTORS INSTALLED UPSIDE DOWN. PLEASE SUBMIT MANUF. |
| | SPECIFICATION/INSTALLATION REQUIREMENTS FOR THE WATER |
| | HAMMER ARRESTORS INDICATING APPROVED INSTALLATION |
| | METHOD. SECTION 104.2.1. ALL WATER HAMMER ARRESTORS |
| | SHALL BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. (ALSO SEE SHT |
| | P5.3 DETAIL 2 WATER RISER DIAGRAM). |
| | |
| | 6. SHT P5.3 DETAIL 1 SANT RISER DIAGRAM. HLAV IN WOMENS |
| | TOILET ROOM IS NOT VENTED AS SHOWN. ("S" TRAP). SEE RED |
| | LINE EXAMPLE FOR CORRECTION. SECTIONS 901.2.1 & 1002.3. |
| | - FLOOR DRAIN NOT VENTED PROPERLY. SECTION 905.4. |
| | |
| | 7. PLEASE INDICATE WHAT THE LARGE AMOUNT OF SHEETS |
| | SUBMITTED WITH PLANS ARE FOR. IF THESE ARE SUBMITTALS, |
| | SUBMIT THEM SEPARATELY. IF THEY WERE TO REPRESENT THE |
| | GAS APPLIANCE MANUF. SPECIFICATIONS REQUIRED, THEY ARE |
| | NOT APPROVED. THE MANUF. SHEETS FOR THE GAS APPLIANCES |
| | SHALL SHOW A LISTING, THE MODEL NUMBER INDICATED AND |
| | THE BTU LOAD INDICATED THAT REFLECTS THE GAS RISER |
| | DIAGRAM. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE RETURN THE RED LINED, MARKED UP SET OF REVISIONS |
| | TO HELP EXPEDITE THE REVISIONS. (THIS WAS NOT ADDRESS |
| | WHEN THESE REVISIONS WERE SUBMITTED). |
| | |
| | REVIEW BY KEN STEVENS |