| 2007-05-21 16:48:11 | REVISION TO MECHANICAL PLANS PAGES M1.1A, M1.1B, M1.1C, |
| | AND M8.2. |
| | *** DENIED *** |
| | 1) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT. |
| | FIRM'S NAME. SEE FAC 61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| | SEE CITY WPB AMEND. 106.1.1). |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 2) SEE YELLOW HIGH LIGHTS ON PAGE M1.1A NORTH ENTRY |
| | LOBBY #129 SHOWS TWO WALLS THAT ARE NOT ON THE BUILDING |
| | PLANS PAGE A1.1, THE WALLS ARE STOPPING AIR FROM |
| | RETURNING TO THE AIR HANDLER, PLEASE CORRECT AND IF |
| | NEEDED REVISE BUILDING PLANS. |
| | |
| | 3) SEE YELLOW HIGH LIGHT ON PAGE M1.1B CORRIDOR #140 |
| | SHOWS TWO RETURN AIR GRILLS IN CORRIDOR, IF THE WALLS |
| | ARE RATED THAN THE AIR CAN NOT RETURN TO THE AIR |
| | HANDLER, PLEASE CORRECT. ALSO SEE THE SUPPLY AIR GRILL |
| | SHOWS THE FIRE DAMPER AT THE GRILL NOT AT THE FIRE |
| | WALL, PLEASE CORRECT. |
| | |
| | 4) SEE YELLOW HIGH LIGHT ON PAGE M1.1C RESTROOMS #114 |
| | AND 115 AND MANICURE ROOM #121 EXHAUST FAN GRILLS NEED |
| | TO SHOW THE CFM'S. ALSO SEE EMPLOYEE RESTROOM #104 |
| | EXHAUST FAN GRILL NEEDS TO SHOW CFM'S IT APPEARS TO BE |
| | 300 CFM'S AT THIS TIME, PLEASE CORRECT. |
| | |
| | 5 PAGE M8.2 ONLY NEEDS THE TITLE BLOCK CORRECTED AS THE |
| | OTHER PAGES DO (SEE NOTE #1). |
| | |
| | MECHANICAL PLAN REVIEW BY; |